FRESH AIR FOR

COMBUSTION AND

VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

__________________ Btu/Hr

 

 

 

 

Gas water heater*

__________________ Btu/Hr

Example:

 

 

 

Gas furnace

__________________ Btu/Hr

Gas water heater

 

40,000

Btu/Hr

 

 

 

Vented gas heater

__________________ Btu/Hr

Vent-free heater

+

20,000

Btu/Hr

Gas fireplace logs

__________________ Btu/Hr

Total

=

60,000

Btu/Hr

Other gas appliances*

+ __________________ Btu/Hr

 

 

 

 

Total

= __________________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 60,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

Continued

104331

5

Image 5
Contents BLUE FLAME VENT-FREENATURAL GAS HEATER OWNER’S OPERATION AND INSTALLATION MANUALWHAT TO DO IF YOU SMELL GAS Do not try to light any applianceWARNINGS SAFETY INFORMATIONBLUE FLAME NATURAL GAS HEATER SAFETY DEVICE PRODUCT FEATURESPRODUCT IDENTIFICATION LOCAL CODESPROVIDING ADEQUATE VENTILATION FRESH AIR FOR COMBUSTION AND VENTILATIONUnusually Tight Construction Confined and Unconfined SpaceFRESH AIR FOR COMBUSTION AND VENTILATION ContinuedDETERMINING FRESH-AIRFLOW FOR HEATER LOCATION Ventilation Air From Inside Building VENTILATION AIRVentilation Air From Outdoors To AtticINSTALLATION ITEMS INSTALLATIONLOCATING HEATER CHECK GAS TYPETHERMOSTAT SENSING BULB INSTALLING HEATER TO WALLLocating Thermostat Sensing Bulb Attaching Thermostat Sensing BulbAttaching Mounting Bracket To Wall Installing Bottom Mounting ScrewsPlacing Heater On Mounting Bracket INSTALLATIONTypical Inlet Pipe Diameters CONNECTING TO GAS SUPPLYINSTALLATION BLUE FLAME NATURAL GAS HEATERFOR YOUR SAFETY CHECKING GAS CONNECTIONSPressure Testing Gas Supply Piping System Pressure Testing Heater GasOPERATING HEATER MANUAL LIGHTING PROCEDURELIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCECLEANING BURNER PILOT AIR INLET HOLE CLEANING AND MAINTENANCEINSPECTING BURNER PILOT FLAME PATTERNOBSERVED PROBLEM TROUBLESHOOTINGPOSSIBLE CAUSE REMEDYTROUBLESHOOTING Maintenance, pageOBSERVED PROBLEM ContinuedRefer to Air for Combustion and Venti ing Gas Connections, pageTROUBLESHOOTING OBSERVED PROBLEMREPLACEMENT PARTS SPECIFICATIONSTECHNICAL SERVICE SERVICE PUBLICATIONSEQUIPMENT SHUTOFF VALVE GA5010 ACCESSORIESFAN KITS - GA3100A,B AND GA3200TA,B FLOOR MOUNTING STANDBaltimore Electric PARTS CENTRALSPortable Heater Parts Master Parts DistBLUE FLAME NATURAL GAS HEATER ILLUSTRATED PARTS BREAKDOWNCGN20TB CGN20TLB CGN30TB CGN30TLB CGN20TB CGN20TLB CGN30TB CGN30TLB PARTS LISTINTERNATIONAL LIMITED WARRANTYCOMFORT GLOW VENT-FREENATURAL GAS HEATERS Model Serial No Date Purchased