Vanguard Managed Solutions FLAME-MAX Minimum Noncombustible Material Clearances, If Using Mantel

Page 8

VANGUARD FLAME-MAX®

UNVENTED NATURAL GAS LOG HEATER

INSTALLATION

Continued

NOTICE: Manual control heaters may be used as a vented product. If so, you must always run heater with chimney flue damper open. If running heater with damper open, noncombustible material above fireplace opening is not needed. Go to Installing Damper Clamp Accessory for Vented Op-

If Using Mantel

You must have noncombustible material(s) above the fireplace opening. Noncombus- tible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible mate- rial must extend at least 8 inches up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory (24", 30" and 36" models only).

Even if noncombustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See Figure 5 and Figures 6 and 7 on page 9 for minimum clearances.

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 10.

eration, page 10.

Minimum Noncombustible Material Clearances

If Not Using Mantel

Note: If using a mantel, proceed to If Using Mantel. If not using a mantel, follow the information below.

You must have noncombustible material(s) above the fireplace opening. Noncombus- tible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible mate- rial must extend at least 8" up (for all mod- els). If noncombustible material is less than 12", you must install the fireplace hood accessory (24", 30" and 36" models only). See Figure 5 for minimum clearances.

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 10.

Noncombustible

 

Requirements for

Material Distance (A)

 

Safe Installation

 

 

 

12" or more

 

Noncombustible material OK.

Between 8" and 12"

 

24", 30", or 36" Models: Install fireplace hood ac-

 

 

 

 

 

 

cessory (GA6050, GA6052 or GA6053, see Acces-

 

 

 

 

 

 

sories, page 29).

 

 

 

 

 

 

18" Model: Noncombustible material OK.

Less than 8"

 

Noncombustible material must be extended to at

 

 

 

 

 

 

least 8". See Between 8" and 12", above. If you

 

 

 

 

 

 

cannot extend material, you must operate heater

 

 

 

 

 

 

with flue damper open.

 

 

 

 

 

 

 

Heat Resistant

 

 

 

 

 

 

 

 

 

 

Material

 

 

 

 

 

 

 

(A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.) Above Fireplace

8

105187

Image 8
Contents What to do if YOU Smell GAS Patent PendingSafety Information Vanguard FLAME-MAX Unvented Natural GAS LOG HeaterLocal Codes Unpacking Product FeaturesProduct Identification AIR for Combustion and Ventilation Providing Adequate VentilationUnusually Tight Construction Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation AIR Ventilation Air From InsideBuilding Ventilation Air From OutdoorsMinimum Wall and Ceiling Clearances see Figure InstallationCheck GAS Type If Using Mantel If Not Using MantelMinimum Noncombustible Material Clearances Eration,Determining Minimum Mantel Clearance When Using a Hood Mantel ClearancesFloor Clearances Determining Minimum Mantel ClearanceInstallation Items Needed Installing Damper Clamp Accessory for Vented OperationInstalling Heater Base Assembly Golden Oak Birch Model Chassis Connecting to GAS SupplyVintage Oak Log Chassis Pressure Testing Gas Supply Piping System Pressure Testing Heater Gas ConnectionsChecking GAS Connections Test Pressures In Excess Of 1/2 PsigInstalling Logs Installing Vintage Oak OneLighting Instructions For Your Safety Read Before LightingOperating Heater Manual Lighting Procedure Variable Control OperationTo Turn OFF GAS To Appliance Shutting Off HeaterInspecting Burners Thermostat Control OperationPilot Flame Pattern Burner Primary AIR HolesCleaning and Maintenance Replacement PartsTroubleshooting Observed Problem Possible Cause RemedyMaintenance, Top Gas leak. See Warning statement atOptional Positioning of Thermostat Sensing Bulb For Masonry and FACTORY-BUILT Metal FireplaceIllustrated Parts Breakdown FLAME-MAXVINTAGE OAK LOG Models VYS18NA, VYS24NA VYS30NAParts List VYS18NA VYS24NA VYS30NAODS Pilot VYD18NA, VYBD18N VYD24NA, VYBD24N VYD30NA, VYBD30N VYD36N 511 VYD18NTA VYD24NTA VYD30NTA Part Number for VYD18NTA VYD24NTA VYD30NTASpecifications Technical Service AccessoriesService Hints Warranty Information