VENTILATION AIR

BLUE FLAME NATURAL GAS HEATER

FRESH AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro- vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see op-

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

tion 3, Figure 2). Follow the National Fuel Gas Code NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Inside Building WARNING: Rework work- sheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two per- manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventila- tion grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

12"

Figure 2 - Ventilation Air from Inside BuildingVentilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

6

104331

Image 6
Contents WHAT TO DO IF YOU SMELL GAS OWNER’S OPERATION AND INSTALLATION MANUALBLUE FLAME VENT-FREENATURAL GAS HEATER Do not try to light any applianceSAFETY INFORMATION BLUE FLAME NATURAL GAS HEATERWARNINGS PRODUCT IDENTIFICATION PRODUCT FEATURESSAFETY DEVICE LOCAL CODESUnusually Tight Construction FRESH AIR FOR COMBUSTION AND VENTILATIONPROVIDING ADEQUATE VENTILATION Confined and Unconfined SpaceContinued DETERMINING FRESH-AIRFLOW FOR HEATER LOCATIONFRESH AIR FOR COMBUSTION AND VENTILATION Ventilation Air From Outdoors VENTILATION AIRVentilation Air From Inside Building To AtticLOCATING HEATER INSTALLATIONINSTALLATION ITEMS CHECK GAS TYPELocating Thermostat Sensing Bulb INSTALLING HEATER TO WALLTHERMOSTAT SENSING BULB Attaching Thermostat Sensing BulbPlacing Heater On Mounting Bracket Installing Bottom Mounting ScrewsAttaching Mounting Bracket To Wall INSTALLATIONINSTALLATION CONNECTING TO GAS SUPPLYTypical Inlet Pipe Diameters BLUE FLAME NATURAL GAS HEATERPressure Testing Gas Supply Piping System CHECKING GAS CONNECTIONSFOR YOUR SAFETY Pressure Testing Heater GasLIGHTING INSTRUCTIONS MANUAL LIGHTING PROCEDUREOPERATING HEATER TO TURN OFF GAS TO APPLIANCEINSPECTING BURNER CLEANING AND MAINTENANCECLEANING BURNER PILOT AIR INLET HOLE PILOT FLAME PATTERNPOSSIBLE CAUSE TROUBLESHOOTINGOBSERVED PROBLEM REMEDYOBSERVED PROBLEM Maintenance, pageTROUBLESHOOTING ContinuedTROUBLESHOOTING ing Gas Connections, pageRefer to Air for Combustion and Venti OBSERVED PROBLEMTECHNICAL SERVICE SPECIFICATIONSREPLACEMENT PARTS SERVICE PUBLICATIONSFAN KITS - GA3100A,B AND GA3200TA,B ACCESSORIESEQUIPMENT SHUTOFF VALVE GA5010 FLOOR MOUNTING STANDPortable Heater Parts PARTS CENTRALSBaltimore Electric Master Parts DistILLUSTRATED PARTS BREAKDOWN CGN20TB CGN20TLB CGN30TB CGN30TLBBLUE FLAME NATURAL GAS HEATER PARTS LIST CGN20TB CGN20TLB CGN30TB CGN30TLBCOMFORT GLOW VENT-FREENATURAL GAS HEATERS LIMITED WARRANTYINTERNATIONAL Model Serial No Date Purchased