Seville 1635 Clearance Chart

Use the chart below together with the diagrams on the next page to determine the minimum clearance required for your particular installation. In any case, it is always advisable to locate the stove as far away from walls as pos- sible in order to take full advantage of the radiant properties of cast iron.

Stove clearances are measured between the steel rear shroud and the combustible surface.

Chimney Connector clearances are measured between the connector surface and the combustible surface. For Douible-wall Chimney Connector, use the manufacturer’s listed clearance specification.

Use NFPA 211 default clearance or manufacturer’s installation specifications for those configurations not tested.

UNPROTECTED SURFACES

PROTECTED SURFACES

 

 

 

 

 

Parallel Installation

 

Corner

Parallel Installation

 

Corner

 

 

 

STOVE CLEARANCE

 

 

 

Installation

 

Installation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Side

Rear

 

Corner

Side

 

Rear

 

Corner

 

 

 

 

 

 

 

 

 

 

 

 

With Single-wall Connector

A 18”

 

B 15”

 

C 12”

D 13”

 

E 8”

 

F 6”

 

 

 

 

 

 

(457mm)

(381mm)

 

(305mm)

(330 mm)

 

(203mm)

 

(152mm)

 

 

 

With Single-wall Connector

G 14”

 

H 10”

 

I 6”

J 12”

 

K 6”

 

L 4”

 

 

 

 

and Connector Heat Shields

(357mm)

(254mm)

 

(152mm)

(305mm)

 

(152mm)

 

(102mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

With Double-wall Connector

G 14”

 

H 10”

 

I 6”

Not

 

Not

 

Not

 

 

 

(357mm)

(254mm)

 

(152mm)

Tested

 

Tested

 

Tested

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHIMNEY CONNECTOR

UNPROTECTED SURFACE / Vertical

PROTECTED SURFACE / Vertical

 

 

 

CLEARANCE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Without Connector Heat Shields

 

10”

(254mm)

 

8”

(203mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

With Connector Heat Shields

 

8”

(203mm)

 

8”

(203mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNPROTECTED SURFACE / Horizontal

PROTECTED SURFACE / Horizontal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-wall Connector

 

18”

(457mm)

 

12” (305mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRONT CLEARANCE

 

 

 

 

ALL INSTALLATIONS

 

 

 

 

 

 

 

TO COMBUSTIBLES*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

48" (1219mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* A distance of 48" must be maintained between the stove and moveable combustible items such as drying

 

 

 

 

 

clothes, furniture, firewood, etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1. Approved Seville Clearances.

 

 

 

 

 

 

 

 

 

 

 

 

12

30001490

Image 12
Contents Seville Table of Contents Installation AccessoriesIntroduction Specifications Seville, ModelInstallation ChimneysMasonry Chimneys Chimney Connector Guidelines Prefabricated ChimneysChimney Size Masonry Chimneys, contdDouble-wall Chimney Connectors Single-wall Chimney ConnectorsSecuring the Single-wall Connector to a Masonry Chimney Freestanding InstallationsConnection Above the Fireplace Wall Pass-throughsAlternate methods approved by the Nfpa Wall Pass-through with ventilated steel thimble Floor Protection Fireplace Hearth ProtectionClearance to Surrounding Combustible Materials Safe Ways To Reduce ClearancesWall Shields Wall shields Seville 1635 Clearance Chart Stove ClearanceAlcove Installations Stove Installed Stove in Corner Parallel to WallUnprotected Protected Surfaces Assembly Install the SnapstatHardware Bag contents Unpack the StoveInstall the Fan Install the Rheostat SwitchInstall Stove Legs Pedestal AssemblyInstall the Outside Air Adapter Attach the Chimney ConnectorUse the Air Control Setting that Works Best for You OperationHow the Seville Works Burn Only High-Quality WoodStarting and Maintaining a Fire Conditioning Your Stove Burn Rate Primary Air Control Shutter PositionStart a fire with small, dry kindling Refuel While the Embers Are Still Hot Ash DisposalSmoke Detectors Maintenance Adjust the Door CreosoteAnnual Maintenance Clean the Primary Air OutletDraft Management Steel Chimney Inside/Outside LocationFlue Sizing Pipe & Chimney LayoutBackpuffing Negative PressureConclusion Seville Woodburning Stove Seville Vermont Castings, Majestic Products