Consumption Materials | Version 06/05 | WTC 600 LP / MP |
|
|
|
(2) Metered Addition
For mixing of the chemical, only un- chlorinated drinking water may be used.
This water is taken from the drinking water sampling valve (44).
44
The metered addition is carried out dependent of the level in the metering container.
Completely emptied metering container:
•Fill 10 l of drinking water into the metering con- tainer.
•With a measuring cup, measure the 7.5
•Fill the container with drinking water to the “75 l” mark and mix according to Section 3.1.2.
Partially emptied metering container:
•Read off the level of the fluid with help of the scale at the metering container, e. g., 35 l.
•Determine the quantity to be refilled by sub- tracting the read level from the 75 l. Example: 75 l - 35 l = 40 l.
•Determine the required amount of the respec- tive chemical from the metering table. Example: 4 x the amount for 10 l water.
•Measure the determined amount of the respec- tive chemical and fill into the container.
•Refill amount of water to the “75 l” mark and mix in accordance with Section 3.1.2.
3.3Switching Off the Equipment
If the equipment is not operated for periods exceeding 14 days, it must be preserved by the Kärcher Service. Otherwise permanent damage must be expected.
•Switch the main switch (20) to the “O” position; the equipment stops the drinking water produc- tion.
Never switch off the equipment over- night! Otherwise the automatic clean- ing of the
4 | Consumption Materials |
|
|
| |
Product | Item No. | |
|
| |
RM 852 sterilization agent 24 kg | ||
Chlorinated lime 6 x 870 g | ||
RM 5000 hardness stabilizer 23 kg | ||
RM 5001 flocculation agent 10 l | ||
RM 5001 flocculation agent 60 l | ||
Filter element 5µ | ||
|
|
|