Trane TSC060-120 manual Selection Procedure IP Units

Page 11

Selection Procedure - IP Units

Cooling Capacity

Step 1

Calculate the building’s total and sensible cooling loads at design conditions. Use theTrane calculation methods or any other standard accepted method.

Factors used in unit selection:

A

Total Cooling Load: 59 MBh

B

Sensible Cooling Load: 40 MBh

C

Airflow: 2000 cfm

D

Electrical Characteristics: 380-415/50/3

E

Summer Design Conditions: Entering

Evaporator Coil: 80 DB, 67 WB Outdoor

Ambient: 95

F

External Static Pressure: 0.45 in. wg

Step 2

Table PD-1a shows that aTSC060AD has a gross cooling capacity of 62.0 MBh and

46.4MBh sensible capacity at 2000 cfm and 95 DB outdoor ambient with 80 DB, 67 WB air entering the evaporator.

To Find Capacity at Intermediate Conditions Not in the Table

When the design conditions are between two numbers that are in the capacity table, interpolation is required to approximate the capacity. Note: Extrapolation outside of the table conditions is not recommended.

Step 3

In order to select the correct unit which meets the building’s requirements, the fan motor heat must be deducted from the gross cooling capacity.The amount of heat that the fan motor generates is dependent on the effort by the motor - cfm and static pressure.To determine the total unit static pressure:

External Static (duct system)

 

0.45 wg

Standard Filter 1 in.

0.15 wg

from Table PD-21a

 

Economizer

0.02 wg

(100% Return Air)

from

Table PD-21a

 

Electric Heater Size 26 MBh

0.07 wg

from Table PD-21a

 

Total Static Pressure

0.69 wg

Note: The Evaporator Fan Performance Table PD-6a has deducted the pressure drop for a 1 in. filter already in the unit (see note below Table PD-6a). Therefore, the actual total static pressure is 0.69 - 0.15 (fromTable PD-21a) = 0.50 wg.

With 2000 cfm and 0.50 wg.

Table PD-6a shows .83 bhp for this unit. Note below the table gives a formula to calculate Fan Motor Heat,

Fan Motor Heat (MBh) =

2.915 x (Fan BHP) + 0.451

= 2.915 x 0.83 + 0.451 = 2.87 MBh

Now subtract the fan motor heat from the gross cooling capacity of the unit: Net Total Cooling Capacity

= 62 MBh - 2.87 = 59.1 MBh.

Net Sensible Cooling Capacity = 46.4 MBh - 2.87 = 43.5 MBh.

Step 5

If the performance will not meet the required load of the building’s total or sensible cooling load, try a selection at the next higher size unit.

Heating Capacity

Step 1

Calculate the building heating load using theTrane calculation form or other standard accepted method.

Step 2

Size the system heating capacity to match the calculated building heating load. The following are building heating requirements:

A

Total heating load of 15 MBH

B

2000 cfm

C

380 volt/3 phase Power Supply

The electric heat accessory capacities are listed inTable PD-23a. From the table, the smallest heater will deliver 26 MBh at 380 volts. Referring toTable ED-2, the electric heater accessory selection is BAYHTRR412A.

Air Delivery Selection

External static pressure drop through the air distribution system has been calculated to be 0.45 inches of water. FromTable PD-21a static pressure drop through the economizer is 0.02 and the 26 kW heater is 0.07 inches of water (0.45

+0.02 + 0.07). EnterTable PD-6a for a TSC060AD at 2000 cfm and 0.54 static pressure. The standard motor will give the desired airflow at a rated bhp of about 1.01.

Accessory Selection

Select accessories needed to accommodate the application.

RT-PRC016-EN

11

Image 11
Contents Packaged Cooling with Electric Heat Rooftop Units American Standard Inc. All rights reserved IntroductionContents Features and Benefits Flexible Applications Easy Access Low Voltage Terminal BoardStandardized Components ReliaTel Micro Micro ControlsComm-3/4Trane Communication Interface Hinged Access DoorsPhase Monitor EconomizerVariTrac Quality And Reliability TestingWe test designs at our factory not on our customers Unit Pitch Barometric ReliefCondensate Trap Clearance RequirementsAir Delivery Selection Accessory SelectionCooling Capacity Step Heating Capacity StepSelection Procedure IP Units 060 11 12,13 Model Number DescriptionTable GD 1 General Data General DataTable PD-1a Gross Cooling Capacities MBH TSC060AD IP Performance DataTable PD-1 Gross Cooling Capacities kW -TSC060AD SI Table PD-2a Gross Cooling Capacities MBH -TSC072AD IP Table PD-2 Gross Cooling Capacities kW -TSC072AD SITable PD-3a Gross Cooling Capacities MBH -TSC090AD IP Table PD-3 Gross Cooling Capacities kW -TSC090AD SITable PD-4a Gross Cooling Capacities MBH -TSC102AD IP Table PD-4 Gross Cooling Capacities kW -TSC102AD SITable PD-5a Gross Cooling Capacities MBH -TSC120AD IP Table PD-5 Gross Cooling Capacities kW -TSC120AD SI← 1-1/2 HP Standard Motor ← 1.12 Nom kW Standard MotorHi Static Drive 2 HP Standard Motor & Drive2 HP Standard Motor Nom kW Standard Motor & Drive← 1.12 Nom kW Standard Motor & Hi Static Drive 2 HP Standard Mtr Drive Nom kW Std MotorNom kW Over-Sized Motor Hi Static Drive 2 HP Standard Motor Hi Static Drive2 HP Std Motor & Hi Static Drive Nom kW Standard Motor & Hi Static DriveNom kW Over-Sized Motor & Hi Static Drive 2 HP Standard Motor & Low Static DriveHP Standard Mtr HP Standard Motor Drive Hi Static Drive HP Std Motor & Hi Static Drive HP Over-Sized Motor Nom kW Standard Motor & Drive Nom kW OSMotor & Hi Static Drive HP Std Motor & Low Static DriveHP Standard Mtr & Drive HP Std Motor & Hi Static Drive Nom kW Over-Sized Motor & High Static DriveHP Standard Motor & Low Static Drive HP Over-Sized Mtr & Drive Nom kW Std Mtr Nom kW Over-Sized High Static DriveNom kW Standard Motor & High Static Drive HP Std Mtr & Low Static DriveNom kW Standard Motor & Low Static Drive HP Standard Motor & High Static Drive 275 300 325 350 375 400 425 450 475 500Table PD-19 Oversized Motor & Drive Sheave/Fan Speed RPM Table PD-20 Sound Power Level dB ref -12WattsTable PD-16 Standard Motor & Sheave/Fan Speed RPM Downflow Horizontal 13-27 EconomizerUnit Airflow Standard Pleated Filters OA/RA Dampers2 100% OA 100% RA Model No M3/hTable PD-23A Auxiliary Electric Heat Capacity IP Table PD-23 Auxiliary Electric Heat Capacity SI14.4 17.2 07.5 09.010.9 13.0 11.3 13.5Automatic Changeover One Heat Zone ControlsZone Sensors Electrical Data Table ED-1 Unit WiringJobsite Connections Zone Sensors Typical Number Of WiresTSC060 DimensionalDataTSC060 DataTSC060 TSC072-090 TSC102-120 DataTSC072-120 ALL Flanges 1 1/4 31 MM TSC060 Swing Diameter for Hinged Doors Option Dimensional TSC060TSC060 Economizer , Manual or Motorized Fresh Air Damper Dimensional TSC072-120 Table W-2a Accessory Net Weights1 2 lbs WeightsTable W-2 Accessory Net Weights1 2 kg Mechanical Specifications Remote Potentiometer Clogged Filter/Fan Failure SwitchElectric Heaters Roof CurbThermostats Differential Pressure SwitchesComm-5 LonTalk Communication Interface Zone SensorStocking Location 03-03Webb/Mason 02-04 Electronic Only Literature Order NumberFile Number PL-UN-000-RT-PRC016-EN-02-04 Supersedes PL-UN-000-RT-PRC016-EN-12-03

TSC060-120 specifications

The Trane TSC060-120 is a prominent member of Trane's commercial HVAC (Heating, Ventilation, and Air Conditioning) systems, designed to meet the demands of various applications, from small offices to larger commercial venues. This model is part of Trane’s variable refrigerant flow (VRF) systems, which are known for their energy efficiency and flexibility.

One of the standout features of the TSC060-120 is its capacity range, which allows for cooling and heating capacities between 60,000 to 120,000 BTUs. This makes it suitable for diverse environments, adapting well to fluctuating load requirements. Additionally, the unit is designed with a modular approach, meaning that multiple units can be connected to meet larger capacity needs without sacrificing efficiency.

The Trane TSC060-120 incorporates advanced inverter technology, which helps optimize energy consumption by adjusting the compressor speed based on the real-time thermal load of the building. This results in a significant reduction in energy costs and improved comfort levels for occupants. The unit also features a high-efficiency multi-stage filtration system that not only ensures clean air circulation but also contributes to the overall indoor air quality.

The system utilizes a compact and versatile design, allowing for flexible installation options. Its lightweight structure and smaller footprint make it easier to install in tight spaces while still accommodating a powerful performance. The TSC060-120 is designed for quiet operation, which is crucial for noise-sensitive environments, delivering comfort without disruptive sound levels.

In terms of control and monitoring, the TSC060-120 is compatible with Trane's advanced building management systems. This integration allows facility managers to monitor energy usage, schedule maintenance, and control temperatures remotely, enhancing overall operational efficiency.

Moreover, the unit is built with sustainability in mind, using eco-friendly refrigerants that comply with the latest environmental regulations. This commitment to sustainability not only minimizes the ecological footprint but also positions the Trane TSC060-120 as a forward-thinking choice for businesses looking to enhance their energy strategy.

In summary, the Trane TSC060-120 stands out for its efficiency, flexibility, and advanced technology, making it a solid choice for commercial HVAC applications. With its combination of high performance, advanced control features, and commitment to sustainability, it provides an effective solution for modern climate control needs.