i.Cycle unit and test to verify all safety and operating controls are properly functioning and the burner top plate flange is free of leaks.

6.If equipped, the combustion air filter should be replaced every six months. If filter blockage becomes excessive the filter safety switch will not allow the burner to fire. To avoid nuisance shutdown in dirty environments, check and replace filter more frequently.

7.Inspect low water cutoffs and relief valves for proper operation at every six months, or more often if indicated by inspection.

8.Keep appliance area clear and free from combustible materials, gasoline and other flammable vapors and liquids.

9.Check frequently to be sure the flow of combustion and ventilation air is unobstructed to the appliance.

10.When electrical controls are serviced or replaced refer to ELECTRICAL COMPONENT LOCATIONS for identification and location of components.

11.All replacement parts are available through your PVI Industries® Dealer. If you need assistance identifying or contacting your local dealer, you may contact PVI Industries, LLC directly at the address and telephone number located on the first and last page of this manual.

12.If the appliance is to be shut down for an extended period of time, the primary gas valve and the water supply should be shut off. When the appliance is returned to service, a thorough inspection of all utilities and general appliance condition should be conducted.

39

PV500-45U 06/12

Image 39
Contents Installation & Maintenance Manual Table of Contents Remote Connections Terminal Strip Operating and Safety ControlsTroubleshooting Guide Replacement Parts Temptrac Electronic Controller PanelProduct Safety Information Safety ConsiderationsBelow scalding temperatures Standard Features and Equipment Series Series Series Electrical Requirements Water Heater InstallationChecking Equipment Before You Install CodesInlet and Outlet Connections Service ClearancesClearances To Combustible Surfaces General Piping GuidelinesPV500-45U 06/12 PV500-45U 06/12 Optional Condensate Neutralization System GAS Supply and Piping Inlet Pressure NAT. GASConvert Fittings to Equivalent Straight Pipe Inches Single Unit Installation Suggested Pipe SizeMultiple Unit Installations GAS Piping Size Chart Nominal Iron Length of Pipe in Straight FeetCombustion and Ventilation AIR Vertical or Horizontal Remote Air Duct Termination Duct Fitting Equivalent Length Duct PipeVenting Venting the TriconMaximum Category IV Vent Length Equivalent Length Combining Category IV Vents Vent Fitting Equivalent Length Vent PipeTemperature and Pressure Relief Valve s Operating and Safety ControlsHigh Water Temperature Limit Control Cathodic ProtectionElectronic Low Water Cut-Off Optional Clock Temptrac Electronic Controller PanelSET DownTo View The Setpoint To Change The SetpointTo Change Other Parameters Remote Connections Terminal Strip LED Display Alarm MessagesAlarm Cause Results of Alarm Condition Message Recommended ActionIncoming 120VAC Sequence of OperationLED Indication Fault Mode Loss of Flame SignalInitial Startup Turn-on main gas shutoff valve PV500-45U 06/12 Gas Train Illustration for Models 65 through Gas Train Illustration for Models 40 throughProblem Probable Cause Corrective Action Troubleshooting GuideReplacement Parts Replacement PartsControl Panel Contact factory for more information Burner Assembly Optional components may or may not be shown Item No Qty PVI Part No Description Contact factory for more informationPeriodic Maintenance PV500-45U 06/12 Recommended Maintenance Schedule PV500-45U 06/12 PV500-45U 06/12