Jotul GZ 550 DV II manual Connect the Gas Supply, Gas Supply Requirements, Gas Pressure

Page 14

Connect the Gas Supply

Gas Supply Requirements

ALL INSTALLATIONS MUST COMPLY WITH LOCAL CODE OR IN THE ABSENCE OF LOCAL CODE, MUST COMPLY WITH THE MOST RECENT EDITION OF THE NATIONAL FUEL GAS CODE ANSI Z223.1/NFPA 54 OR CAN-B149.

Shutoff Valve

All codes require a gas shutoff valve (gas cock) and union to be installed in the supply line and in the same room as the appliance. This allows for the disconnection of the fireplace for servicing and maintenance. See fig. 25.

A T-handle gas shutoff valve is required in Massachusetts in compliance with Code 248CMR.

The fireplace and gas control valve must be disconnected from the gas supply piping during any pressure testing of the system at test pressures in excess of 1/2 psig. For pressures lower than 1/2 psig, isolate the gas supply by closing the manual shutoff valve.

Control Valve Connection

The gas supply line connection is made to the left side of the valve. The gas supply line should be a minimum 3/8" diameter, or the appropriate size to provide sufficient gas pressure to the valve regard- less of the input setting.

The use of flexible gas appliance connectors is acceptable in many areas in the U.S. In Canada, methods vary depending on local code. If local codes permit, use flexible gas line for ease of installation and service. For those locales where flexible gas lines are not permitted, use the 3/8” iron fitting to make the connection at the left side of the Control Valve. See Figures 25 and 26.

Secure all joints tightly using appropriate tools and sealing compounds (for propane units, be sure to use compounds that are propane resistant). Turn on gas supply and test for gas leaks using a soapy water solution. Never use an open flame to check for leaks.

Leak test:

Mix a 50-50 solution of water and dish soap.

Light appliance- see lighting instructions on page 23 of this manual or on the fireplace’s rating plate.

Brush or spray all joints and connections with the soapy water solution.

If bubbles appear at any connection or seam or a gas odor is detected, immediately turn gas control knob to the OFF position.

Tighten or reconnect the leaking joint and retest for any gas leaks.

Figure 25. Gas supply line fittings.

Gas Pressure

Proper gas pressure provides a consistent flow of gas to the appliance and is instrumental in checking for gas leaks. The gas control valve on the fireplace is equipped with pressure test points for gauge connections. The gauge connections are located on the front of the valve under the On/Off/ Pilot knob. Gauge connections are identified by:

IN/E for inlet or supply pressure (the amount of gas coming to the valve.)

OUT/A for manifold pressure (the amount of gas that is coming out of the valve to the burner.)

E A

Figure 26. Pressure test point as located on the front of the valve.

14

Image 14
Contents Installation and Operation Instructions Jøtul GZ 550 DV Acadia Direct Vent Gas FireplaceWelcome to Jøtul Table of Contents Input Rates SpecificationsTest Standards Suggested Tools for Installation and Service General InformationPlacement and Framing Safety InformationInstallation Requirements Parallel InstallationCabinet Dimensions Mantel and Trim Clearance Hearth ProtectionFacing and Clearance Requirements Vent Requirements Venting GuidelinesVertical Termination Horizontal TerminationHorizontal Termination Clearance Heightin FeetVariable Vent Restriction Fireplace InstallationOptional Blower Final Cabinet Positioning If appropriate, attach the 4/6 Vent Adaptor CollarGas Pressure Connect the Gas SupplyGas Supply Requirements High Altitude Orifice Chart High Altitude AdjustmentDerating Procedure Excessive gas pressureFuel Conversion Fuel Conversion ProcedureConversion Kit Contents Tools requiredChange the Pilot Orifice Burner OrificeApply the Conversion Labels Adjust the Air Shutter See figChange the Regulator See fig Wall Thermostat Installation Remote ControlBrick Panel Assembly Glass Frame latch locationsLogset Assembly Install Right Log, Rear Log and Left Log in that orderDoor Alignment Adjustment Surround AssemblyDoor Installation Optional Double DoorFlame Appearance / Air Shutter Adjustment System CheckAir Shutter Adjustment Air Inlet SettingsOperation Burner ControlsGlass Care MaintenanceGeneral Cleaning Gasket InspectionWAS Fireplace CON GZ550 Acadia Lllustrated Parts BreakdownGZ 550 DV Acadia Parts GZ 550 DV Optional Accessories QuickFace Fronts w/ ScreenLighting Instructions Control ValveJøtul ASA Jøtul North America

GZ 550 DV II specifications

The Jotul GZ 550 DV II is a remarkable gas fireplace that combines elegance with efficiency, making it a perfect addition to any modern home. Known for its impressive design and advanced technology, this model captures the essence of warmth and sophistication that homeowners seek in their heating solutions.

One of the main features of the Jotul GZ 550 DV II is its contemporary and sleek aesthetic. Available in various finishes, including a rich black or a striking steel, it complements diverse interior styles, from minimalist to rustic. The full-view glass door enhances the visual appeal, allowing the mesmerizing flames to be a focal point of any room.

The fireplace operates on direct vent gas technology, a standout feature that enables it to draw air from the outside instead of depleting indoor air. This not only enhances safety but also improves energy efficiency, making it a more environmentally friendly choice. Homeowners can enjoy consistent heating without worrying about negatively impacting their indoor air quality.

Equipped with variable flame control, the Jotul GZ 550 DV II allows users to adjust the intensity of the flames according to their preferences. Whether it’s a cozy gathering with friends or a quiet evening alone, the adjustable flames provide a tailored ambiance. Additionally, the remote control feature offers convenience, allowing users to ignite or adjust the fireplace from the comfort of their seat.

Another notable characteristic of this gas fireplace is its efficient heat exchanger system. It maximizes heat output while minimizing gas consumption, ensuring homeowners can enjoy warmth without excessive utility bills. The fireplace has an impressive heating capacity, capable of warming medium to large spaces effectively.

Safety features are paramount in the Jotul GZ 550 DV II. It includes a safety screen to prevent any accidental contact with the hot glass, as well as an automatic shut-off mechanism in case of any irregularities, providing peace of mind for families.

In summary, the Jotul GZ 550 DV II is not just a fireplace; it is a blend of modern design, technology, and efficiency. With its elegant aesthetics, direct vent technology, user-friendly controls, and robust safety features, it stands out as a premier option for those looking to enhance their living space with the warmth and beauty of a gas fireplace. It reflects Jotul's commitment to quality and innovation, making it a worthy investment for any home.