Desa LDL3924NR Determining FRESH-AIR Flow for Heater Location, Confined and Unconfined Space

Page 5

AIR FOR COMBUSTION AND VENTILATION

Providing Adequate Ventilation (Cont.) Determining Fresh-Air Flow for Heater Location

5

AIR FOR COMBUSTION AND VENTILATION

Continued

c.caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of the three criteria (a,b, and c, you must provide additional fresh air. See Ventila- tion Air From Outdoors, page 6.

If your home does not meet all of the three criteria above, proceed to Determining Fresh-Air Flow For Heater Location.

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.

*Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ___________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space

can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr

Gas water heater*

 

_____________ Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

Other gas appliances* +

_____________ Btu/Hr

Total

=

_____________ Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws com- bustion air from the outdoors and vents to the outdoors.

Example:

Gas water heater

 

40,000

Btu/Hr

Vent-free heater

+

33,000

Btu/Hr

Total

=

73,000

Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/ Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Out- doors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec- tion 5.3 or applicable local codes.

For morevisit www..com

111515-01A

Image 5
Contents What to do if YOU Smell GAS OWNER’S Operation Installation ManualSafety Information Table of ContentsUnpacking Local CodesAIR for Combustion and Ventilation Product FeaturesProduct Identification Determining if You Have a Confined or Unconfined Space Determining FRESH-AIR Flow for Heater LocationConfined and Unconfined Space Ventilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building LOG Sizing Requirements InstallationCheck GAS Type Minimum Noncombustible Material Clearances If Not Using MantelMantel Clearances Determining Minimum Mantel Clearance When Using a HoodFloor Clearances Determining Minimum Mantel ClearanceInstalling Heater Base Assembly Installing Damper Clamp Accessory for Vented OperationInstallation Items Needed Area of Various StandardInstalling Battery into Remote Installing Batteries in ReceiverSure regulator Connecting to GAS SupplyChecking GAS Connections Pressure Testing gas Supply Piping systemPressure Testing Heater Gas Connections Rear Log Log #1 Placement Installing LogsLighting Instructions For Your Safety Read Before LightingOperating Heater HAND-HELD Remote Operation Manual Lighting ProcedureTo Turn OFF GAS To Appliance Shutting Off HeaterPilot Flame Pattern Inspecting BurnersBurner Primary AIR Holes Main BurnerLogs Cleaning and MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole Observed Problem Possible Cause Remedy TroubleshootingMaintenance, Gas leak. See Warning statement Models LDL3924NR, LDL3924PR LDL3930NR and LDL3930PR Illustrated Parts BreakdownParts List Replacement Parts SpecificationsWiring Diagram Service Hints Technical ServiceOwners Registration Form Postage Required Accessories Warranty Information

LDL3924NR specifications

Desa LDL3924NR is a state-of-the-art model that embodies innovative technology and advanced features aimed at providing optimal performance in its class. This model is particularly designed for users who demand reliability and efficiency in their operations.

One of the standout features of the Desa LDL3924NR is its high-performance engine. Designed to deliver excellent power output, this engine ensures that operations are smooth and efficient, making it suitable for a variety of tasks. The power-to-weight ratio is optimized, which provides the user with enhanced control and responsiveness, ensuring that even the most demanding applications can be tackled with ease.

The design of the Desa LDL3924NR incorporates advanced materials, which not only contribute to its durability but also help in reducing maintenance requirements. This characteristic is particularly beneficial for users who prioritize longevity and reliability in their equipment. Moreover, the ergonomic design ensures that the model is user-friendly, allowing operators of varying skill levels to handle it with confidence.

In terms of technology, the Desa LDL3924NR is equipped with a sophisticated control system that monitors performance metrics in real time. This technology provides users with insights into efficiency and operational status, empowering them to make informed decisions that can enhance productivity. Additionally, the model is designed with safety features that prioritize operator well-being, minimizing risks and ensuring compliance with industry standards.

Another key characteristic of the Desa LDL3924NR is its versatility. It performs reliably across different settings, whether in industrial, agricultural, or commercial environments. This multifunctionality makes it an attractive option for a diverse range of users.

In conclusion, the Desa LDL3924NR stands out due to its powerful engine, durable construction, innovative technology, and safety features. Its versatility allows it to adapt to various applications, making it an indispensable tool for professionals seeking efficiency and reliability. With its commitment to quality and performance, the Desa LDL3924NR is poised to meet the growing demands of users across multiple sectors.