Vermont Casting 1636, 1635, 1638, 1637 Connection Above the Fireplace, Wall Pass-throughs

Page 7

Connection Above the Fireplace

In this installation, the chimney connector enters the fireplace flue though a thimble located above the fireplace. (Fig. 6) The liner of the fireplace chimney should extend at least to the point at which the chim- ney connector enters the chimney. Follow all the guidelines for installing a chimney connector into a freestanding masonry chimney, and pay special attention to these additional points:

The stove and chimney connector clearances to combustible mantel and trim materials are the same as clearances to combustible walls. If necessary, use a combination of mantel, trim, and connector heat shields to provide the required clearances. Refer to Page 12.

Double-check connector clearance to the ceiling.

The fireplace damper must be closed and sealed to prevent room air from being drawn up the flue which could reduce performance. However, it must be possible to reopen the damper to inspect or clean the chimney.

Floor protection requirements also apply to fireplace installations.

Wall Pass-throughs

Vermont Castings Seville

Chimney Connector

Heat Shield

*

 

Note clearance

 

* requirement on

*

Pages 12-13

 

 

Mantel

ST244

Fig. 6 If the clearance between the chimney connector and either the ceiling or the mantel is inadequate, a protective heat shield is required.

Whenever possible, design the installation so that the connector does not pass through a combustible wall. If you must include a wall pass-through in your installa- tion, check with your building inspector before you begin. Also check with the chimney connector manu- facturer for any specific requirements.

Consult with your dealer regarding special connection components available for use as wall pass-throughs. Use only parts that have been tested and listed for use as a wall pass-through.

U.S. Requirements: The National Fire Protection Association (NFPA) has established guidelines for use

Fire clay liner

A

A

Min. 2" (51mm) Chimney clearance to brick and combustibles

Masonry

 

Min. 12"

Chimney

Flue

(305 mm)

constructed

 

 

 

to NFPA

Chimney

Chimney

211

 

 

connector

 

 

 

 

Fire clay

 

 

liner

A = Minimum 12" (305 mm) brick construction between liner and combustible framing materials

ST272

in the United States for passing chimney connectors through combustible walls. Many building code inspectors follow these guidelines.

Fig. 7 Masonry Wall Pass-through with single wall chimney connector.

Figure 7 shows one NFPA-approved method. All combustible material in the wall is cut away to provide 12" (305mm) clearance to the connector. Brick and mortar are used to enclose the clearance area.

Alternate methods approved by the NFPA:

Using a section of double-wall chimney with a 9"

(229mm) clearance to combustibles. (Fig. 8)

Solid insulated, listed factory- built chimney

length set flush

Min. 9"with flue 229mm

Masonry

Chimney constructed to NFPA 211

 

Min. 2"

 

(51mm)

 

Min. 9"

Flue

(229mm)

Chimney

Chimney

Connector

Air Space

 

Placing a chimney connector pipe inside a steel

double-wall ventilated thimble, which is then sepa-

rated from combustibles by 6" (152mm) of fiber-

glass insulating material. (Fig. 9)

 

 

Non-soluble

24 ga.Sheet

 

Sheet Steel

Steel

 

refractory cement

Supports

 

Supports

ST273

 

 

 

 

 

Fig. 8 Wall Pass-through using factory-built insulated chimney section.

30001490

7

Image 7
Contents Seville Installation Accessories Table of ContentsIntroduction Seville, Model SpecificationsChimneys InstallationMasonry Chimneys Masonry Chimneys, contd Chimney Connector GuidelinesPrefabricated Chimneys Chimney SizeFreestanding Installations Double-wall Chimney ConnectorsSingle-wall Chimney Connectors Securing the Single-wall Connector to a Masonry ChimneyWall Pass-throughs Connection Above the FireplaceAlternate methods approved by the Nfpa Wall Pass-through with ventilated steel thimble Fireplace Hearth Protection Floor ProtectionSafe Ways To Reduce Clearances Clearance to Surrounding Combustible MaterialsWall Shields Wall shields Stove Clearance Seville 1635 Clearance ChartStove Installed Stove in Corner Parallel to Wall Alcove InstallationsUnprotected Protected Surfaces Unpack the Stove AssemblyInstall the Snapstat Hardware Bag contentsPedestal Assembly Install the FanInstall the Rheostat Switch Install Stove LegsAttach the Chimney Connector Install the Outside Air AdapterBurn Only High-Quality Wood Use the Air Control Setting that Works Best for YouOperation How the Seville WorksBurn Rate Primary Air Control Shutter Position Starting and Maintaining a Fire Conditioning Your StoveStart a fire with small, dry kindling Ash Disposal Refuel While the Embers Are Still HotSmoke Detectors Maintenance Creosote Adjust the DoorClean the Primary Air Outlet Annual MaintenanceDraft Management Pipe & Chimney Layout Steel ChimneyInside/Outside Location Flue SizingNegative Pressure BackpuffingConclusion Seville Woodburning Stove Seville Vermont Castings, Majestic Products