Vanguard Heating VYS18PWA, VYS24PWA, VYS30PWA installation manual AIR for Combustion Ventilation

Page 5

OWNER’S MANUAL

AIR FOR

COMBUSTION AND

VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = _____________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

_______________ (volume of space) x 20 = (maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr

Example:

 

 

 

Gas water heater*

 

_____________ Btu/Hr

Gas water heater

 

40,000

Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vent-free heater

+

31,500

Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

 

Total

=

71,500

Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

 

 

 

 

 

Other gas appliances*

+

_____________ Btu/Hr

 

 

 

 

Total

=

_____________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 71,500 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3 or applicable local codes.

Continued

105190

5

Image 5
Contents Save this manual for future reference OWNER’S Operation and Installation ManualWhat to do if YOU Smell GAS Vanguard Unvented PROPANE/LP GAS LOG Heater Safety InformationRemote Control Accessories Product FeaturesProduct Identification Local CodesProviding Adequate Ventilation AIR for Combustion and VentilationUnusually Tight Construction Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Inside Ventilation AIRBuilding Ventilation Air From OutdoorsInstallation InstallationCheck GAS Type Minimum Fireplace Clearance to Combustible MaterialsMaterial Clearances Minimum NoncombustibleFloor Clearances Mantel ClearancesInstalling Heater Base Assembly Installing Damper Clamp Accessory for Vented OperationInstallation Items Needed Area of Various Standard Round FluesConnecting to GAS Supply Installing GWMS2 Optional Wall Mounted SwitchItems Included for Installation Connecting To Log SetChecking GAS Connections Pressure Testing Gas Supply Piping SystemPressure Testing Heater Gas Connections Installing LogsLighting Instructions For Your Safety Read Before LightingOperating Heater Optional Remote Operation Manual Lighting ProcedureTo Turn OFF GAS To Appliance Pilot Flame Pattern Inspecting BurnersBurner Primary AIR Holes Main BurnerObserved Problem Possible Cause TroubleshootingObserved Problem Possible Cause Remedy Gas leak. See Warning statement at Specifications Wiring DiagramReplacement Parts Service HintsLogs Cleaning and MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole Vintage OAK LOG Models VYS18PWA, VYS24PWA VYS30PWA Illustrated Parts BreakdownVintage OAK LOG Models VYS18PWA, VYS24PWA, VYS30PWA Parts ListAccessories 105190 Warranty Information