INSTALLING THE UNIT

Cutting/Extending the Piping

5 metres of piping is supplied with the air conditioner(Optional). This length can if necessary be:

￿ Extended to a maximum of 15metres

￿Shortened as required

If more than 5 metres of piping is required:

￿ The assembly cable must also be extended

￿ Refrigerant must be added to the circuit by an approved installer; otherwise, the indoor unit may freeze

1Make sure that you have the required tools available (pipe cutter, reamer, flaring tool and pipe holder).

2If you wish to shorten the piping, cut it using a pipe cutter, taking care to

ensure that the cut edge remains at a 90¡ angle with the side of the pipe, and referring to the illustrations below for examples of edges cut correctly and incorrectly.

90O

Oblique

Rough

Burr

O

x

x

x

3To prevent any gas from leaking out, remove all burrs at the cut end of the pipe, using a reamer.

4Slide a flare nut on to the pipe and modify the flare.

Outer Diameter (D)

Depth (A)

6.35 mm

1.3 mm

9.52 mm

1.8 mm

12.70 mm

2.0 mm

5Check that the flaring is correct, referring to the illustrations below for

examples of incorrect flaring.

x

x

x

x

Inclined

Damaged Surface

Cracked

Uneven Thickness

6Align the pipes to be connected and tighten the flare nuts first manually and then with a torque wrench, applying the following torque.

Outer Diameter

Torque (kgf•cm)

6.35 mm

140~170

9.52 mm

~

250 280

12.70 mm

380~420

7For further details on how to connect up to the outdoor unit and purge the circuit, refer to page 12.

E-11

Image 11
Contents Cooling and Heating AQ12F Series AQ09N Series AQ12N SeriesSafety Precautions Contents Indoor Unit Deciding on Where to Install the Air ConditionerPreparing the Installation Accessories in the Outdoor Unit Case Air Conditioner and AccessoriesAccessories in the Indoor Unit Case Then follow Steps Fixing the Installation PlatePurging the Unit Connecting the Assembly Cable Installing and Connecting the Outdoor Unit Drain Hose Installing and Connecting the Indoor Unit Drain HoseTorque kgfcm Installing and Connecting the Indoor Unit Assembly PipingDepth a Cutting/Extending the PipingIf you have used Then Connecting Up and Purging the CircuitOuter Diameter Torque kgfcm Placing the Indoor Unit in Position To check for gas leaks on Then, using a leak detector CheckPerforming Leak Tests Fixing the Outdoor Unit in Position Checking and Testing OperationsExplaining Operations to the Owner Electronics ÊìäéÇéÑëíÇé èé ìëíÄçéÇäÖ ÅÂ˚ è‰ÓÒÚÓÓÊÌÓÒÚË ËÓ‰ÂʇÌË ÄÓÏ̇ÚÌ˚È ·ÎÓÍ ˚·Ó ÏÂÒÚ‡ ‰Îfl ÛÒÚ‡ÌÓ‚ÍË ÍÓ̉ˈËÓÌÂ‡300 ÏÏ ËÎË ·ÓΠ125 ÏÏ ËÎË ·ÓΠÊËθÌ˚È ÄÓ̉ˈËÓÌÂ Ë ÔË̇‰ÎÂÊÌÓÒÚË Í Ìâïû12068 ‡‡ÍÚÂËÒÚËÍË Í‡·ÂÎfl ÔËÚ‡ÌËfl ÈÓ‰Íβ˜ÂÌË ÒÓ‰ËÌËÚÂθÌÓ„Ó Í‡·ÂÎflÌÒÚ‡Ìӂ͇ Ë èÓ‰ÒÓ‰ËÌÂÌË ÑÂ̇ÊÌÓ„Ó ò·̄‡ äÓÏ̇ÚÌÓ„Ó ÅÎÓ͇ ÅÓÌÚ‡Ê Ë ÔÓ‰ÒÓ‰ËÌÂÌË ‰Â̇ÊÌÓ„Ó ¯Î‡Ì„‡ Í ÍÓÏ̇ÚÌÓÏÛ ·ÎÓÍÛÅÓÌÚ‡Ê Ë ÔÓ‰ÒÓ‰ËÌÂÌË ÚÛ·ÓÔÓ‚Ó‰‡ Í ÍÓÏ̇ÚÌÓÏÛ ·ÎÓÍÛ ‰ÎËÌÂÌ ÊÂÁ͇ ÚÛ·ÓÍ/ ì‰ÎËÌÂÌË ÚÛ·ÓÔÓ‚Ó‰‡‡ÛÊÌ˚È ÄÓÏ̇ÚÌ˚È ÌÒÚ‡Ìӂ͇ ÍÓÏ̇ÚÌÓ„Ó ·ÎÓ͇ ‚ Ìûêìóï Ôóîóêâìëë Ó‚Â͇ ÓÚÒÛÚÒÚ‚Ëfl ÛÚ˜ÍË „‡Á‡Ó‚ÂÍË Ë ÔÓ·Ì˚È Ôûòí ‡ÍÂÔÎÂÌË ç‡ÛÊÌÓ„Ó ÅÎÓ͇ÀÌÒÚÛÍÚ‡Ê ÔÓθÁÓ‚‡ÚÂÎfl AQ07X*RIM27212 1/19/07 1121 AM