Desa VP20BT, VN20BT installation manual Checking GAS Connections, VN30BT, VP30BT 1/2 or greater

Page 12

INSTALLATION

Continued

CAUTION:Useonlynew,black ironorsteelpipe.Internally-tinned

IMPORTANT: Hold the pressure regulator with wrench when connecting it to gas piping and/or fittings. Do not over tighten pipe connection to regulator. The regulator body could be damaged.

copper tubing may be used in cer- tainareas.Checkyourlocalcodes. Usepipeoflargeenoughdiameter to allow proper gas volume to heater. If pipe is too small, undue loss of volume will occur.

Typical Inlet Pipe Diameters VN20BT, VP20BT - 3/8" or greater

VN30BT, VP30BT - 1/2" or greater

Installation must include equipment shutoff valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 15).

IMPORTANT: Install an equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

WARNING: Use pipe joint

 

Pressure

 

Regulator

3/8" NPT

Pipe Nipple

Connection*

Tee Joint

 

 

Reducer

 

Bushing

Gauge

to 1/8"

NPT

 

 

1/8" NPT

Test

Plug Tap

 

Trap

Tee Joint

Pipe

Sediment

Nipple

 

 

Cap

Note: Burner bracket not shown for clarity

Heater Cabinet

Ground Joint

Union

Equipment

Shutoff

Valve *

3" Min.

Natural Gas From Gas Meter (4" W.C. to 10.5" W.C. Pressure) Propane/LP From External Regulator (11" W.C. to 14" W.C. Pressure)

sealant that is resistant to liquid petroleum (LP) gas.

Install sediment trap in supply line as shown in Figure 15. Locate sediment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

 

External

Propane/LP

Regulator

Supply Tank

 

Vent

Pointing

Down

Figure 14 - External Regulator With Vent

Pointing Down

Figure 15 - Gas Connection

*A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 21.

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detec- tion fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

12

www.desatech.com

107886-01J

Image 12
Contents What to do if YOU Smell GAS Table of Contents Safety Information Product Features Local CodesUnpacking AIR for Combustion Ventilation Providing Adequate VentilationUnusually Tight Construction Confined and Unconfined SpaceDetermining FRESH-AIR Flow for Heater Location Determining if You Have a Confined or Unconfined SpaceInstallation Ventilation AIRCheck GAS Type Ventilation Air From Inside BuildingInstallation Items Locating HeaterInstalling Heater to Wall Thermostat Sensing BulbInstalling Bottom Mounting Screws Attaching To Wall Anchor MethodPlacing Heater On Mounting Bracket Connecting to GAS Supply Mounting Base Feet to Floor Where required by local codeMounting Heater to Floor Mounting Base Feet to HeaterChecking GAS Connections VN30BT, VP30BT 1/2 or greaterPressure Testing Heater GAS Connections Test Pressures Equal To or Less Than 1/2 Psig 3.5 kPaFor Your Safety Read Before Lighting Operating HeaterLighting Instructions Inspecting Heater Cleaning Maintenance ODS/PILOT and BurnerBurner Pilot AIR Inlet CabinetSpecifications Service HintsTechnical Service Service PublicationsTroubleshooting Observed Problem Possible Cause RemedySee Cleaning and Mainte Gas leak. See Warning Statement aboveReplacement Parts AccessoriesIllustrated Parts Breakdown Models VN20BT, VP20BT VN30BT, VP30BTParts List NJF 8CWarranty Information Keep this WarrantyLimited Warranty VENT-FREE Residential GAS Heaters