Vanguard Heating VMH3000TPSA Ventilation AIR, Ventilation Air From Inside Building

Page 7

OWNER’S MANUAL

AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

Ventilation Air From

Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro- vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 7). You can also remove door into adjoining room (see op-

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

tion 3, Figure 7). Follow the National Fuel Gas Code, NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

WARNING: Rework work- sheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two per- manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

12"

Figure 7 - Ventilation Air from Inside Building

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 8 - Ventilation Air from Outdoors

107102

7

For more information, visit www.desatech.com

Image 7
Contents What to do if YOU Smell GAS VENT-FREE PROPANE/LP GAS MINI-HEARTHHEATERLocal Codes Safety InformationUnpacking AssemblyProduct Features Product IdentificationAssembling and Attaching Brass Trim Attaching Brass Front Trim to Front PanelLocate brass front trim in brass trim package Confined and Unconfined Space AIR for Combustion and VentilationProviding Adequate Ventilation Unusually Tight ConstructionDetermining FRESH-AIR Flow for Heater Location AIR for Combustion VentilationDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Locating Heater InstallationInstallation Items Check GAS TypeThermostat Sensing Bulb Installation OptionsMounting Heater to Wall Mounting Heater on Optional Hearth Base Installing Bottom Mounting ScrewsPlacing Heater On Mounting Bracket Mounting Heater to Optional Hearth Base Mounting Heater to Optional MantelSecuring Hearth Base to Floor External Regulator with Vent Pointing Down Connecting to GAS SupplyPressure Testing Heater Gas Connections Pressure Testing Gas Supply Piping SystemChecking GAS Connections To Turn OFF GAS To Appliance For Your Safety Read Before LightingOperating Heater Lighting InstructionsPilot Flame Pattern Manual Lighting ProcedureInspecting Burner Thermostat Control OperationAfter ODS/pilot lights, keep control TroubleshootingPilot assembly Safety interlock system has beenPane/LP company Maintenance,Position Gas odor even when control knob is in OFFReplacement Parts Cleaning and MaintenanceVMH3000TPSA Illustrated Parts BreakdownKEY VMH3000TPSA Description QTY Parts ListWhen Gas Pressure Is Too Low SpecificationsTechnical Service Service HintsAccessories Warranty Information