Vermont Casting 2823, 820, 2828, 2825 Restictor Plate is used on Direct Vent installations only

Page 8

Vermont Castings Jefferson Direct Vent/Natural Vent Gas Heater

Vertical Termination - Direct Vent ONLY

Vent Termination Clearances

A vertical vent system must terminate no less than 8' (2.44m) and no more than 40Õ (12m) above the appli- ance flue collar. A 2¹⁄₄" restrictor plate (supplied) must be used, where specified, in all vertically terminated vent systems. (Refer to Figure 8) NOTE: The restrictor plate supplied with the vertical termination should be discarded. Install restrictor plate supplied with the stove directly at stove outlet. A vertically terminated vent system must also conform to the following criteria:

¥No more than two 90û elbows may be used.

¥Two 45û elbows may be substituted for one 90û elbow. No more than six elbows may be used.

¥Vent must rise a minimum of 2 feet before offset is used.

¥Termination height must conform to roof clearance as specified in Figure 9.

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

39

ALL VERTICAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38

TERMINATIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

37

 

 

 

 

 

 

 

 

 

 

 

 

 

REQUIRE USE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36

 

 

 

 

 

 

 

 

 

 

 

 

 

pipe.)

35

OF THE 2¹⁄₄Ó

 

 

 

 

 

 

 

 

 

 

 

 

 

 

34

RESTRICTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

vent

33

 

 

 

 

 

 

 

 

 

 

 

 

 

PLATE*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

top

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to the

29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(in feet)

flue collar

27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

 

Vertical terminations

 

 

 

 

 

 

 

 

 

 

 

 

Vertical Run

the appliance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

must be within this area

 

 

 

 

 

 

 

 

 

 

 

23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Measure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

 

 

 

 

 

 

 

 

 

 

 

 

Unacceptable

 

 

 

 

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Venting Configuration

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

Horizontal Run (in feet)

ST132a

Fig. 8 Vertical vent termination window.

*The Restictor Plate is used on Direct Vent installations only.

When planning the installation, consider the location of the vent terminal and clearances. Some of the most common clearances to keep in mind are shown in Figure 10.

Important: All vent clearances must be maintained. Check your vent termination clearances against Figures 10 and 11.

The vent should be placed so that people cannot be burned by accidentally touching the vent surfaces when the stove is operating.

The vent termination should be located where it cannot be damaged by such things as automobile doors, lawn mowers or snowblowers and it should be located away from areas where it could become blocked by snow, etc.

Some considerations are:

¥Obstructions or impediments to venting.

¥Nearby combustible materials that could come into contact with combustion exhaust gases.

¥Other nearby openings {within 9" (230mm)} through which exhaust gas could reenter the building.

¥All vegetation within 3' (.9m) that may interfere with the draft.

Other factors that influence where the installation will be sited include the location of outside walls, where addi- tional heat may be desired in the home, where the family members gather most regularly, and perhaps most importantly, the distance limitations of the venting system.

IMPORTANT

Direct Vent Only

¥The horizontal termination must not be recessed into the exterior wall or siding.

¥Horizontal vent runs must be level toward the vent termination.

¥Clearances around the vent termination must be maintained.

¥For installations using Simpson DuraVent pipe, parallel installations with minimum wall clearance have restricted access for connecting the Horizon- tal Vent Cap straps to the vent pipe. See the makerÕs instructions for recommended installation procedures.

8

20002191

Image 8
Contents Jefferson Table Of Contents Installation & Operating Instructions Jefferson Direct Vent/ Natural Vent Stove Dimensions Jefferson dimensionsClearance Requirements Installation RequirementsLocating the Stove Wall Thimble Centerline from Floor Hearth RequirementsGas Specifications Gas Inlet and Manifold PressuresHorizontal Termination Direct Vent only High ElevationsRestictor Plate is used on Direct Vent installations only PlateVent Termination Clearances Direct Vent only Location of Vent TerminationCanadian Installations US Installations General Venting Information Termination LocationSupplied with the stove is not used Venting Requirements Natural Vent OnlyHorizontal Run in feet Venting Requirements and Options Direct Vent only Minimum Horizontal Vent Kit 2792Assembly Procedures Install the Optional FanTools Required Unpack the StoveVenting System Assembly Direct Vent General Information Install the Vent Adapter PipeInstall the Restrictor Plate. Consult the ÔVent Run Install the Outer Adapter Pipe. Apply a 1/4Ó beadSimpson Dura-Vent Components Discard the inner starter pipe shipped withSide Wall Termination Assembly Simpson Dura-Vent install outer adapter pipeVent Termination Below Grade Measure the horizontal lengthVertical Through the Roof Vent Assembly Snorkel kit installationVenting System Assembly Natural Vent General Information Install the Vent PipeInstall the Log Set Aged LogsAir Shutter Adjustment Air Shutter Adjustment InstructionsConnect the Gas Supply Line Burner InformationRemove stove front Install ON/OFF Switch Install the Stove FrontComplete the Assembly This completes assembly of the Jefferson stove Thermostat Connection optionalUse only a thermostat rated for 500 millivolts ThermostatFlame & Temperature Adjustment Flame CharacteristicsOperation Your First FireLighting And Operating Instructions To Turn Off Gas To HeaterTroubleshooting / Honeywell #8420 Gas Control System Symptom Possible Causes Corrective ActionConversion Precautions Conversion ProcedureFuel Conversion Instructions Pilot TypeConversion to Natural Gas Input BTU/h Conversion to LP Input BTU/hMaintenance Gasket Replacement Stove DisassemblyInspect the Vent System Annually Check the Gas Flame RegularlyWiring Diagrams BLKJefferson Direct Vent/Natural Vent Gas Heater DescriptionLeft Right Front Number End Fuel Conversion KitsShell Enamel Part Numbers Model Color Optional Accessories Remote ControlsFan Kits Decorative RingsLimited Lifetime Warranty

2823, 2825, 820, 2827, 2828 specifications

Vermont Casting stoves are renowned for their quality and performance, with models such as the 2823, 2822, 2828, 820, and 2825 exemplifying the brand’s dedication to craftsmanship and innovation. Each model presents unique features and technologies that cater to different heating needs and preferences.

The 2823 model is a testament to Vermont Casting's commitment to efficiency and style. It boasts a clean-burning gas system that maximizes heat output while minimizing emissions. Additionally, the model's design emphasizes both aesthetic appeal and functionality, making it a perfect centerpiece for any room. With its user-friendly controls, it allows easy adjustments to heat levels, offering a tailored experience for homeowners.

The 2822 model is known for its compact design, making it an ideal choice for smaller spaces. Despite its size, it does not compromise on performance, delivering a substantial heat output. This model is equipped with a dual-burner system that enhances its heating capabilities, ensuring a consistent and comfortable environment. Furthermore, its built-in safety features provide peace of mind, allowing users to enjoy their heating solution with confidence.

In contrast, the 2828 model offers a higher output, perfect for larger areas. Its innovative heat exchanger technology ensures optimal heat distribution throughout the space, making it a favorite among those with bigger homes. The model’s sleek design and customizable options allow homeowners to choose finishes that complement their existing decor, enhancing both the visual and functional aspects of their living areas.

The 820 model stands out with its unique style, offering a combination of traditional and modern aesthetics. This model features a powerful combustion system that maximizes efficiency while reducing fuel consumption. Its large viewing window provides a beautiful fire display, turning any space into a cozy retreat. The 820 is particularly favored among users who appreciate the ambiance of a traditional fireplace with the convenience of modern technology.

Finally, the 2825 model is designed for users seeking maximum customization. Its adjustable heating options and multiple finish choices allow homeowners to create a truly personalized experience. The advanced technology incorporated into the 2825 ensures enhanced performance, making it one of the most sought-after models in the Vermont Casting lineup.

In summary, the Vermont Casting 2823, 2822, 2828, 820, and 2825 models each have their unique features that cater to different heating needs. With advanced combustion technologies, customizable designs, and a commitment to efficiency, these stoves highlight Vermont Casting's reputation for quality and innovation in home heating solutions.