Vanguard Heating Gas Log Heater installation manual Determining AIR Flow for Heater Location

Page 7

AIR FOR COMBUSTION AND VENTILATION

Continued

DETERMINING AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1. Determine the volume of the space (length x width x height).

Length x Width x Height = ___________________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

____________ (volume of space) ÷ 50 cu. ft. = (maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3. Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

___________________ Btu/Hr

Gas water heater*

 

___________________ Btu/Hr

Gas furnace

 

___________________ Btu/Hr

Vented gas heater

 

___________________ Btu/Hr

Gas fireplace logs

 

___________________ Btu/Hr

Other gas appliances*

+ ___________________ Btu/Hr

Total

= ___________________ Btu/Hr

Example: Gas water heater

 

40,000

Btu/Hr

Vent-free heater

+

31,500

Btu/Hr

Total

=

71,500

Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________

Btu/Hr (maximum the space can support)

_________________

Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200

Btu/Hr (maximum the space can support)

71,500

Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 8.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 8.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

103515

7

Image 7
Contents Log Design OWNER’S Operation and Installation ManualFLAME-MAX DesignContents Safety Information Information SafetyProduct Identification Product FeaturesLocal Codes UnpackingConfined and Unconfined Space AIR for Combustion and VentilationProviding Adequate Ventilation Unusually Tight ConstructionDetermining if You Have a Confined or Unconfined Space Determining AIR Flow for Heater LocationVentilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Check GAS Type InstallingLOG Sizing Requirements Minimum Fireplace Clearance To Combustible MaterialsMinimum Wall and Ceiling Clearances see Figure Minimum Non Combustible Material Clearances If Using Mantel Installing Attaching Damper Clamp Installing Damper Clamp Accessory for Vented OperationInstallation Items Needed Installing Heater Base AssemblyAttaching Flexible Gas Hose to Heater Gas Regulator Installation Items Needed Connecting to GAS SupplyGas Connection Checking GAS ConnectionsTest Pressures Equal To or Less Than 1/2 Psig Pressure Testing Heater Gas ConnectionsFor Vintage Oak Log Model Installing LogsFor Golden Oak or Birch Models Installing Golden Oak or Birch One-Piece Log SetOperating Heater For Your Safety Read Before LightingVariable Control Operation Pilot Flame Pattern Operating Heater Inspecting BurnersLogs Trouble ShootingQualified service person should service and repair heater ODS/PILOT and BurnerTROUBLE- Shooting Maintenance,Refer to Air for Com Statement at top Technical ServiceReplacement Parts ServiceHints Illustrated Parts Breakdown KEY Part Number for VYS18N VYS24N Description QTY Parts ListFlame-Max  Golden Oak Birch Log Models VYD24N and VYBD24N Parts List Hood GA6052 AccessoriesValve GA5010 Hood GA6050103515 Keep this Warranty Warranty Information