INSTALLATION
Continued
CAUTION: Use only new, black iron or steel pipe. Inter-
Typical Inlet Pipe Diameters
VN18A, VN18TA, VP16A, VP16TA and
VP16ITA - 3/8" or greater
VN30A, VN30TA, VP26A, VP26TA and
VP22ITA - 1/2" or greater
Installation must include equipment shutoff valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 15).
IMPORTANT: Install an equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
Install sediment trap in supply line as shown in Figure 15. Locate sediment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.
IMPORTANT: Hold the pressure regulator with wrench when connecting it to gas piping and/or fittings. Do not over tighten pipe connection to regulator. The regulator body could be damaged.
Pressure |
|
|
| ||
Regulator |
|
| 3/8" NPT | ||
Regulator |
|
| |||
|
| Pipe | |||
Bracket |
|
| Nipple | ||
Heater |
|
| Ground | ||
Cabinet |
|
| Joint | ||
Connection* |
|
|
| Union | |
Tee Joint |
| Equipment | |||
|
| ||||
| Reducer |
| |||
|
| Shutoff | |||
| Bushing to |
| Valve * | ||
Gauge | 1/8" NPT |
| Natural Gas | ||
1/8" NPT |
| ||||
|
| ||||
| 3" | From Gas | |||
| Plug Tap | Meter (7" W.C. | |||
Test | Min. | ||||
|
| ||||
|
|
| to 10.5" W.C. | ||
|
|
|
| ||
| Tee | Pipe Cap |
| Pressure) | |
|
| Propane/LP | |||
| Joint | Nipple |
| ||
| Sediment Trap |
| From External | ||
|
| Regulator |
(11" W.C. to 14" W.C. Pressure)
*A CSA
Figure 15 - Gas Connection
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.
WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detec- tion fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.
CAUTION: For propane/LP gas, make sure external regula- tor has been installed between propane/LP supply and heater. See guidelines under Connect- ing to Gas Supply, page 11.