Desa RFN30TA Inspecting Burner, Thermostat Control Operation, Manual Lighting Procedure

Page 15

OWNER’S MANUAL

OPERATING

HEATER

Continued

THERMOSTAT

CONTROL

OPERATION

The thermostatic control used on this heater differs from standard thermostats. Standard thermostats simply turn on and off the burner. The thermostat used on this heater senses the room temperature. The thermostat adjusts the amount of gas flow to the burner. This increases or de- creases the burner flame height. At times the room may exceed the set temperature. If so, the burner will shut off. The burner will cycle back on when room temperature drops below the set temperature.

The control knob can be set to any heat level between HI and LO.

Note: The thermostat sensing bulb mea- sures the temperature of air near the heater cabinet. This may not always agree with room temperature (depending on housing construction, installation loca- tion, room size, open air temperatures, etc.). Frequent use of your heater will let you determine your own comfort levels.

MANUAL LIGHTING

PROCEDURE

1.Remove front panel (see Figure 2, page 4).

2.Follow steps 1 through 5 under Lighting Instructions, page 14.

3.With control knob pressed in, strike match. Hold match to pilot until pi- lot lights.

4.Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob. Now follow step 8 under Lighting Instruc- tions, page 14.

5.Replace front panel.

INSPECTING

BURNER

Check pilot flame pattern and burner flame pattern often.

PILOT FLAME PATTERN

Figure 23 shows a correct pilot flame pat- tern. Figure 24 shows an incorrect pilot flame pattern. The incorrect pilot flame is not touching the thermocouple. This will cause the thermocouple to cool. When the thermocouple cools, the heater will shut down.

If pilot flame pattern is incorrect, as shown in Figure 24

turn heater off (see To Turn Off Gas to Appliance, page 14)

seeTroubleshooting, pages 17 through 19

Thermocouple

Pilot Burner

Figure 23 - Correct Pilot Flame Pattern

Thermocouple

Pilot Burner

 

Figure 24 - Incorrect Pilot Flame Pattern

BURNER FLAME PATTERN

Figure 25 shows a correct burner flame pattern. Figure 26 shows an incorrect burner flame pattern. The incorrect burner flame pattern shows yellow tipping of the flame. It also shows the flame higher than one inch above the log.

Note: When using the heater the first time, the flame will be yellow for approximately one hour until the log cures.

WARNING: If yellow tipping occurs, your heater could pro- duce increased levels of carbon monoxide. If burner flame pattern shows yellow tipping, follow in- structions at bottom of this page.

NOTICE: Do not mistake orange flames with yellow tipping. Dirt or other fine particles enter the heater and burn causing brief patches of orange flame.

If burner flame pattern is incorrect, as shown in Figure 26

turn heater off (see To Turn Off Gas to Appliance, page 14)

seeTroubleshooting, pages 17 through 19

Top of Flame Even

With Top of Log

Figure 25 - Correct Burner Flame Pattern

Yellow Tipping

Figure 26 - Incorrect Burner Flame Pattern

107099

15

For more information, visit www.desatech.com

Image 15
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GAS15,000 to 30,000 Btu/Hr With Thermostat Local Codes Safety InformationUnpacking AssemblyProduct Features Product IdentificationAssembling and Attaching Brass Trim Attaching Brass Front Trim to Front PanelConfined and Unconfined Space AIR for Combustion and VentilationProviding Adequate Ventilation Unusually Tight ConstructionAIR for Combustion Ventilation Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Ventilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Check GAS Type InstallationInstallation Items Locating HeaterInstallation Options Thermostat Sensing BulbMounting Heater to Wall Placing Heater On Mounting Bracket Installing Bottom Mounting ScrewsMounting Heater on Optional Hearth Base Attaching Mounting Bracket To WallSecuring Hearth Base to Floor Mounting Heater to Optional Hearth BaseSee Instructions Included With Mantel Kit Assembling Mantel Gas Connection Connecting to GAS SupplyClose equipment shutoff valve see Fig- ure Pressure Testing Gas Supply Piping SystemPressure Testing Heater Gas Connections Checking GAS ConnectionsTo Turn OFF GAS To Appliance For Your Safety Read Before LightingOperating Heater Lighting InstructionsPilot Flame Pattern Manual Lighting ProcedureInspecting Burner Thermostat Control OperationCleaning and Maintenance Replacement PartsService Hints Troubleshooting Natural gas company Line. Have gas line checked by localLation requirements Gas odor even when control knob is in OFFSpecifications Technical ServiceParts Centrals Accessories RFN30TA Illustrated Parts BreakdownKEY RFN30TA Description QTY Parts ListWarranty Information