Napoleon Fireplaces GD82NT, GD82PT manual Pilot burning no Themostat or switch is de, Standing Main

Page 31

 

 

 

31

SYMPTOM

PROBLEM

 

TEST SOLUTION

Pilot burning; no

Themostat or switch is de-

- connect a jumper wire across the wall switch terminals; if main burner

gas to main burner;

fective.

lights, replace switch / thermostat.

gas knob is on ‘HI’;

Wall switch wiring is defec-

-

disconnect switch wires &connect a jumper wire across terminals

wall switch / ther-

tive.

1 & 3; if the main burner lights, check the wires for defects and / or

mostat is on.

 

replace wires.

 

Main burner orifice is

-

remove stoppage in orifice.

 

Faulty valve.

-

replace.

Pilot goes out while

Gas piping is undersized.

- turn on all gas appliances and see if pilot flame flutters, diminishes or

standing; Main

 

extinguishes, especially when main burner ignites. Monitor appliance

burner is in ‘OFF’

 

supply working pressure.

position.

 

-

check if supply piping size is to code. Correct all undersized piping.

Pilot will not light.

No spark at pilot burner

-

check if pilot can be lit by a match

PILOT

 

-

check that the wire is connected to the push button ignitor.

 

-

check if the push button ignitor needs tightening.

BURNER THERMOPILE

-

replace the wire if the wire insulation is broken or frayed.

THERMOCOUPLE

 

 

-

replace the electrode if the ceramic insulator is cracked or broken.

 

 

 

 

-

replace the push button ignitor.

 

Out of propane gas

-

fill the tank.

 

Spark gap is incorrect

-

spark gap should be 0.150” to 0.175” (5/32” to 11/64” approx.) from

 

 

the electrode tip and the pilot burner. To ensure proper electrode loca-

 

 

tion, tighten securing nut (finger tight plus 1/4 turn).

 

No gas at the pilot burner

-

check that the manual valve is turned on.

 

 

-

check the pilot orifice for blockage.

 

 

-

replace the valve.

 

 

-

call the gas distributor.

Main burner goes

Pilot flame is not large enough

-

turn up pilot flame.

out; pilot stays on.

or not engulfing the thermo-

- replace pilot assembly.

 

pile

 

 

 

Thermopile shorting

- clean thermopile connection to the valve. Reconnect.

 

 

- replace thermopile / valve.

 

Remote wall switch wire is too

-

shorten wire to correct length or wire gauge.

 

long; too much resistance in

 

 

 

the system.

 

 

 

Faulty thermostat or switch.

-

replace.

Main burner goes out; pilot goes out.

Refer to “Main burner goes out; pilot stays on”

Vent is blocked

-

check for vent blockage.

 

 

 

Vent is re-circulating

-

check joint seals and installation.

 

 

 

4” flexible vent has become

-

re-attach to fireplace.

disconnected from fireplace.

 

 

Remote wall switch is in “off” position; main burner comes on when gas knob is turned to “ON” position.

Wall switch is mounted up-

- reverse.

side down

 

Remote wall switch is ground-

- replace.

ing.

 

 

 

Remote wall switch wire is

- check for ground (short); repair ground or replace wire.

grounding.

 

Faulty valve.

- replace.

W415-0536 / C / 09.06.06

Image 31
Contents W415-0536 / C What to do if YOU Smell GAS Table of Contents Napoleon gas fireplace president’s lifetime limited warranty 21 3/4 to top of fireplace opening General instructionsGeneral inFORMATION 37 5/8 17 3/4 DIA 21 22 1/8 13 7Care of glass, and plated parts VENTINGSupplier Formula 1 HT VT Formula 2 HT + VT 40 feet Example TOP Exit / horizontal terminationDefinitions Elbow Vent Length ValuesFormula 2 HT + VT 24.75 feet Formula HT 4.2 VT10.7 Formula HT + VT 24.75 feet 6.7Formula 1 HT 3VT Formula 2 HT + VT 40 feet Example TOP Exit Vertical terminationTOP Vertical termination Formula 1 HT VT Formula 2 HT + VT 40 feetW415-0536 / C Vertical Installation Installation Wall and Ceiling ProtectionHorizontal Installation Through the attic Using Flexible Vent ComponentsHorizontal AIR Terminal Installation Vertical AIR Terminal InstallationExtended Horizontal AIR Terminal Installation Using Rigid Vent ComponentsFireplace Vent Connection Use open flame Vertical Venting InstallationGAS Installation Restricting Vertical VentsClearance to Combustibles FramingElectrical Connection Hard Wiring ConnectionSchematic It is necessary to hard wire this fireplaceLog Shipping Bracket Log PlacementFinishing Door RemovalFirebox must be sealed Blower ReplacementNight Light Replacement Turn off the power to the fireplaceStep Decorative Brick Panel InstallationAfk / wi face kit installation Burner assembly removal REMOTE, Receiver and Valve Access1a. Rectangular Front Removal Hand Held Remote Operations Operation / MaintenanceTime OUT Fireplace OperationFAN Speed Setting Address Setting Procedure Dip switch number 0 = on / 1 = off Lighting Instructions For Your Safety Read BeforeOperating Instructions What to do if YOU Smell GASVenturi Adjustment AdjustmentsMaintenance Pilot Burner AdjustmentTerminal Kits ReplacementsReplacement Parts Accessories000 Symptom Problem Test Solution Trouble Shooting GuideShorten wire to correct length or wire gauge Pilot burning no Themostat or switch is deCheck that the wire is connected to the push button ignitor Replace the wire if the wire insulation is broken or frayedFireplace Service History W415-0536 / C W415-0536 / C

GD82PT, GD82NT specifications

Napoleon Fireplaces has long been recognized for its exceptional quality and innovative designs in the world of home heating. Among its impressive lineup are the GD82PT and GD82NT gas fireplaces, two models that stand out for their remarkable features and technologies. These fireplaces provide an ideal combination of aesthetic appeal and functional performance, making them a popular choice for modern homes.

Both the GD82PT and GD82NT are direct vent gas fireplaces, meaning they efficiently draw air from the outside for combustion and exhaust the leftover gases outside, ensuring optimal indoor air quality. This system allows them to be installed in a variety of locations without the need for a traditional chimney, providing flexibility in design and placement.

One of the key features of these models is their large viewing area, which is enhanced by a minimalist design that eliminates bulky frames. This offers an unobstructed view of the mesmerizing flames, turning the fireplace into a stunning focal point in any room. Additionally, both models boast an impressive heating capacity, ensuring that they efficiently warm up spaces even in the coldest climates.

The GD82PT model comes with a traditional logset and ember bed, creating a classic look that many homeowners desire. It is designed to accommodate a 35,000 BTU input, providing substantial heat while still being energy efficient. The GD82NT, on the other hand, features a contemporary linear design, which appeals to those looking for a modern aesthetic in their living spaces. This model also includes a unique glass media option that allows for a sleek and stylish appearance.

Both fireplaces feature Napoleon's advanced electronic ignition system, which ensures a reliable startup every time. Furthermore, the built-in remote control allows users to adjust heat output and flame height with ease. These models are also equipped with a variable speed blower, enhancing heat circulation throughout the room, making them not only visually appealing but highly functional as well.

Safety is another priority for Napoleon. Both models come with a safety screen barrier, preventing accidental contact with the hot glass surface. The intelligent gas control system also includes an oxygen depletion sensor, automatically shutting off the gas supply if oxygen levels drop to unsafe levels.

In summary, the Napoleon GD82PT and GD82NT gas fireplaces exemplify cutting-edge technology and elegant design, providing warmth and ambience to any space. With their innovative features, customizable options, and a strong commitment to safety, these models represent the pinnacle of modern fireplace design.