b.Attach a manometer to measure the gas pressure at the manual gas shutoff valve located just upstream of the gas train. Adjust gas train inlet pressure to the specified value (e.g. 14" W.C.), and tightly close the gas train manual shutoff valve closest to the burner.
c.Reattach the manometer to the gas train manual shutoff valve at the burner and record the measured gas pressure in inches of water column (W.C.). Measure gas pressure again after 15 minutes. If gas pressure has increased 0.5" W.C. or more, the gas leak must be isolated to one or more of the operating gas valves. (For example, a solenoid actuated gas shutoff valve.) After any leaking valve is replaced, the reassembled gas train must be leak tested again before
5.Remove enclosure panel cover on the appliance to expose control circuit. A wiring diagram, included in this packet, will show the controls used in our circuitry.
6.Visually check that all components are intact and no damage has occurred during transit.
7.Check all connections within the control cabinet. A loose connection could cause intermittent shutdowns.
8.All burners will use a hot surface igniter (HSI) as the ignition source. They may use a single gas pressure regulator and valves, valve regulator combinations or multiple gas trains.
9.Connect a test meter to the control for reading the flame response signal.
NOTE: Some flame controls read the flame signal in micro amps and some in volts DC.
10.CAUTION: Be sure the tank is filled with water. Dry firing can destroy the appliance.
11.Check the inlet gas pressure before
12.Connect a second manometer to the manifold test port at the shutoff valve closest to the burner.
13.
14.Disable or jumper out any BMS/BAS control interface to allow independent setup and adjustment of each water heater.
15.Turn unit on using the rocker switch on the front of the control enclosure assembly. When the burner fails to light, the flame control will lockout.
Start the burner in Low Fire (Burner combustion must be optimized at both Low and High Fire). To set the TempTrac control for manual modulation output:
−Push and hold the EXT key for more than 3 seconds. The LED switches ON and the PS4 parameter is displayed in the upper display, while the PAS label is shown in the lower display.
−Release the key, and insert the password:
−To adjust modulation manually, push the SET key, the value starts flashing. Then use UP or DOWN keys to modify it. 100 = High Fire; 0 = Low Fire.
−To exit, press SET + UP or wait 30s without pressing any key.
NOTE: After a modification, it will be possible to enter the Modulation output setting without entering the password for 10min. After this time you will be asked for the password again.
16.Turn-on main gas shutoff valve.
17.If the operating control switches are closed, the burner blower should come on and
18.If nothing happens, check for a lockout condition and reset it by pushing the flame safeguard reset button. Some safety devices are wired in the operating circuit and may not indicate alarm. If no indication of alarm exists, check gas pressure switches, electronic low water cutoffs (if equipped) and temperature limits.
29