Bard WH183, WH242 Wiring LOW Voltage Wiring, Compressor Cutoff Thermostat and Outdoor Thermostats

Page 13

WIRING – LOW VOLTAGE WIRING

230/208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TAP

RANGE

240

253

- 216

208

220

- 187

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

Nine (9) wires should be run from thermostat subbase to the 24V terminal board in the unit. A nine conductor, 18 gauge copper, color-coded thermostat cable is recommended.. The connection points are shown in Figure 7.

TABLE 3

THERMOSTAT WIRE SIZE

 

 

 

Maximum

Transformer

 

 

Distance

VA

FLA

Wire Gauge

In Feet

 

 

 

 

55

2.3

20 gauge

45

 

 

18 gauge

60

 

 

16 gauge

100

 

 

14 gauge

160

 

 

12 gauge

250

 

 

 

 

COMPRESSOR CUTOFF THERMOSTAT AND OUTDOOR THERMOSTATS

Heat pump compressor operation at outdoor temperatures below 0° F are neither desirable not advantageous in terms of efficiency. Since most equipment at time of manufacture is not designated for any specific destination of the country and most of the equipment is installed in areas not approaching the lower outdoor temperature range, the compressor cutoffs are not factory installed.

Outdoor thermostats are available to hold off various banks of electric heat until needed as determined by outdoor temperature. The set point of either type of thermostat is variable with geographic region and sizing of the heating equipment to the structure. Utilization of the Heating Application Data and the heat loss calculation of the building are useful in determining the correct set points.

See Figure 8 for compressor cutoff and outdoor thermostat wiring.

FIGURE 8 – COMPRESSOR CUTOFF AND OUTDOOR THERMOSTAT WIRING

4 & 8 KW 1 Phase – 6 KW 3 Phase

MIS-409

Manual 2100-373

Page 11

Image 13
Contents WH183 WH242 Installation Instructions Wall Mounted Package Heat PumpContents Getting Other Information and Publications Heat Pump Wall Mount Model Nomenclature Wall Mount General InformationShipping Damage GeneralUnit Dimensions Wire Size Electrical SpecificationsDuct Work Filters Fresh AIR Damper AssemblyFresh AIR Intake Condensate DrainWall Mounting Information Installation InstructionsMounting the Unit Mounting Instructions Wall Mounting Instructions Common Wall Mounting Installations Unit 24V Terminal Board Wiring Main PowerThermostat Wire Size Wiring LOW Voltage WiringCompressor Cutoff Thermostat and Outdoor Thermostats Heat Anticipation Thermostat Indicator LampsCompressor Malfunction Light Wall Thermostat and Subbase CombinationsService Hints Important Installer NoteStart UP Crankcase HeatersDefrost Cycle Pressure Service PortsDefrost Control Board Solid State Heat Pump Control Troubleshooting Procedure TroubleshootingTroubleshooting Temperature F VS Resistance R of Temperature Sensor Checking Temperature Sensor Outside Unit CircuitRemoval of the FAN Shroud FAN Blade Setting DimensionsRefrigerant Charge Indoor Blower PerformancePressure Table Heating Pressure Table CoolingReturn Air Model Pressure 100 105 110 115WH183-A WH242-A WH242-B WH242-C Optional Accessories

WH183, WH242 specifications

The Bard WH242 and WH183 are innovative heating and cooling systems designed to meet the demands of various residential and commercial applications. These units are recognized for their efficiency, reliability, and advanced technologies, making them popular choices among property owners and HVAC professionals.

The Bard WH242 is a high-capacity unit that delivers optimal temperature control, making it ideal for larger spaces. It boasts a robust design and a powerful compressor, which work together to provide consistent heating and cooling throughout the year. The unit features a multi-speed blower, helping to distribute air evenly while also enhancing comfort levels. Energy efficiency is a key highlight, as the WH242 complies with Energy Star standards, which means it consumes less energy while offering high performance.

On the other hand, the Bard WH183 is designed for smaller spaces without compromising on comfort or efficiency. It incorporates a compact design, making it easier to install in tight spaces. Despite its size, the WH183 is equipped with advanced technologies that ensure reliable operation. Like the WH242, this unit also features a multi-speed blower, which aids in maintaining a steady and comfortable indoor climate.

Both models utilize high-quality insulation and advanced refrigerant management systems that minimize energy loss. The systems are also equipped with advanced diagnostics, allowing for easier maintenance and troubleshooting. This means that HVAC technicians can quickly identify potential issues, ensuring that the units remain operational with minimal downtime.

Overall, the Bard WH242 and WH183 represent cutting-edge solutions for temperature management. Their design emphasizes durability, efficiency, and user-friendliness, appealing to a wide range of customers. With their combination of power, compactness, and advanced features, these units are well-suited for diverse applications, including schools, offices, and residential homes. Whether for heating in the winter or cooling in the summer, Bard's commitment to quality and innovation is evident in both the WH242 and WH183 models, making them a smart choice for efficient climate control.