15 TROUBLESHOOTING GUIDE
Problem | Probable Cause | Corrective Action | |
| Power Supply | Check fuse and/or circuit breaker. Check voltage at | |
| 120/24V | ||
|
| ||
| Check if | ||
| Temperature Control | Check that the operating temperature control is set | |
| higher than the temperature of the water heater. | ||
|
| ||
| Flame Safeguard Control | Check for bad ground or bad control. Replace if | |
| necessary. | ||
|
| ||
| Remote enable/disable open | Enable water heater or place jumper between | |
| terminals | ||
|
| ||
|
| Check if fan connection terminals on flame control | |
|
| is closed | |
Starting or | Combustion Air blower | Check for 24V at field access terminal C2. Remote | |
Failure |
| interlock may be open. | |
|
| Fan VFD may be defective. Verify proper voltage. | |
|
| Check switch contacts are closed. | |
|
| Check for 24V at the N.O. side of air switch | |
| Check for 24V at the common side of air switch | ||
|
| Check for proper blower pressure setting – adjust if | |
|
| required. Air switch may be defective. | |
| Blocked Filter Switch | Check for 24V at the N.C. side of the blocked filter | |
| (if equipped) | switch. Replace filter or switch as required. | |
| Flame Control Pressure Switch | Check for 24V at the pressure switch terminal. | |
| Loose Wire Connections | Check connections to all components | |
| Power Supply | Check fuse and/or circuit breaker. Check voltage at | |
| 120/24V | ||
|
| ||
| Flame Safeguard Control | Check for bad ground or bad control. Replace if | |
| necessary. | ||
|
| ||
|
| Check amp draw during | |
| Hot Surface Igniter | greater than 3.1A. Check for overheating condition | |
|
| due to damaged refractory around igniter. | |
Flame Failure | Check if switch is bouncing. Adjust or replace. | ||
Gas Pressure | Check for proper inlet static and dynamic gas | ||
| |||
| pressure. | ||
|
| ||
| Combustion | Inadequate flame signal may result from improper | |
| combustion. Adjust to proper CO2 levels at low fire. | ||
|
| ||
| Grounding | Check for proper ground from flame control to | |
| burner housing. | ||
|
| ||
| Safety Limits | Check all safety limits for fault condition and correct | |
| as required. | ||
|
|