Trane TSC060-120 manual Cooling Capacity Step, Heating Capacity Step, Air Delivery Selection

Page 10

Selection Procedure - SI Units

Cooling Capacity

Step 1

Calculate the building’s total and sensible cooling loads at design conditions. Use theTrane calculation methods or any other standard accepted method.

Factors used in unit selection:

A

Total Cooling Load: 16.7 kW

B

Sensible Cooling Load: 11.7 kW

C

Airflow: 3400 m3/h

D

Electrical Characteristics: 380-415/50/3

E

Summer Design Conditions: Entering

Evaporator Coil: 27 DB, 19 WB Outdoor

Ambient: 35

F

External Static Pressure: 110 Pa

Step 2

Table PD-1 shows that aTSC060AD has a gross cooling capacity of 17.8 kW and

14.4kW sensible capacity at 3400 m3/h and 35 DB outdoor ambient with 27 DB, 19 WB air entering the evaporator.

To Find Capacity at Intermediate Conditions Not in the Table

When the design conditions are between two numbers that are in the capacity table, interpolation is required to approximate the capacity. Note: Extrapolation outside of the table conditions is not recommended.

Step 3

In order to select the correct unit which meets the building’s requirements, the fan motor heat must be deducted from the gross cooling capacity.The amount of heat that the fan motor generates is dependent on the effort by the motor - cfm and static pressure.To determine the total unit static pressure:

External Static (duct system)

 

110 Pa

Standard Filter 1 in.

37 Pa

from Table PD-21

 

Economizer

5 Pa

(100% Return Air)

from

Table PD-21

 

Electric Heater Size 7.5 kW

17 Pa

from Table PD-21

 

Total Static Pressure

169 Pa

Note: The Evaporator Fan Performance Table PD-6 has deducted the pressure drop for a 25 mm filter already in the unit (see note belowTable PD-6). Therefore, the actual total static pressure is 169-17 (fromTable PD-21) = 152 Pa.

With 3400 m3/h and 152 Pa

Table PD-6 shows .67 kW for this unit. Note below the table gives a formula to calculate Fan Motor Heat,

Fan Motor Heat (kw) =

1.144 x (Fan kW) + 0.132

= 1.144 x 0.67 + 0.132 = 0.90 kW

Now subtract the fan motor heat from the gross cooling capacity of the unit: Net Total Cooling Capacity

= 17.8 kW - 0.9 = 16.9 kW.

Net Sensible Cooling Capacity = 14.4 kW - 0.9 = 13.5 kW.

Step 4

If the performance will not meet the required load of the building’s total or sensible cooling load, try a selection at the next higher size unit.

Heating Capacity

Step 1

Calculate the building heating load using theTrane calculation form or other standard accepted method.

Step 2

Size the system heating capacity to match the calculated building heating load. The following are building heating requirements:

A

Total heating load of 5 kW

B

2000 cfm

C

380 volt/3 phase Power Supply

The electric heat accessory capacities are listed inTable PD-23. From the table, the smallest heater will deliver 7.5 kW at 380 V. Referring toTable ED-2, the electric heater selection is BAYHTRR412A.

Air Delivery Selection

External static pressure drop through the air distribution system has been calculated to be 110 Pa. FromTable PD- 21 static pressure drop through the economizer is 5 Pa and the 7.5 kW heater is 17 Pa (110 + 5 + 17). EnterTable PD-6 for a TSC060AD at 3400 m3/h and 132 Pa static pressure. The standard motor will give the desired airflow at a rated kW of 0.64.

Accessory Selection

Select accessories needed to accommodate the application.

10

RT-PRC016-EN

Image 10
Contents Packaged Cooling with Electric Heat Rooftop Units Introduction American Standard Inc. All rights reservedContents Features and Benefits Standardized Components Easy Access Low Voltage Terminal BoardFlexible Applications Micro Controls ReliaTel MicroEconomizer Hinged Access DoorsPhase Monitor Comm-3/4Trane Communication InterfaceWe test designs at our factory not on our customers Quality And Reliability TestingVariTrac Clearance Requirements Barometric ReliefCondensate Trap Unit PitchHeating Capacity Step Accessory SelectionCooling Capacity Step Air Delivery SelectionSelection Procedure IP Units Model Number Description 060 11 12,13General Data Table GD 1 General DataTable PD-1 Gross Cooling Capacities kW -TSC060AD SI Performance DataTable PD-1a Gross Cooling Capacities MBH TSC060AD IP Table PD-2 Gross Cooling Capacities kW -TSC072AD SI Table PD-2a Gross Cooling Capacities MBH -TSC072AD IPTable PD-3 Gross Cooling Capacities kW -TSC090AD SI Table PD-3a Gross Cooling Capacities MBH -TSC090AD IPTable PD-4 Gross Cooling Capacities kW -TSC102AD SI Table PD-4a Gross Cooling Capacities MBH -TSC102AD IPTable PD-5 Gross Cooling Capacities kW -TSC120AD SI Table PD-5a Gross Cooling Capacities MBH -TSC120AD IP2 HP Standard Motor & Drive ← 1.12 Nom kW Standard MotorHi Static Drive ← 1-1/2 HP Standard Motor← 1.12 Nom kW Standard Motor & Hi Static Drive Nom kW Standard Motor & Drive2 HP Standard Motor 2 HP Standard Motor Hi Static Drive Nom kW Std MotorNom kW Over-Sized Motor Hi Static Drive 2 HP Standard Mtr Drive2 HP Standard Motor & Low Static Drive Nom kW Standard Motor & Hi Static DriveNom kW Over-Sized Motor & Hi Static Drive 2 HP Std Motor & Hi Static DriveHP Standard Mtr HP Standard Motor Drive Hi Static Drive HP Std Motor & Low Static Drive Nom kW Standard Motor & Drive Nom kW OSMotor & Hi Static Drive HP Std Motor & Hi Static Drive HP Over-Sized MotorHP Standard Motor & Low Static Drive Nom kW Over-Sized Motor & High Static DriveHP Standard Mtr & Drive HP Std Motor & Hi Static Drive HP Std Mtr & Low Static Drive Nom kW Std Mtr Nom kW Over-Sized High Static DriveNom kW Standard Motor & High Static Drive HP Over-Sized Mtr & DriveNom kW Standard Motor & Low Static Drive 275 300 325 350 375 400 425 450 475 500 HP Standard Motor & High Static DriveTable PD-16 Standard Motor & Sheave/Fan Speed RPM Table PD-20 Sound Power Level dB ref -12WattsTable PD-19 Oversized Motor & Drive Sheave/Fan Speed RPM 100% OA 100% RA Model No M3/h EconomizerUnit Airflow Standard Pleated Filters OA/RA Dampers2 Downflow Horizontal 13-27Table PD-23 Auxiliary Electric Heat Capacity SI Table PD-23A Auxiliary Electric Heat Capacity IP11.3 13.5 07.5 09.010.9 13.0 14.4 17.2Zone Sensors Zone ControlsAutomatic Changeover One Heat Table ED-1 Unit Wiring Electrical DataZone Sensors Typical Number Of Wires Jobsite ConnectionsDimensional TSC060DataTSC060 DataTSC060 TSC072-090 TSC102-120 DataTSC072-120 ALL Flanges 1 1/4 31 MM TSC060 Economizer , Manual or Motorized Fresh Air Damper Dimensional TSC060TSC060 Swing Diameter for Hinged Doors Option Dimensional TSC072-120 Table W-2 Accessory Net Weights1 2 kg WeightsTable W-2a Accessory Net Weights1 2 lbs Mechanical Specifications Roof Curb Clogged Filter/Fan Failure SwitchElectric Heaters Remote PotentiometerZone Sensor Differential Pressure SwitchesComm-5 LonTalk Communication Interface ThermostatsSupersedes PL-UN-000-RT-PRC016-EN-12-03 Literature Order NumberFile Number PL-UN-000-RT-PRC016-EN-02-04 Stocking Location 03-03Webb/Mason 02-04 Electronic Only

TSC060-120 specifications

The Trane TSC060-120 is a prominent member of Trane's commercial HVAC (Heating, Ventilation, and Air Conditioning) systems, designed to meet the demands of various applications, from small offices to larger commercial venues. This model is part of Trane’s variable refrigerant flow (VRF) systems, which are known for their energy efficiency and flexibility.

One of the standout features of the TSC060-120 is its capacity range, which allows for cooling and heating capacities between 60,000 to 120,000 BTUs. This makes it suitable for diverse environments, adapting well to fluctuating load requirements. Additionally, the unit is designed with a modular approach, meaning that multiple units can be connected to meet larger capacity needs without sacrificing efficiency.

The Trane TSC060-120 incorporates advanced inverter technology, which helps optimize energy consumption by adjusting the compressor speed based on the real-time thermal load of the building. This results in a significant reduction in energy costs and improved comfort levels for occupants. The unit also features a high-efficiency multi-stage filtration system that not only ensures clean air circulation but also contributes to the overall indoor air quality.

The system utilizes a compact and versatile design, allowing for flexible installation options. Its lightweight structure and smaller footprint make it easier to install in tight spaces while still accommodating a powerful performance. The TSC060-120 is designed for quiet operation, which is crucial for noise-sensitive environments, delivering comfort without disruptive sound levels.

In terms of control and monitoring, the TSC060-120 is compatible with Trane's advanced building management systems. This integration allows facility managers to monitor energy usage, schedule maintenance, and control temperatures remotely, enhancing overall operational efficiency.

Moreover, the unit is built with sustainability in mind, using eco-friendly refrigerants that comply with the latest environmental regulations. This commitment to sustainability not only minimizes the ecological footprint but also positions the Trane TSC060-120 as a forward-thinking choice for businesses looking to enhance their energy strategy.

In summary, the Trane TSC060-120 stands out for its efficiency, flexibility, and advanced technology, making it a solid choice for commercial HVAC applications. With its combination of high performance, advanced control features, and commitment to sustainability, it provides an effective solution for modern climate control needs.