8. Clearances

Heaters must be installed so that the clearances in the table are provided for combus- tion air space, inspection and service, and for proper spacing from combustible con- struction. Clearance to combustibles is defined as the minimum distance from the heater to a surface or object that is necessary to ensure that a surface temperature of 90°F above the surrounding ambient temperature is not exceeded.

Clearances - inches/mm

Size

Top

Flue

Front

Rear

Disconnect

Side

Bottom

Connector

(Access Panel)

Side

 

 

 

 

 

 

 

 

 

inches

mm

inches

mm

inches

mm

inches

mm

inches

mm

inches

mm

inches

mm

400

12

305

6

152.4

18

457

2

50.8

18

457

2

50.8

60

1524

800

12

305

6

152.4

18

457

2

50.8

18

457

2

50.8

60

1524

1200

12

305

6

152.4

18

457

2

50.8

18

457

2

50.8

60

1524

9.Combustion Air

FIGURE 2 - Definition of Confined Space and Required Openings for Combustion Air

Confined Space:

A space whose volume is less than 50 cubic feet per 1000 BTUH of the installed appliance input rating

(3)

(1)

(2)

Confined

Space

(3) (1) (2)

This heater must be supplied with the air that enters into the combustion process and is then vented to the outdoors. Sufficient air must enter the equipment location to replace that exhausted through the heater vent system. In the past, the infiltration of outside air assumed in heat loss calculations (one air change per hour) was assumed to be sufficient. However, current construction methods using more insulation, vapor barriers, tighter fitting and gasketed doors and windows, weather-stripping, and/or mechanical exhaust fans may now require the introduction of outside air through wall openings or ducts.

The requirements for combustion and ventilation air depend upon whether the heater is located in a confined or unconfined space. An "unconfined space" is defined as a space whose volume is not less than 50 cubic feet per 1000 BTUH of the installed appliance. Under ALL conditions, enough air must be provided to ensure there will not be a negative pressure condition within the equipment room or space.

WARNING: A Model LDAP power-vented heater is designed to take combustion air from the space in which the heater is installed and is not designed for connection to outside combustion air intake ducts. Connecting outside air ducts voids the warranty and could cause hazardous operation. See Hazard Levels, page 2.

Combustion Air Requirements for a Heater Located in a Confined Space

Do not install a heater in a confined space without providing wall openings leading to and from the space. Provide openings near the floor and ceiling for ventilation and air for combustion as shown in FIGURE 2, depending on the combustion air source as noted in Items 1, 2, and 3 below.

Add total BTUH of all appliances in the confined space and divide by figures below for square inch free area size of each (top and bottom) opening.

1.Air from inside the building - openings 1 square inch free area per 1000 BTUH. Never less than 100 square inches free area for each opening. See (1) in FIGURE 2.

2.Air from outside through duct - openings 1 square inch free area per 2000 BTUH. See (2) in FIGURE 2.

3.Air direct from outside - openings 1 square inch free area per 4000 BTUH. See

(3) in FIGURE 2.

NOTE: For further details on supplying combustion air to a confined space, see the National Fuel Gas Code ANSI Z223.1a (latest edition).

Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 6

Image 6
Contents Table of Contents Reznor Model LdapGeneral Installation Codes WarrantyHazard Levels of Warnings in this Manual Switches Uncrating and Preparation High Altitude OperationModel One Technical DataDimensions DownflowModel LDAP800 and Model LDAP1200 Clearances Combustion AirClearances inches/mm Heater Location Mounting Height Heater Throw All ModelsThrow feet and meters Sound Data Hanging or Mounting the Heater and Installing LouversHeater Location cont’d Location RecommendationsWall Mounting Guidelines for Wall Mounting Model Ldap HeatersGas Piping and Pressures Installing Heater and Louvers cont’dInstalling Louvers Sizing Gas SupplyHorizontal Supply Valve Outlet or Orifice Pressure SettingGas Connection Size Vertical SupplyGas PressuresCont’d Supply Wiring Burners Electrical Supply ConnectionsDisconnect Switch Electrical Supply and Connections cont’dThermostat and Connections CL7 Connections for Model Ldap 1200 with Option Thermostat and Connections cont’dMultiple Heater Control Option CL31 and Option CL32 CL1, CL2, CL3, CL7, or CL18Limit Control Combustion Air Proving Pressure SwitchesPressure Switch Settings High Limit ControlIgnition System Normal Heat Cycle Operating Sequence Abnormal Heat Cycle FunctionsIgnition System cont’d Gas Valves Fault Modes LockoutFan Motor Wiring Fan MotorsWiring Diagrams Wiring DiagramWhite = Neutral Black = High Heat Speed Wiring Diagrams cont’d Above control wiring isAbove control wiring is Line VoltageType of Vent Pipe VentingVenting Requirements VerticalJoints and Sealing Joints and Sealing cont’d Venting cont’dVenting Requirements cont’d Double Vent Wall Pipe With Sealant Pipe RunWall Ft 1M Minimum 305 mm Check Installation and Startup Check the installation prior to startup Heater StartupOperating Instructions Operating Sequence Check installation after startup Vent System Testing ProcedureWay Discharge Louvers, Option CD32 Nozzles Maintenance ScheduleDimensions NozzleHeat Exchanger Maintenance Burner Maintenance Location of ControlsRe-Install the Burner Burner Maintenance cont’dInspect and Clean the Burner Instructions to Re-Install the Burner Refer to FigureIgnitor Flame Sensor Burner OrificesHeat Section Venter Motor and Wheel MeasurementFan Blades Heat Section Venter Motor and Wheel cont’dMain Venter Motor and Wheel Models 800 and 1200 only GuardsCombustion Air Pressure Switches Operating Gas ValvesTroubleshooting Vent SystemGeneral Troubleshooting Problem Probablecause RemedyGeneral Troubleshooting cont’d No heat Heater

LDAP 1200 specifications

The Thomas & Betts LDAP 1200 is a cutting-edge lighting control system designed specifically to enhance energy efficiency, reduce operational costs, and promote flexibility in various lighting applications. Ideal for commercial and industrial environments, the LDAP 1200 integrates advanced technologies to create a robust solution for managing lighting systems.

One of the standout features of the LDAP 1200 is its intelligent control capabilities. With occupancy sensors and daylight harvesting technology, the system can automatically adjust lighting levels based on the presence of people and the amount of natural light available. This results not only in energy savings but also in improved occupant comfort.

The LDAP 1200 is designed for easy installation and configuration. Its modular design allows for scalability, making it suitable for both small spaces and large commercial projects. The system supports a variety of lighting types, including LED, fluorescent, and incandescent, ensuring compatibility with existing infrastructure.

User-friendly interfaces are another key characteristic of the LDAP 1200. Operating through a centralized control panel or a mobile app, users can easily monitor and adjust lighting settings, schedule operations, and receive real-time feedback. This level of control empowers facility managers to respond quickly to changing needs and optimize lighting performance.

In terms of energy management, the LDAP 1200 integrates seamlessly with building management systems (BMS), enabling complex scheduling and reporting functions. The system collects data on energy usage, helping organizations to track performance and implement strategies to further reduce consumption.

Durability and reliability are paramount in industrial applications, and the LDAP 1200 does not disappoint. Constructed with high-quality materials, the system is designed to withstand everyday wear and tear. Its robust architecture ensures that it will function effectively in various environmental conditions.

In summary, the Thomas & Betts LDAP 1200 is a versatile and efficient lighting control solution that plays a critical role in enhancing energy efficiency, reducing costs, and improving user experience. With its intelligent control features, user-friendly interfaces, and compatibility with various lighting types, the LDAP 1200 represents a significant advancement in lighting technology, making it a smart choice for modern facilities seeking to optimize their lighting systems.