Maintenance and Care | Version 06/05 | WTC 600 LP / MP |
|
|
|
3.2During Operation
Drinking water quality is ensured only when the following control intervals are met. In case deviations from the desired condition can not be eliminated through the measures mentioned, the drinking water production must be stopped and the Kärcher Service must be notified.
3.2.1Control and Corrective Action Intervals
d…daily, w…weekly, m… monthly
Interval | Check/Activity | Target/Purpose | In Case of Deviation |
|
|
|
|
d | Level, metering container | Sufficient amount/filling | Fill up; mixing chemi- |
|
|
| cals, |
|
|
| see Section 3.2.6 |
|
|
|
|
| Air bubbles in metering line | No air bubbles | Bleed metering pump, |
|
|
| see Section 3.2.3 |
|
|
|
|
| Flow of drinking water | Reduction of the drinking water | Fine adjustment, |
| based on the operational | flow up to 10 % | see Section 3.2.5 (1) |
|
|
|
|
| Drinking water conductance value | Increase of the drinking water | Fine adjustment, |
| based on the operational | conductance value up to 10 % | see Section 3.2.5 (2) |
|
|
|
|
| Pressure difference between pump | 15 % maximum above | See Section 3.2.5 (3) |
| and concentrate pressure | difference | Kärcher Service |
|
|
|
|
| Hour meter for sand und activated | Backwashing has occurred | Kärcher Service |
| carbon filter * | within the past 24 h |
|
| Pressure difference, fine filter | ≥ 0,8 bar | Replace fine filter, |
|
|
| see Section 3.2.4 |
|
|
|
|
| Visual inspection of the equipment | No leakage | Kärcher Service |
|
|
|
|
w | Fill out operating log |
|
|
|
|
|
|
m | Clean and flush the metering |
|
|
| container |
|
|
|
|
|
|
| Visually check the untreated water | No damages/leaks detectable | Kärcher Service |
| pump |
|
|
|
|
|
|
| Float switch in the drinking water | No operational malfunctions | Kärcher Service |
| tank | detectable |
|
|
|
|
|
* for switching over the indication, see Section 3.2.2
3.2.2Sand and Activated Carbon Filter
During operation, the sand and activated carbon filter control indicates the actual time. To change the indication:
•Press button (32) for approx. 5 s; the display (31) indicates the time of the regeneration.
•Press button (32) briefly; the display indicates the number of regenerations.
•Press the ADVANCE key button briefly; the display indicates the number of days and hours since the last regeneration.
6