AIR FOR COMBUSTION

AND VENTILATION

Continued

Unusually Tight Construction

The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.

Unusually tight construction is defined as construction where:

a. walls and ceilings exposed to the out- side atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10-11kg per pa-sec-m2) or less with openings gasketed or sealed and

b. weather stripping has been added on openable windows and doors and

c.caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumb- ing, electrical and gas lines and at other openings.

If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 7.

If your home does not meet all of the three criteria above, proceed to Determining Fresh-Air Flow For Heater Location.

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms com- municating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.

*Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height =__________cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maxi- mum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

___________ Btu/Hr

Gas water heater*

___________ Btu/Hr

Gas furnace

___________ Btu/Hr

Vented gas heater

___________ Btu/Hr

Gas fireplace logs

___________ Btu/Hr

Other gas appliances*

+__________ Btu/Hr

Total

=__________ Btu/Hr

*Do not include direct-vent gas appliances. Di- rect-vent draws combustion air from the outdoors and vents to the outdoors.

Example:

Gas water heater

40,000

__________ Btu/Hr

Vent-free fireplace

33,000

+ ________ Btu/Hr

Total

73,000

= ________ Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________Btu/Hr (maximum the space can support)

_________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support)

73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You

6

www.desatech.com

111347-01E

Image 6
Contents Echo Valley Oak Log Design Meadowbrook Oak Log Design Variable ManuallyTable of Contents Safety Information Local Codes UnpackingProduct Features Product IdentificationUnusually Tight Construction AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Confined and Unconfined SpaceUnconfined space, remove door to adjoining Ventilation AIRVentilation AIR from Outdoors Size makes room unconfinedInstallation Check GAS TypeIf Using Mantel Installation and Clearances for VENT-FREE OperationIf Not Using Mantel Side Wall CeilingTible Material Installation Distance a Mantel ClearancesNoncombus Installing Damper Clamp Accessory for Vented Operation Floor ClearancesChimney Minimum Permanent Installing Heater Base Assembly Installation Items NeededConnecting to GAS Supply External Regulator With Vent Pointing DownTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Checking GAS ConnectionsTest Pressures In Excess Of 1/2 Psig 3.5 kPa Correct all leaks at onceInstalling Logs Variable Manually-Controlled ModelsOperating Heater Thermostat Models CDLLighting Instructions To the OFF positionVariable Control Operation Manual Lighting ProcedureThermostat Models For Your Safety Read Before Lighting To Turn OFF GAS To ApplianceControl Knob and Ignitor Button Location Pilot Flame Pattern Inspecting BurnersThermostat Control Operation Burner Primary AIR HolesCleaning Maintenance Burner Injector Holder and Pilot AIR Inlet HoleLogs Troubleshooting Observed Problem Possible Cause RemedyPilot is lit Pane/LP gas company Burner orifices clogged Dark residue on logs inside Improper log placementInlet gas pressure is too low Replace burner orificesGas leak. See Warning Optional Positioning Thermostat Sensing Bulb Tools needed 1/4 hex driver or socketEcho Valley Oak Log SpecificationsImportant Do not crimp capillary Meadowbrook Oak LogTechnical Service AccessoriesService Hints Replacement PartsIllustrated Parts Breakdown ODS PilotPropane/LP Parts List Variable MANUALLY-CONTROLLED Echo Valley OAK LOG Models24-3 24-4 24-2 24-1 THERMOSTATICALLY- Controlled Meadowbrook OAK LOG Warranty Information Keep this WarrantyLimited Warranty VENT-FREE GAS LOG Heaters

LSL3124P, CDL3924PT, CDL3924NT specifications

Desa CDL3924NT, LSL3124P, and CDL3924PT are notable choices in the realm of heating appliances, demonstrating advanced engineering and an array of user-friendly features. Each model has unique characteristics, making them suitable for diverse heating needs.

The Desa CDL3924NT is particularly distinguished by its dual-fuel capability, allowing users to switch between natural gas and propane. This flexibility ensures that homeowners can choose the energy source that best suits their preferences and availability. Moreover, the model boasts a heating capacity of up to 39,000 BTUs, providing substantial warmth for large spaces. Its compact design makes it ideal for installations in rooms with limited space, while an aesthetically pleasing finish ensures that it blends seamlessly with various home decors.

Meanwhile, the LSL3124P shines with its sleek design and powerful performance. This direct vent gas stove focuses on efficiency, delivering up to 26,000 BTUs of heating output. One of its standout features is the advanced airflow system, which ensures even heat distribution, reducing cold spots and providing consistent warmth. The LSL3124P is equipped with a straightforward digital thermostat that allows for precision temperature adjustments, enhancing user convenience. Additionally, the model is designed for quiet operation, making it an excellent choice for relaxation areas like living rooms or bedrooms.

The CDL3924PT, on the other hand, emphasizes versatility and efficiency. Equipped with a programmable timer, this appliance allows users to pre-set heating schedules according to their daily routines, ultimately conserving energy and reducing utility costs. With a maximum output of 39,000 BTUs, the CDL3924PT is capable of heating larger areas effectively. The unit boasts a built-in safety shut-off feature, ensuring peace of mind in household environments. Its stylish design complements modern interiors, and its easy installation process caters to both new and seasoned homeowners.

In summary, the Desa CDL3924NT, LSL3124P, and CDL3924PT models stand out for their innovative technologies and feature sets. Each unit addresses unique heating needs with efficiency and style, making them valuable additions to any home. Whether you prioritize flexibility in fuel options, quiet operation, or programmable settings, Desa's offerings cater to various lifestyles and heating requirements. Their robust heating capabilities, coupled with user-friendly designs, ensure that every homeowner can find a suitable option for comfort during colder months.