Vanguard Heating Gas Log Heater installation manual TROUBLE- Shooting, Maintenance

Page 26

TROUBLE- SHOOTING

OBSERVED

POSSIBLE

 

PROBLEM

CAUSE

REMEDY

 

 

 

Continued

When ignitor button is pressed, there is spark at ODS/pilot but no ignition

1.Gas supply turned off or manual shutoff valve closed

2.Control knob not in PILOT position

3.Control knob not pressed in while in PILOT position

4.Air in gas lines when installed

5.ODS/pilot is clogged

6.Gas regulator setting is not correct

1.Turn on gas supply or open manual shutoff valve

2.Turn control knob to PILOT position

3.Press in control knob while in PILOT position

4.Continue holding down control knob. Repeat igniting operation until air is removed

5.Clean ODS/pilot (see Cleaning and Mainte- nance, page 25) or replace ODS/pilot assembly

6.Replace gas regulator

26

ODS/pilot lights but

1.

Control knob not fully

1.

Press in control knob

flame goes out when

 

pressed in

 

fully

control knob is

2.

Control knob not

2.

After ODS/pilot lights,

released

 

pressed in long enough

 

keep control knob

 

 

 

 

pressed in 30 seconds

 

3.

Safety interlock system

3.

Wait one minute for

 

 

has been triggered

 

safety interlock system

 

 

 

 

to reset. Repeat ignition

 

 

 

 

operation

 

4.

Manual shutoff valve

4.

Fully open manual

 

 

not fully open

 

shut-off valve

 

5.

Pilot flame not touching

5.

A) Contact local

 

 

thermocouple, which

 

natural gas company

 

 

allows thermocouple to

 

 

 

 

cool, causing pilot flame

 

B) Clean ODS/pilot

 

 

to go out. This problem

 

(see Cleaning and

 

 

could be caused by one

 

Maintenance, page 25)

 

 

or both of the following:

 

or replace ODS/pilot

 

 

A) Low gas pressure

 

assembly

 

 

B) Dirty or partially

 

 

 

 

clogged ODS/pilot

 

 

 

6.

Thermocouple connec-

6.

Hand tighten until

 

 

tion loose at control

 

snug, then tighten 1/4

 

 

valve

 

turn more

 

7.

Thermocouple damaged

7.

Replace thermocouple

 

8.

Control valve damaged

8.

Replace control valve

Continued

103515

Image 26
Contents Design OWNER’S Operation and Installation ManualFLAME-MAX Log DesignContents Safety Information Safety InformationProduct Identification Unpacking FeaturesLocal Codes ProductUnusually Tight Construction AIR for Combustion and VentilationProviding Adequate Ventilation Confined and Unconfined SpaceDetermining AIR Flow for Heater Location Determining if You Have a Confined or Unconfined SpaceVentilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Installing Check GAS TypeMinimum Wall and Ceiling Clearances see Figure Minimum Fireplace Clearance To Combustible MaterialsLOG Sizing Requirements Minimum Non Combustible Material Clearances If Using Mantel Installing Installing Damper Clamp Accessory for Vented Operation Attaching Damper ClampInstalling Heater Base Assembly Installation Items NeededAttaching Flexible Gas Hose to Heater Gas Regulator Connecting to GAS Supply Installation Items NeededChecking GAS Connections Gas ConnectionPressure Testing Heater Gas Connections Test Pressures Equal To or Less Than 1/2 PsigInstalling Logs For Vintage Oak Log ModelInstalling Golden Oak or Birch One-Piece Log Set For Golden Oak or Birch ModelsFor Your Safety Read Before Lighting Operating HeaterVariable Control Operation Operating Heater Inspecting Burners Pilot Flame PatternODS/PILOT and Burner Trouble ShootingQualified service person should service and repair heater LogsMaintenance, TROUBLE- ShootingRefer to Air for Com Technical Service Statement at topHints ServiceReplacement Parts Illustrated Parts Breakdown Parts List KEY Part Number for VYS18N VYS24N Description QTYFlame-Max  Golden Oak Birch Log Models VYD24N and VYBD24N Parts List Hood GA6050 AccessoriesValve GA5010 Hood GA6052103515 Warranty Information Keep this Warranty