4.Proof of Air Pressure Switch - The control will look for a signal from the
a.When the airflow generated by the blower is sufficient to cause the differential air switch to close, the 15 - second
b.During this period any flue products or combustible gases which may have settled in the water heater are evacuated.
5.
a.The flame control will monitor the current applied to the hot surface igniter.
b.If the flame control determines the proving current meets the threshold, a dwell time delay starts to assure the hot surface igniter has sufficient time to reach ignition temperature.
6.Ignition - When dwell time is completed a
a.The
b.During TFI the flame safeguard control will monitor the flame using flame rectification through the hot surface igniter.
c.If the flame control senses the presence of flame before the end of the TFI period, the igniter will be de- energized and the flame control will continue to monitor the flame, through the igniter, until the operating thermostat ends the call for heat condition.
7.Loss of Flame Signal
a.If the igniter fails to sense flame at any time, the igniter and gas valve will be
b.When the call for heat condition ends or flame failure occurs following the third TFI period (one time if CSD- 1), a
8.
a.The TempTrac will continue to monitor the stored water temperature in the tank.
b.When the setpoint temperature is reached the
c.The flame safeguard control deenergizes the VFD blower system and the gas valve, thereby suspending burner operation.
d.As heat is transferred to the building, the water heater loop temperature will fall below the set point. The TempTrac will sense this condition and begin the
9.Flame Safeguard LED Diagnostic Indicator - If the Fenwal Flame Safeguard Control at any time during the operating sequence senses an improper operating state and locks out, the diagnostic red LED located on the control board will flash to indicate one of the following conditions exist:
LED INDICATION | FAULT MODE | |
On | Normal Operation | |
OFF | Internal Control Failure – check power | |
1 | Flash | Airflow Fault |
|
|
|
2 | Flashes | Erroneous Flame Signal |
3 | Flashes | Ignition Lockout |
4 | Flashes | Hot Surface Igniter Fault |
|
|
|
5 | Flashes | Low Voltage (24 VAC) |
6 | Flashes | Valve Relay Problem |
|