Napoleon Fireplaces GDS28P manual Vent Terminal Clearances, Covered Balcony Applications ††

Page 13

13

3.4VENT TERMINAL CLEARANCES

COVERED BALCONY APPLICATIONS ††*

 

Q

S

 

 

 

 

R

 

G

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

QMIN

= 3 feet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R MAX

= 2 x QACTUAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RMAX

”  feet

 

 

 

 

 

 

 

 

 

 

INSTALLATIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CANADA

U.S.A.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

12”

 

12”

Clearance above grade, veranda porch, deck or balcony.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

12” Δ

 

9” Δ

Clearance to windows or doors that open.

 

 

C

 

 

 

 

 

 

12” *

 

12” *

Clearance to permanently closed windows.

 

 

D

 

 

 

 

 

 

18” **

18” **

Vertical clearance to ventilated soffits located above the terminal within a horizontal distance of 2’ from

 

 

 

 

 

 

the centerline of the terminal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

12” **

12” **

Clearance to unventilated soffit.

 

 

 

F

 

 

 

 

 

 

 

 

0”

 

0”

Clearance to an outside corner wall.

 

 

G

 

 

 

 

 

 

0” ***

0” ***

Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).

 

 

 

 

 

 

2” ***

2” ***

Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

3’

3’ ****

Clearance to each side of the centerline extended above the meter / regulator assembly to a maximum

 

 

 

 

 

 

 

 

vertical distance of 15’.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

3’

3’ ****

Clearance to a service regulator vent outlet.

 

 

 

J

 

 

 

 

 

 

 

 

12”

 

9”

Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.

K

 

 

 

 

 

 

 

 

6’

 

3’ †

Clearance to a mechanical air supply inlet.

 

 

 

L

 

 

 

 

 

 

 

7’ ‡

7’ ****

Clearance above a paved sidewalk or paved driveway located on public property.

M

 

 

 

 

 

12” ††

12” ****

Clearance under a veranda, porch or deck.

 

 

N

 

 

 

 

 

 

 

 

16”

 

16”

Clearance above the roof.

 

 

O

 

 

 

 

 

 

2’ †*

 

2’ †*

Clearance from an adjacent wall including neighbouring buildings.

 

 

 

P

 

 

 

 

 

 

 

 

8’

 

8’

Roof must be non-combustible without openings.

 

 

Q

 

 

 

 

 

 

 

 

3’

 

3’

See chart for wider wall dimensions.

 

 

R

 

 

 

 

 

 

 

 

6’

 

6’

See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an open-

 

 

 

 

 

 

 

 

 

ing between the terminal and the open side of the structure.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

 

12”

 

12”

Clearance under a covered balcony

 

 

ΔThe terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.

* Recommended to prevent condensation on windows and thermal breakage

** it is recommended to use a heat shield and to maximize the distance to vinyl clad soffits.

*** The periscope requires a minimum 18 inches clearance from an inside corner.

**** This is a recommended distance. For additional requirements check local codes.

† 3 feet above if within 10 feet horizontally.

‡ A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings. †† Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the floor.

†*

Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.

††*

Permitted only if the balcony is fully open on a minimum of one side.

NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.

12.1B

W415-0153 / B / 06.10.10

Image 13
Contents What to do if YOU Smell GAS Installation Operating InstructionsTable of Contents Installation Overview Introduction General Instructions DimensionsWe suggest that our gas GDS28 General InformationOutput CS280/GS28RENDEMENT Rating Plate InformationVenting Refer to the section applicable to your installationPart Supplier Website Venting Lengths and ComponentsMinimum Feet Maximum Typical Vent InstallationMinimum Plus RiseMinimum MIN. to Grade Special Vent Installations 3.3.1 Periscope TerminationMIN. to Grade Covered Balcony Applications †† Vent Terminal ClearancesDefinitions Venting Application Flow Chart TOP ExitElbow Vent Length Values Feet InchesHT VT Simple venting configuration only one 90 elbow TOP Exit Horizontal TerminationHT VT TOP Exit Vertical Termination Simple venting configurationsV T Pipe Vertical Through Existing ChimneyMinimum Clearances to Combustibles InstallationWall and Ceiling Protection Horizontal InstallationHorizontal AIR Terminal Installation Model GDS28 Vertical InstallationVertical AIR Terminal Installation High Temperature Sealant Mobile Home Installation Model GDS28Appliance Vent Connection Self DrillingOptional Wall Switch / Thermostat / Remote GAS InstallationWire Size MAX. Length Vent Specifics Chimney Installation Plates and Gasket Installing B VentAdding Vent Sections Combustion AIRDoor Closing and Opening FinishingLOG Placement Glowing Embers Logo PlacementCharcoal Embers Model GS28 only Venting Action Check OperationLighting Instructions OPERATING/LIGHTING InstructionsTo Turn OFF GAS Pilot Burner Adjustment AdjustmentVenturi Adjustment Restricting Vertical Vents Model GDS28 Flame CharacteristicsBurner Sensor Flame Must EnvelopCare of Glass MaintenanceBlower Replacement Common Components ReplacementsGS28 Components Common Accessories 51 52 46 45 Symptom Problem Trouble ShootingDo not Over Torque Symptom Problem Test SolutionGDS28 Conditions and Limitations WarrantyService History 44.1 44.1

GDS28P specifications

Napoleon Fireplaces has long been a respected name in the world of home heating, and the GDS28P model is a shining example of the brand's dedication to quality and efficiency. This direct vent gas stove is not only a stylish addition to any living space, but it also boasts a range of features and technologies that enhance both performance and user experience.

One of the standout features of the GDS28P is its compact yet powerful design. With a heat output of up to 20,000 BTUs, this stove is capable of warming areas up to 1,000 square feet. Its impressive heating capacity makes it ideal for use in a variety of home settings, whether in a cozy living room or as a supplementary heating source in a larger open floor plan.

The GDS28P incorporates Napoleon's advanced high-efficiency technology, which maximizes heat output while minimizing emissions. The unit features a dual burner system that allows for both a lively flame and a more subdued ambiance. The adjustable flame height and heat output provide homeowners with complete control over their heating experience, ensuring comfort throughout the colder months.

Another notable characteristic is the GDS28P's sleek design, which includes a large viewing area, allowing for an unobstructed view of the alluring flames. The stove is available in a range of finishes, making it easy to integrate into various decor styles. The large glass front allows users to enjoy the mesmerizing effect of the fire, while also ensuring that heat is efficiently radiated into the room.

Additionally, the GDS28P is equipped with a state-of-the-art electronic ignition system, providing reliable startup even in the coldest conditions. The built-in fan kit enhances air circulation, ensuring even heat distribution throughout any space. The unit can be operated via a remote control, allowing users to easily adjust settings while lounging comfortably.

For those concerned about the environment, the GDS28P exceeds the stringent guidelines set by the EPA, providing a cleaner burn compared to traditional wood stoves. This not only reduces your carbon footprint, but it also means less maintenance and cleaning.

In summary, the Napoleon Fireplaces GDS28P is a cutting-edge heating solution that combines efficiency, style, and user-friendly features. Its powerful heating capabilities, advanced technologies, and aesthetic appeal make it a valuable addition to any home, providing warmth and enhancing living spaces while safeguarding the environment.