OWNER’S MANUAL
INSTALLATION
Continued
CHECKING GAS
CONNECTIONS
WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.
WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.
Pressure Testing Gas Supply Piping System
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1.Close equipment shutoff valve (see Fig- ure 19).
2.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.
3.Check all joints from gas meter to equip- ment shutoff valve (see Figure 20). Ap- ply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
4.Correct all leaks at once.
Open
Equipment
Shutoff
Valve
Closed
Figure 19 - Equipment Shutoff Valve
Pressure Testing Heater Gas Connections
1.Open equipment shutoff valve (see Fig- ure 19).
2.Open main gas valve located on or near gas meter.
3.Make sure control knob of heater is in the OFF position.
4.Check all joints from equipment shutoff valve to thermostat gas valve (see Fig- ure 20). Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.
5.Correct all leaks at once.
6.Light heater (see Operating Heater, pages 14 and 15). Check all other in- ternal joints for leaks.
7.Turn off heater (see To Turn Off Gas to Appliance, page 14).
8.Replace front panel.
1.Disconnect appliance with its appliance main gas valve (control valve) and equip- ment shutoff valve from gas supply pip- ing system. Pressures in excess of 1/2 psig will damage heater regulator.
2.Cap off open end of gas pipe where equipment shutoff valve was con- nected.
3.Pressurize supply piping system by ei- ther using compressed air or opening main gas valve located on or near gas meter.
4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.
5.Correct all leaks at once.
6.Reconnect heater and equipment shutoff valve to gas supply. Check re- connected fittings for leaks.
Thermostat Gas
Valve Location
Gas Meter
Equipment
Shutoff
Valve
Figure 20 - Checking Gas Joints
107099 | 13 | For more information, visit www.desatech.com |