Enerco HSU 45, HSU 75 Horizontal Venting General, Vent Termination on Single Wall Vent

Page 7

B – VERTICAL VENTS USING METAL VENT PIPE – COMMERCIAL AND RESIDENTIAL INSTALLATIONS

MHU/HSU compact unit heaters are listed as Category I appliances for vertical vent installations.

1.MHU/HSU unit heaters are to be used with NFPA- or ANSI- approved chimneys, U.L. listed type B-1 gas vents, single wall metal pipe, or listed chimney lining system for gas venting where applicable, as well as the modifications and limitations listed in figure 2. Seal single wall vent material according to the section A - General Recommendations and Requirements.

2.The vent connector shall be 3” (76mm) diameter on 45 units.

In all cases, a flue transition piece (supplied) is required to fit over the outlet of the induced draft assembly on the appliance.

3.Keep the vent connector runs as short as possible with a minimum number of elbows. Refer to the (American)

National Fuel Gas Code ANSI Z223.1 or (Canada) CSA B149.1

Natural Gas and Propane Installation Code for maximum vent and vent connector lengths. Horizontal run of the vent connector from the induced draft blower to the chimney/vent cannot exceed the values in table 2.

4.When the length of a single wall vent, including elbows, exceeds 5 feet (1.5m), the vent shall be insulated along its entire length with a minimum of 1/2” thick foil faced fiberglass 1-1/2# density insulation. If a single wall vent is used in an unheated area it shall be insulated. Failure to do so will result in condensation of flue gases.

5.The unit may be vented vertically as a single appliance or as a common vent with other gas-fired appliances. In common venting situations, vent connectors for other appliances must maintain a 4” (100mm) vertical separation between the vent connectors. Refer to common venting tables in the

(American) National Fuel Gas Code ANSI Z223.1 or (Canada)

CSA B149.1 Natural Gas and Propane Installation Code for proper vent size.

6.Clearance to combustible material is 6” (152mm) for single wall vent material except where a listed clearance thimble is used. Clearance to combustible material for type B-1 vent or factory-built chimney is per manufacturer’s instructions.

7.The vent connector shall be supported without any dips or sags. Vertical vents shall be supported in accordance with their listing and manufacturers’ instructions. All horizontal vent connector runs shall have a slope up to the vertical vent of at least 1/4” per foot (1mm per 50mm).

8.All vertical type B-1 vents, single wall vents, or listed chimney lining system must be terminated with a listed vent cap or listed roof assembly.

9.The vent must extend at least 3’ (1m) above the highest point where it passes through a roof of a building and at least 2’

(0.6m) higher than any part of a building within a horizontal distance of 10’ (3.05m) unless otherwise specified by the

(American) National Fuel Gas Code, ANSI Z223.1 or (Canada) CAN/CGA-B149 Installation Code. The vent must extend at least 5’ (1.6m) above the highest connected equipment flue collar.

C – HORIZONTAL VENTING – GENERAL

Common venting is not allowed when horizontally venting the unit heater.

The minimum horizontal vent length is three feet (914mm).

1.If possible, do not terminate the horizontal vent through a wall that is exposed to prevailing wind. Exposure to excessive winds can affect unit performance.

2.Vent termination must be free from obstructions and at least 12” (306mm) above grade level and maximum snow height.

VENT TERMINATION ON SINGLE WALL VENT

SINGLE WALL TERMINATION

ROOF FLASHING

ROOF PITCHED

FROM 0” TO 45”

2” CLEARANCE

SHALL NOT BE ATHIMBLE CONCEALED SPACE

DOUBLE WALL (TYPE B-1) TERMINATION

ROOF FLASHING

ROOF PITCHED

FROM 0” TO 45”

12” MAX

CLEARANCE TO BE AS

 

 

SPECIFIED ON TYPE “B”

 

VENT PIPE

SEAL JOINT BETWEEN SINGLE WALL VENT

AND “B”VENT AND THE ANNULAR SPACE OF THE “B” VENT

FIGURE 2

3.Do not terminate vent directly below roof eaves or above a walkway, or any other area where condensate dripping may be troublesome and may cause some staining. Avoid windows where steam may cause fogging or ice buildup.

4.When horizontally vented, minimum clearance for termination from any door, window, gravity air inlet, gas or electric meter, regulators, and relief equipment is 4 ft. (1.2m) for U.S. installations. Refer to NFPA 54/ANSI Z223.1 in the U.S.A. and

CSA B149.1 Natural Gas and Propane Installation Code and

.2 in Canada or with authorities having local jurisdiction. In Canada, vent termination must have a minimum 6 ft. (1.8 m) horizontal clearance from gas and electric meters and relief devices as specified in the Canadian B149.1, Natural Gas Installation Code.

Enerco Compact Unit Heater

7

Operating Instructions and Owner’s Manual

Image 7
Contents MR. Heater For Your SafetyStarting Serial Numbers HSU75LPGeneral Hazard Warning ContentsTOP View MHU45/MHU75 and HSU45/HSU75 Unit DimensionsBack View Side View START-UP and Performance Check List Requirements CSA in Canada Garage InstallationsShipping Requirements CSA in the USAGeneral Recommendations and Requirements Unit Heater InstallationCombustion and Ventilation AIR VentingClearance Shall not be Athimble Concealed Space Horizontal Venting GeneralVent Termination on Single Wall Vent Roof Flashing Roof PitchedCondensate Drain Through TEE Pipe and Drain Loop Refer to for maximum vent connector lengthsHorizontal Venting Commercial Horizontal Venting ResidentialVent Termination CAP Listed Thimble Through Combustion Wall Venting Using a Masonry ChimneyHorizontal Venting Residential Installation Removal of Unit from Common VentGAS Supply to Unit Heater Line Voltage Field WiringElectrical Connections GAS Supply ConnectionUnit START-UP GAS ConnectionLeak Check Start UP and OperationAdjustments Service Ladder Diagram Failure to Operate Repair PartsElectrical Flue and ChimneySee Back page for Parts Ordering Information Parts ListEnerco Compact Unit Heater Limited Warranty For Information Regarding ServiceParts Ordering Information Fabricant du directement Comman LA SUR OrmationsinfDœuvre-main Limitée GarantieCompacts chauffage de Appareils nercoE Listepiècesdes NE Lappareilpas Ionne Électrique CircuitVI Intentionnellement Laissée ÉTÉ a Colonne CettePANNEAUCOMMAN6À Nnecteurd Schémacâblageavecduappareilsdes Escalier EN IagrammedCondu Uitd LimiteurCommutateur Gazdu RéglagesAGE Chau LappareilET Émarragedonctionnementf RobertshawSoupape LA Pour VériicationfTension LA À Place SUR Câblage AvertissementAvertissement Chaude GAZ EN AlimentationCommune Ventilation Horizontale Ventilation Rési InstallationMaçonnerie EN Cheminée UNE Utilisant VentilationfRésientield CommercialMilieu Horizontale VentilationdVEN Wallt Single on Termination Vent ET Commerciales InstallationsVentilationb Horizontale VentilationcAtions AGE InstallationET Combustiond Eair VentilationEXIGENCES.U-.É AUX SA Garage UN ANS InstallationsHangars Aéroned171 3/4-6 108 1/4-4 165 1/2-6 140 1/2-5 432 305 HSU45/HSU75 ET MHU45/MHU75DENSIONS AppareilsdesLatérale VUE Arrière VUE Plan EN VUEElgénérale E AngercmmoAvertissement TablematièresdesDébut de série de Numéros Reila AP UFF P CHD EPour Aver

HSU 45, HSU 75 specifications

Enerco HSU 75 and HSU 45 are standout models in the realm of portable heating solutions, designed for efficiency and convenience. These units serve a range of applications, from construction sites to workshops, and even for personal use in outdoor settings. With their robust engineering and advanced features, they are ideal for anyone needing reliable warmth in cold conditions.

One of the main features of the Enerco HSU series is their impressive heating capacity. The HSU 75 offers a maximum output of 75,000 BTU, making it suitable for larger spaces, while the HSU 45 delivers 45,000 BTU, perfect for smaller areas. This flexibility allows users to choose the right model based on their specific heating needs.

Both models utilize a forced air heating system, which efficiently circulates warmth throughout the space. This technology ensures rapid heating, allowing for immediate relief from the cold, an essential feature in situations where time is of the essence.

Durability is another key characteristic of the HSU series. Constructed with heavy-duty materials, these units are built to withstand the rigors of demanding environments. The robust design makes them suitable for outdoor use, capable of enduring tough weather conditions without compromising performance.

Safety is paramount with Enerco heaters, and both the HSU 75 and HSU 45 come equipped with safety features such as automatic shut-off sensors and flame failure devices. These innovations give users peace of mind, knowing that the unit will operate safely even in unpredictable environments.

Portable design is a hallmark of these heaters, featuring built-in handles and a lightweight structure. This makes it easy for users to transport the units from one location to another, enhancing their versatility in use.

Finally, both models are compatible with various fuel sources, allowing for flexibility based on user preference and availability. Whether using propane or natural gas, users can enjoy efficient heating tailored to their requirements.

In conclusion, the Enerco HSU 75 and HSU 45 represent a perfect blend of power, safety, and portability. Their advanced features and durable build make them ideal companions for anyone needing dependable heat in diverse scenarios. With these units, warmth is always within reach, ensuring comfort regardless of the harshness of the outdoor conditions.