AIR FOR COMBUSTION AND VENTILATION

Providing Adequate Ventilation (Cont.)

 

Determining Fresh-Air Flow for Heater Location

 

 

AIR FOR COMBUSTION AND VENTILATION

Continued

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1.3/ NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.

*Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.

*Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ___________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space

can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr

Gas water heater*

 

_____________ Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

Other gas appliances* +

_____________ Btu/Hr

Total

=

_____________ Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws com- bustion air from the outdoors and vents to the outdoors.

Example:

 

 

Gas water heater

 

30,000

 

_____________ Btu/Hr

Vent-free heater

+

26,000

_____________ Btu/Hr

Total

=

56,000

_____________ Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 56,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/ Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B.Vent room directly to the outdoors. See Ventilation Air From Out- doors, page 7.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec- tion 5.3 or applicable local codes.

For..com

111043-01A

Image 6
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASTable of Contents Safety InformationLocal Codes Product IdentificationProduct Features AssemblyUnpacking Assembling Hood AIR for Combustion and VentilationProviding Adequate Ventilation Unusually Tight ConstructionDetermining FRESH-AIR Flow for Heater Location Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside Building InstallationVentilation AIR Ventilation Air From OutdoorsInstallation Items Check GAS TypeLocating Fireplace BUILT-IN Fireplace Installation Rough Opening for Installing in WallOptional Mantel Installation Mantel Clearances for Built-In InstallationInstalling Blower Accessory GA3450T Removing Upper Louver AssemblyAssembling Brass Trim Brass Trim Shipped with Mantel Installing Blower Assembly Removing Valve Cover ShieldFor Built-In Installation OutletConnecting to GAS Supply Attaching Wood Base to Solid FloorExtension Cord Connecting Equipment Shutoff Valve to Heater Control Installation Items NeededPressure Testing Gas Supply Piping System Pressure Testing Fireplace Gas ConnectionsChecking GAS Connections For Your Safety Read Before Lighting Operating FireplaceLighting Instructions Inspecting Burner Burner Flame Pattern Cleaning and MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole CabinetTroubleshooting Observed Problem Possible Cause RemedyMaintenance, Gas leak. See Warning statement at Replacement Parts SpecificationsService Hints Technical ServiceIllustrated Parts Breakdown VMH26TNBParts List KEY VMH26TPB VMH26TNB Description QTYAccessories Owners Registration Form Postage Required 111043-01A Warranty Information

WMH26TNB specifications

The Vanguard Heating WMH26TNB is a powerful and efficient heating solution designed to meet the needs of residential spaces. This heating unit stands out for its innovative technology, robust features, and reliability, making it a preferred choice for homeowners looking to maintain a comfortable environment during colder months.

One of the main features of the WMH26TNB is its impressive heating capacity. With an output that can effectively warm spaces up to 1,000 square feet, it ensures consistent and uniform heat distribution throughout the room. This makes it an ideal option for living rooms, bedrooms, and even larger areas, providing a cozy atmosphere for family gatherings and quiet evenings.

Equipped with advanced heating technology, the WMH26TNB utilizes high-efficiency heating elements that minimize energy consumption while maximizing output. This not only helps in reducing electricity bills but also contributes to environmental sustainability. The unit's Energy Star certification further underscores its commitment to energy efficiency, allowing homeowners to enjoy warmth without compromise.

Another notable characteristic of the Vanguard WMH26TNB is its user-friendly digital thermostat. This intuitive interface allows for precise temperature control and programming, enabling users to set their heating preferences with ease. The programmable functionality means that users can schedule heating times based on their daily routines, ensuring that the space is warm when they need it most, without wasting energy when it's not.

The design of the WMH26TNB is both functional and aesthetically pleasing. Its sleek, modern look allows it to blend seamlessly with various home decors. The unit is also compact, making it easy to install in tight spaces, and it features a durable housing that can withstand the rigors of daily use.

Safety is paramount in any heating appliance, and the WMH26TNB does not disappoint. It includes multiple safety features, such as overheat protection and tip-over shutoff, giving users peace of mind when the unit is in operation.

In summary, the Vanguard Heating WMH26TNB is a versatile heating solution that combines advanced technology, efficient performance, and user-friendly features. Its capacity to efficiently heat large spaces, coupled with energy-saving capabilities, makes it a reliable choice for homeowners seeking warmth and comfort. Whether for everyday use or special occasions, the WMH26TNB stands as a testament to Vanguard's commitment to quality and innovation in heating solutions.