Teledyne EHE warranty 3C. Lighting and Shutdown, 3D. Water Chemistry

Page 19

Hi-E2

Page 17

 

 

 

 

GAS CONTROL

KNOB SHOWN

IN “ON” POSITION

Figure 26. Gas Valve.

3C. Lighting and Shutdown

3C-1. Lighting the Heater

Lighting and shutdown instructions are listed on the label attached to the inside of the service door and also on the inside of the control compartment door.

Lighting instructions are as follows:

1.Turn off all electrical power to the heater at the main junction box.

2.Open the control compartment door and turn the gas valve to OFF.

3.Turn the rotary switch on the temperature control panel to OFF.

4.Wait 5 minutes before trying to start the heater.

5.Turn the gas valve control knob counterclockwise to ON (see Figure 26).

6.Replace the control compartment door.

7.Turn on electrical power to the heater.

8.Turn on the filter pump.

9.Turn the rotary switch to either SPA or POOL. Set the temperature control to the desired setting. The ignition control automatically lights the burner when the thermostat calls for heat.

10.Set the time clock, if one is installed.

3C-2. Shutdown

Complete shutdown instructions are as follows:

1.Set both temperature controls to the lowest setting.

2.Turn the rotary switch on the control panel to OFF.

3.Turn off all electrical power to the heater at the main junction box.

4.Open the control compartment door and turn the gas valve knob clockwise to OFF.

5.Turn external gas valve off.

3D. Water Chemistry

3D-1. Pools

The mineral content of swimming pool water increases daily, due to natural evaporation and the addition of sanitizing chemicals. If the mineral concentration in the pool gets too high, the excess minerals will deposit on the walls of the pool, in the filter system, and in the heater tubes. It is important to keep the pH factor of the pool water between 7.4 and

7.6.See Table 7 for guidelines on other chemical measurements.

3D-2. Spas

The proper chemical balance in spa water is more critical than in a swimming pool heater operation. Due to the spa's size, high water temperature, and heavy usage, chemical values in a spa can vary greatly. This chemical imbalance can result in unsanitary water conditions, and affect the life of the heater.

3D-2a. Spa Water Chemistry

Maintaining safe water conditions in a spa can only be done by regular water changes and the proper addition of sanitizing chemicals. Kits are available from your local pool supply dealer for making the various tests for mineral content. One of these kits will detect copper in the system. This is usually a warning that corrosion is taking place, possibly due to a low pH value combined with other chemistry problems. The condition can be corrected by changing the spa water and closely monitoring the pH factor and chemical properties of the water (see Table 7).

Test

Recommended

 

Level*

Free Chlorine or

1.0 to 3.0 ppm

Total Bromine

2.0 to 4.0 ppm

pH

7.2 to 7.6

Total Alkalinity (TA)

100 to 150 ppm

Calcium Hardness (CH)

200 to 400 ppm

Langelier Saturation Index (SI)

-0.5 to +0.5

Cyanuric Acid

30 to 150 ppm

Total Dissolved Solids (TDS)

Less than 1500 ppm

Copper

0 ppm

*As recommended by IPSA

 

 

 

Table 7. Chemical concentration levels.

3D-2b. Water Changing

Teledyne Laars recommends changing of spa water every 60 days if usage is light and every 30 days during heavy usage. Be sure to stabilize the water chemistry after every water change.

Image 19
Contents Installation Hi-E2 Model EHE Gas-Fired Pool Spa Heater Table of Contents General Information Installation InstructionsInstallation at High Elevation 2B. Heater Assembly and Preparation2D. Installation Clearances 2E. Outdoor InstallationUnited States 2F. Outdoor Shelter Installation Canada2G. Indoor Installation 2G-1. Preparation of Heater For Indoor Installation2G-3b. Piping Materials 2G-2. Combustion Air Requirements for One-Pipe Installation2G-3. Two-Pipe Installation Direct Vent 2G-3a. Connection of Combustion Air Pipe2G-3d. Combustion Air and Vent Pipe Installation2G-3c. Size and Length of Combustion Air and Vent Piping Indoor Vent Connection, Hi-E2 Pool Heater 2H. Condensate Disposal 2G-3e. Room Ventilation2I. Gas Supply and Piping 60Hz High Elevation2J-2. Bonding 2J. Electric Wiring2J-1. Electrical Power 2J-3. Auxiliary Time Clock Wiring2K-1. Reversal of Heater Water Connections 2K. Water Piping2K-3. Connections at Heater 2K-5. Automatic Chlorinators Chemical Feeders 2K-4. Pressure Relief Valve2L-1. Normal Operation 2L. Start-up and Adjustment2L-4. Gas Pressure 2L-5. Adjustment of Water Pressure Switch2L-2. Start-up 2L-3. CondensateOperating Instructions 2L-6. Water Temperature Rise3B. Temperature Controls 3A. Start-Up Procedure3D. Water Chemistry 3C. Lighting and Shutdown3D-2c. Corrosion 3E. Spa/Hot Tub Safety Rules3D-2d. Testing 3F. Swimming Pool Energy Savings Tips3G-2. Winterizing 3G. Seasonal Care3H. Periodic Inspection 3G-1. Spring and Fall Operation4A. General Maintenance and Service3H-2. Professional Inspection 4C. Heater Components and Their Operation 4B. Induced-Draft Combustion System4E-1 V Electrical Power Supply 4E. Electrical Trouble Shooting4D. Combustion Air Filter 4E-2a. Transformer 4E-2. Control Circuit Trouble Shooting4E-2b. Fuse 4E-2f. Temperature Control 4E-2c. Fireman Switch and External Interlocks4E-2d. Limit Switches 4E-2e. Water Pressure Switch4F. Venturi Combustion Flow System 4F-2c. Gas Orifice Differential 4F-2. Venturi System Checkout4F-2a. Unfired Venturi Differential Pressure 4F-2b. Gas Pressure Offset4F-3a. Combustion Air Flow 4F-3. Air Flow Investigation4F-5. High Elevation Operation 4G. Combustion Condensate4F-3b. Flow in Heater and Vent 4F-4. Fuel Gas Type and Gas Orifice Size4H. Major Component Service Capacities and Dimensions5A. General Information 6A. Parts List Replacement PartsExploded View of the Hi-E2 Limited Warranty