AIR FOR COMBUSTION

AND VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a con- fined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless pas- sageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height =__________cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

_______ (volume of space) x 20 = (Maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

______________ Btu/Hr

Gas water heater*

______________ Btu/Hr

Gas furnace

______________ Btu/Hr

Vented gas heater

______________ Btu/Hr

Gas fireplace logs

______________ Btu/Hr

Other gas appliances* + __________

Btu/Hr

Total

= __________

Btu/Hr

*Do not include direct-vent gas appliances. Di- rect-vent draws combustion air from the outdoors and vents to the outdoors.

Example:

40,000

Gas water heater

______________ Btu/Hr

Vent-free heater

20,000

+ _____________ Btu/Hr

Total

60,000

= _____________ Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_______________Btu/Hr (maximum the space can support)

_______________Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

60,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maxi- mum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoin- ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B.Vent room directly to the outdoors. See Ventila- tion Air From Outdoors, page 7.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an uncon- fined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be oper- ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

6

www.desatech.com

107886-01J

Image 6
Contents What to do if YOU Smell GAS Table of Contents Safety Information Product Features Local CodesUnpacking Unusually Tight Construction AIR for Combustion VentilationProviding Adequate Ventilation Confined and Unconfined SpaceDetermining FRESH-AIR Flow for Heater Location Determining if You Have a Confined or Unconfined SpaceCheck GAS Type InstallationVentilation AIR Ventilation Air From Inside BuildingInstallation Items Locating HeaterInstalling Heater to Wall Thermostat Sensing BulbInstalling Bottom Mounting Screws Attaching To Wall Anchor MethodPlacing Heater On Mounting Bracket Mounting Heater to Floor Connecting to GAS SupplyMounting Base Feet to Floor Where required by local code Mounting Base Feet to HeaterChecking GAS Connections VN30BT, VP30BT 1/2 or greaterPressure Testing Heater GAS Connections Test Pressures Equal To or Less Than 1/2 Psig 3.5 kPaFor Your Safety Read Before Lighting Operating HeaterLighting Instructions Inspecting Heater Burner Pilot AIR Inlet Cleaning MaintenanceODS/PILOT and Burner CabinetTechnical Service SpecificationsService Hints Service PublicationsTroubleshooting Observed Problem Possible Cause RemedySee Cleaning and Mainte Gas leak. See Warning Statement aboveReplacement Parts AccessoriesIllustrated Parts Breakdown Models VN20BT, VP20BT VN30BT, VP30BTParts List NJF 8CWarranty Information Keep this WarrantyLimited Warranty VENT-FREE Residential GAS Heaters