Vanguard Managed Solutions FLAME-MAX Troubleshooting, Observed Problem Possible Cause Remedy

Page 18

VANGUARD FLAME-MAX®

UNVENTED NATURAL GAS LOG HEATER

TROUBLESHOOTING

Note: For additional help, visit DESA International’s technical service web site at www.desatech.com.

Note: All troubleshooting items are listed in order of operation.

WARNING: Turn off and un- plug heater and let cool before servicing. Only a qualified ser- vice person should service and repair heater.

CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/ pilot unit.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

When ignitor button is pressed, there is no

1.

Ignitor electrode not connected to igni-

1.

Reconnect ignitor cable

spark at ODS/pilot

 

tor cable

 

 

 

2.

Ignitor cable pinched or wet

2.

Free ignitor cable if pinched by any

 

 

 

 

metal or tubing. Keep ignitor cable dry

 

3.

Piezo ignitor nut is loose

3.

Tighten nut holding piezo ignitor to base

 

 

 

 

panel of log set. Nut is located behind

 

 

 

 

base panel.

 

4.

Broken ignitor cable

4.

Replace ignitor cable

 

5.

Bad piezo ignitor

5.

Replace piezo ignitor

 

6.

Ignitor electrode positioned wrong

6.

Replace ignitor

 

7.

Ignitor electrode broken

7.

Replace ignitor

 

 

 

 

 

When ignitor button is pressed, there is

1.

Gas supply turned off or manual shutoff

1.

Turn on gas supply or open manual

spark at ODS/pilot but no ignition

 

valve closed

 

shutoff valve

 

2.

Control knob not in PILOT position

2.

Turn control knob to PILOT position

 

3.

Control knob not pressed in while in

3.

Press in control knob while in PILOT

 

 

PILOT position

 

position

 

4.

Air in gas lines when installed

4.

Continue holding down control knob.

 

 

 

 

Repeat igniting operation until air is

 

 

 

 

removed

 

5.

ODS/pilot is clogged

5.

Clean ODS/pilot (see Cleaning and

 

 

 

 

Maintenance, page 17) or replace ODS/

 

 

 

 

pilot assembly

 

6.

Gas regulator setting is not correct

6.

Replace gas regulator

 

 

 

 

 

ODS/pilot lights but flame goes out when

1.

Control knob not fully pressed in

1.

Press in control knob fully

control knob is released

2.

Control knob not pressed in long enough

2.

After ODS/pilot lights, keep control

 

 

 

 

knob pressed in 30 seconds

 

3.

Safety interlock system has been

3.

Wait one minute for safety interlock sys-

 

 

triggered

 

tem to reset. Repeat ignition operation

 

4.

Manual shutoff valve not fully open

4.

Fully open manual shut-off valve

 

5.

Pilot flame not touching thermocouple,

5.

A) Contact local natural gas company

 

 

which allows thermocouple to cool,

 

 

 

 

causing pilot flame to go out. This prob-

 

B) Clean ODS/pilot (see Cleaning and

 

 

lem could be caused by one or both of

 

Maintenance, page 17) or replace ODS/

 

 

the following:

 

pilot assembly

 

 

A) Low gas pressure

 

 

 

 

B) Dirty or partially clogged ODS/pilot

 

 

 

6.

Thermocouple connection loose at con-

6.

Hand tighten until snug, then tighten 1/4

 

 

trol valve

 

turn more

 

7.

Thermocouple damaged

7.

Replace thermocouple

 

8.

Control valve damaged

8.

Replace control valve

www.desatech.com

18

105187

Image 18
Contents What to do if YOU Smell GAS Patent PendingSafety Information Vanguard FLAME-MAX Unvented Natural GAS LOG HeaterUnpacking Product Features Product IdentificationLocal Codes Unusually Tight Construction AIR for Combustion and VentilationProviding Adequate Ventilation Confined and Unconfined SpaceAIR for Combustion Ventilation Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Building Ventilation AIRVentilation Air From Inside Ventilation Air From OutdoorsInstallation Check GAS TypeMinimum Wall and Ceiling Clearances see Figure Minimum Noncombustible Material Clearances If Using MantelIf Not Using Mantel Eration,Floor Clearances Determining Minimum Mantel Clearance When Using a HoodMantel Clearances Determining Minimum Mantel ClearanceInstalling Damper Clamp Accessory for Vented Operation Installing Heater Base AssemblyInstallation Items Needed Connecting to GAS Supply Vintage Oak Log ChassisGolden Oak Birch Model Chassis Checking GAS Connections Pressure Testing Gas Supply Piping SystemPressure Testing Heater Gas Connections Test Pressures In Excess Of 1/2 PsigInstalling Logs Installing Vintage Oak OneFor Your Safety Read Before Lighting Operating HeaterLighting Instructions To Turn OFF GAS To Appliance Manual Lighting ProcedureVariable Control Operation Shutting Off HeaterPilot Flame Pattern Inspecting BurnersThermostat Control Operation Burner Primary AIR HolesCleaning and Maintenance Replacement PartsTroubleshooting Observed Problem Possible Cause RemedyMaintenance, Top Gas leak. See Warning statement atOptional Positioning of Thermostat Sensing Bulb For Masonry and FACTORY-BUILT Metal FireplaceIllustrated Parts Breakdown FLAME-MAXVINTAGE OAK LOG Models VYS18NA, VYS24NA VYS30NAParts List VYS18NA VYS24NA VYS30NAODS Pilot VYD18NA, VYBD18N VYD24NA, VYBD24N VYD30NA, VYBD30N VYD36N 511 VYD18NTA VYD24NTA VYD30NTA Part Number for VYD18NTA VYD24NTA VYD30NTASpecifications Accessories Service HintsTechnical Service Warranty Information