REMOTE CONNECTIONS – TERMINAL STRIP

 

 

 

 

12.1

Making BMS/BAS remote connections for analog and binary (on/off) signals

 

A terminal strip for the remote connection is located behind the hinged control panel at the top of the cabinet and is

 

accessed by removing the bottom cover and then removing the screws at the top of the hinged cover.

 

Important: Do not use single strand bell wire for remote field connections to terminals R1-R2 and C1-C2. Use only

 

multi-strand copper wire. See table below for wire length and gauge:

 

 

 

 

 

 

 

 

 

 

 

 

Wire Gauge

18 GA

16GA

14 GA

12 GA

 

 

 

 

 

 

 

 

 

 

 

Maximum Length

30 FT

50 FT

75 FT

100 FT

 

 

 

 

 

 

 

 

 

 

WARNING: Turn off all electrical service to the appliance when accessing the remote connections located

 

inside the control cabinet. These terminals are High Voltage. If the electrical service is not turned off and

 

these terminals are touched, a dangerous shock causing personal injury or loss of life could occur. Close

 

and fasten the control cabinet cover before restoring electrical service to the appliance.

12.2

The Following Describes The Functions Of Each Of These Terminals And The Factory-Installed Options

 

Required To Activate The Terminals:

 

 

 

 

 

Note: Terminal P1-P2are functional only when the water heater is equipped with the factory installed options required to activate the terminals. Terminals R1-R2, A1-A2,C1-C2and T1-T2are standard pre-wired functions on all models.

R1-R2:Used to activate / de-activate water heater from remote master control.

Terminals are wired to a relay in a remote Energy Management System. When relay closes, circuit from R1 to R2 is completed and appliance controls are enabled. Appliance ships from factory with jumper between terminals Remove jumper when connecting to a remote controller.

A1-A2:Used to activate a remote alarm, signaling shutdown of combustion control.

Provides a maximum 10 amp relay contact closure when the flame safeguard terminates combustion due to a tripped safety interlock (i.e.: air proving switch, high limit switch, low water flow switch or flame sensor, etc.).

P1-P2:Activates remote equipment and requires confirmation signal back to the appliance.

Provides a maximum 10-amp relay contact closure to activate a remote device (i.e.: mechanical room air louvers, draft inducer or power vent, etc.). The remote device must send return signal via proving switch to confirming proper operation to terminals C1-C2, prior to the appliance being able to energize. Options Required - Consult Factory.

C1-C2:Used for proving operation of remote device.

Terminals are wired to a proving switch on a remote device such as a power venter. When relay closes, circuit from C1 to C2 is completed and appliance controls are enabled. This appliance ships form the factory with jumper between terminals.

T1-T2:Used for external modulation control.

To connect external modulation control, disconnect and cap the blue wire connected to terminal T2 and connect the external modulating signal to terminals T1 (positive) and T2 (negative).

26

PV500-46U 06/12

Image 26
Contents Installation & Maintenance Manual Table of Contents Temptrac Electronic Controller Panel Operating and Safety ControlsTroubleshooting Guide Replacement Parts Remote Connections Terminal StripSafety Considerations Product Safety InformationBelow scalding temperatures Standard Features and Equipment Series Series Codes Water Heater InstallationChecking Equipment Before You Install Electrical RequirementsGeneral Piping Guidelines Service ClearancesClearances To Combustible Surfaces Inlet and Outlet ConnectionsPV500-46U 06/12 PV500-46U 06/12 Optional Condensate Neutralization System Inlet Pressure NAT. GAS Single Unit Installation Suggested Pipe SizeGAS Supply and Piping Convert Fittings to Equivalent Straight PipeInches Multiple Unit Installations GAS Piping Size ChartNominal Iron Length of Pipe in Straight Feet Appliance Isolation during Gas Supply Piping Pressure Test∙ All Air From Outdoors Combustion and Ventilation AIREquipment Located In Confined Spaces ∙ All Air From Inside The BuildingDuct Fitting Equivalent Length Duct Pipe Vertical or Horizontal Remote Air Duct TerminationVenting Venting the Power VT Plus Sani modelsVenting the Power VT Plus Maximum Category IV Vent Length Equivalent LengthVent Fitting Equivalent Length Vent Pipe Vertical or Horizontal Vent Termination Combining Category IV VentsOperating and Safety Controls Temperature and Pressure Relief ValvesElectronic Low Water Cut-Off Optional High Water Temperature Limit ControlCathodic Protection Down Temptrac Electronic Controller PanelSET ClockTo Change Other Parameters To View The SetpointTo Change The Setpoint Recommended Action LED Display Alarm MessagesAlarm Cause Results of Alarm Condition Message Remote Connections Terminal Strip Incoming 120VAC Loss of Flame SignalSequence of Operation LED Indication Fault Mode OFFInitial Startup Turn-on main gas shutoff valve PV500-46U 06/12 Gas Train Illustration Alternate Gas Train IllustrationTroubleshooting Guide Problem Probable Cause Corrective ActionReplacement Parts Replacement PartsControl Panel Contact factory for more information Burner Assembly Optional components may or may not be shown Burner Assembly Components SUPPORT, GAS Train FB14 PvifBurner GAS Train Components Contact factory for more informationPeriodic Maintenance PV500-46U 06/12 Recommended Maintenance Schedule PV500-46U 06/12 PV500-46U 06/12

150, 180 specifications

PVI Industries has established itself as a prominent manufacturer in the water heating industry, particularly known for its range of commercial water heaters. Among their well-regarded products is the PVI Industries 150,180, a robust unit engineered to meet the demanding needs of various commercial applications.

The PVI Industries 150,180 is designed to deliver high-efficiency performance, catering primarily to large-scale operations such as hotels, hospitals, and other facilities that require a constant supply of hot water. The unit boasts impressive heating capacity, enabling it to serve multiple points of use simultaneously. With a focus on reliability and durability, the construction of the 150,180 incorporates high-quality materials that ensure longevity even in the most challenging environments.

One of the standout features of the PVI 150,180 is its advanced heating technology. The unit utilizes a state-of-the-art gas-fired burner system, which not only ensures rapid heating but also maximizes energy efficiency. This attention to energy performance is crucial for businesses aiming to reduce operational costs and minimize their environmental impact. Furthermore, the unit supports a range of fuel types, including natural gas and propane, providing flexibility for different regional needs and preferences.

From a technological standpoint, the PVI Industries 150,180 includes an intuitive control system that allows users to monitor and adjust settings easily. This sophisticated interface provides real-time data on water temperature, operational status, and maintenance alerts, significantly enhancing user experience and system management.

Safety features are paramount in PVI’s design philosophy. The 150,180 comes equipped with multiple safety mechanisms, including a high-temperature limit switch and a pressure relief valve, ensuring safe operation and compliance with strict industry regulations.

In terms of installation, the PVI Industries 150,180 is engineered with versatility in mind. It can be installed in various configurations, making it adaptable to the spatial constraints of any facility. Maintenance is straightforward, with accessible components designed to reduce downtime and service costs.

Overall, the PVI Industries 150,180 represents a leading choice for commercial water heating solutions, characterized by its efficiency, reliability, and advanced technology, meeting the diverse needs of modern businesses while upholding the highest standards of safety and performance.