CHECKING GAS

CONNECTIONS

WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

CAUTION: Make sure exter- nal regulator has been installed between propane supply and heater. See guidelines under Con- necting to Gas Supply, page 10.

Test Pressures Equal To or Less Than 1/2 PSIG

1.Close manual shutoff valve (see Fig- ure 15).

2.Pressurize supply piping system by ei- ther using compressed air or opening propane supply tank valve.

3.Check all joints from propane supply tank to manual shutoff valve (see Fig- ure 15). Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

4.Correct all leaks at once.

Manual

Shutoff Open

Valve

Closed

Figure 15 - Manual Shutoff Valve

Pressure Testing Heater Gas Connections

1.Open manual shutoff valve (see Fig- ure 15).

2.Open propane supply tank valve.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from manual shutoff valve to control valve (see Figure 16). Apply mixture of liquid soap and wa- ter to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 14 and 15). Check all other in- ternal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, page 15).

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG

1.

Disconnect heater and its individual

 

manual shutoff valve from gas supply

 

piping system. Pressures in excess of

 

1/2 psig will damage heater regulator.

2.

Cap off open end of gas pipe where

 

manual shutoff valve was connected.

3.

Pressurize supply piping system by ei-

 

ther using compressed air or

 

opening propane supply tank valve.

4.

Check all joints of gas supply piping

 

system. Apply mixture of liquid soap

 

and water to gas joints. Bubbles form-

 

ing show a leak.

5.

Correct all leaks at once.

Propane Supply Tank

Manual

Control Valve

Shutoff

Location

Valve

 

6. Re-connect heater and manual shutoff

valve to gas supply. Check re-con-

nected fittings for leaks.

Figure 16 - Checking Gas Joints

12

104256

Image 12
Contents FLAME-MAX What to do if YOU Smell GASDesign Log DesignSafety Information Vanguard FLAME-MAX Unvented PROPANE/LP GAS LOG HeaterProduct Features Product IdentificationLocal Codes UnpackingDetermining AIR Flow for Heater Location Unusually Tight ConstructionConfined and Unconfined Space Determining if You Have a Confined or Unconfined SpaceVentilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Smaller than that defined as anInstallation InstallationCheck GAS Type Minimum Fireplace Clearance To Combustible MaterialsIf Not Using Mantel If Using MantelMinimum Non Combustible Material Clearances Determining Minimum Mantel Clear- ance When using a Hood Mantel ClearancesDeterming Minimum Mantel Clearance Installing Damper Clamp Accessory for Vented Operation Installing Heater Base AssemblyInstallation Items Needed Floor ClearancesConnecting to GAS Supply Standard Oak Log ChassisGolden Oak and Birch Model Chassis External Regulator With Vent Pointing Down Pressure Testing Heater Gas Connections Pressure Testing Gas Supply Piping SystemChecking GAS Connections Test Pressures Equal To or Less Than 1/2 PsigInstalling Logs For Vintage Oak ModelFor Golden Oak or Birch Models For Your Safety Read Before Lighting Operating HeaterLighting Instructions Cleaning and Maintenance Inspecting BurnersTroubleshooting Observed Problem Possible Cause RemedyRefer to Air for Combustion and Venti Top Gas leak. See Warning statement atSpecifications Replacement PartsAccessories Technical ServiceIllustrated Parts Breakdown FLAME-MAX Vintage OAK Models VYS18P and VYS24PODS Pilot Parts List KEY Part Number for VYS18P VYS24P Description QTY1A* 1A Parts List Warranty Information