Prefabricated Chimneys
A prefabricated metal chimney must be one tested and listed for use with
A horizontal connector run should be inclined 1/4” per foot (20 mm per meter) from the stove toward the chimney. The recommended maximum length of a hori- zontal run is 3 feet (1m) and the total length of chimney connector should be no longer than 8 feet (2.5m).
Chimney Height
For proper draft and good performance, the chimney should extend at least 16’ (5 m) above the flue collar of the stove.
The chimney must also extend at least 3’ (914 mm) above the highest point where it passes through a roof, and at least 2’ (610 mm) higher than any portion of a building within 10’ (3 m). (Fig. 2)
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
| 0 To 10' |
|
| 2' Min. 3' | 0 To 10' |
| Min. |
|
|
| 2' Min. 3' |
|
| Min. |
| Reference |
|
| Point |
|
|
| AC246 |
Fig. 3 | The 2/3/10 rule for chimneys. |
Chimney Size
The Model 2479 heater should be vented into a ma- sonry chimney with a square flue with nominal flue size of 8” x 8” (203 x 203 mm), or a round flue with nominal flue size of 6” (152 mm).
Chimney liners larger than 8” x 12” (203 x 305 mm) may promote rapid cooling of smoke and reduction in draft, especially if they are located outside the home. These large chimneys may need to be insulated or have their flues relined for proper stove performance.
Accessories to help make the connection between stainless steel chimney liners and the stove are avail- able through your local dealer.
Dutchwest
Guidelines for Installing the Chimney Connector
The chimney connector is the
Do not pass the chimney connector through a combus- tible wall, floor, or ceiling, through an attic or roof space, or through a closet or similar concealed space. If pas- sage through a combustible wall is unavoidable, follow the recommendations in the following section on Wall
Two Types of Connector
You may use either a
Single-Wall Connector
The
Install
In cathedral ceiling installations, extend the prefabri- cated chimney downward to within 8 feet (2.5 meters) of the stove. The entire chimney connector should be exposed and accessible for inspection and cleaning.
Do not use galvanized chimney connector; it cannot withstand the high temperatures that can be reached by smoke and exhaust gases and it may release toxic fumes under high heat.
Chimney | Flue Liner |
| |
Elbow | Flue |
| Thimble |
Slip Pipe
Standard Connector
Flue Collar
Floor Protector
ST418
Fig. 4 Sections of a steel chimney connector of at least 24 gauge thickness are fastened together with screws to connect the stove to the chimney.
30002291 | 5 |