Fedders F80A dimensions Left Inducer Position 35-2, Vent Connector

Page 11

INDUCER ROTATION STEPS ON 35-2, 50-3 (See Figures 5A and 5B below)

1.Ensure all power to the furnace is disconnected.

2.Disconnect inducer wiring and pressure switch tubing.

3.Remove four screws securing inducer and inducer plate to flue box cover plate. (see figure 4A on page 9)

4.Place inducer plate and gasket in desired position and locate mounting holes required. NOTE: INDUCER PLATE AND GASKET MUST BOTH BE ROTATED.

NOTE: Any holes not concealed by the inducer gasket require the use of screws to plug the holes.

5.Secure inducer and inducer plate to flue box cover using four screws in the correct mounting position.

6.Carefully remove side panel knockout corresponding to the venting application and install cover (part #30763) underneath top panel using two screws (field supplied). In the event of a right hand discharge inucer application, the pressure switch will have to be relocated to the underside of the top panel. The pressure switch tubing will have to be cut to the length listed in Table 4 (below) if inducer is mounted in right hand configuration.

7.Reconnect inducer wiring and pressure switch tubing to the inducer

FIGURE 5A: LEFT INDUCER POSITION (35-2, 50-3)

 

 

C2

C3

FF

N

C1

 

WARM AIR FURNACE

VENT CONNECTOR

The furnace may be vented with a listed single wall or Type B double wall vent connector to a B-Vent or lined masonry chimney. Most United States jurisdictions require a minimum 28-gauge galvanized single wall vent connector. Most Canadian jurisdictions require the vent connector to have corrosion resistance equivalent to 24-gauge galvanized sheet metal.

Observe the rules concerning clearance to combustibles.

The vent connector must be readily accessible for inspection, cleaning or replacement.

Keep the vent connector as short as possible by locating the furnace as close as practical to the vent or chimney. Avoid unnecessary turns or bends that create resistance to the flow of the vent gases. Fittings such as elbows add resistance to the vent connector.

Use Type B vent connectors in attics, crawl spaces, or other cold areas. Install thimbles that meet clearance to combustibles requirements and local code requirements if the vent connector must pass through a wall or partition constructed of combustible material. The preferred method to join vent connectors to a vent or chimney is by individual connections. If two vent connectors must be joined before the vent or chimney, use a correctly sized wye or tee-wye fitting as close to the vent or chimney as practical.

All furnace collars are 4 inch. When the United States ANSI Z223.1 / NFPA 54 or Canadian B149 venting tables specify the use of 3 inch venting, use a 4 to 3 reducer at the furnace collar. When the venting tables specify the use of 5inch venting, use a 5 to 4 reducer at the furnace collar.

Secure all single wall vent connector segments together with a minimum of three sheet metal screws per joint. Secure the vent connector to the furnace collar with a minimum of three sheet metal screws. Type B vent connectors do not require sheet metal screws since they have their own locking system.

FIGURE 5B: RIGHT INDUCER POSITION (35-2, 50-3)

C2

C3

TABLE 4: PRESSURE SWITCH TUBING LENGTH FOR RIGHT INDUCER POSITION (IN INCHES)

35-2

50-3

70-3

70-4

85-3

85-4

12 1/2”

12 1/2”

13 1/2”

13 1/2”

13 1/2”

13 1/2”

100-3

100-4

100-5

115-5

135-5

 

13 1/2”

13 1/2”

13 1/2”

13 1/2”

13 1/2”

 

 

 

 

 

 

 

10

Image 11
Contents Model F80A Introduction SafetySafety Rules Codes What to do if YOU Smell GASDo not Destroy this Manual Other Considerations Furnace SizingGeneral AIR Conditioning Installation PositionsInspection / Access Panel Clearances to Combustibles ClearancesDuctwork Steps DuctworkGuide Case Furnace Located in a Confined Space Determing Combustion AIRCase Furnace Located in AN Unconfined Space Design Considerations Furnace VentingDefinitions Vent Sizing Vent InstallationInducer Blower Installation Left Inducer Position 35-2 Vent ConnectorDedicated Venting Vent TerminationGAS Piping Existing Vent ConsiderationsGAS Supply Conversions Airflow Specifications High Altitude Specifications USAHigh Altitude Specifications Canada Outlet Regulator Pressure Vent Boss Electrical SpecificationsThermostat LOW Voltage WiringFurnace Connection Important USE Copper Conductors onlySequence of Operation Start UP ProceduresTo Start the Furnace To Shut Down the FurnaceChecking Furnace Input Temperature Rise CheckAirflow Annual Inspection / Service MaintenanceCirculating FAN Electronic AIR CleanerHUMIDIFIER/ Electronic AIR Cleaners Induced BlowerTroubleshooting 50V51-250 General Troubleshooting WHITE-RODGERS Integrated FAN Control Factory Setting User’s Information Manual Regulator Vent General Safety RulesFurnace Components Furnace Operation Information Air Filter Variations Sequence of Operation

F80A specifications

The Fedders F80A is a notable air conditioning unit that has gained recognition for its efficiency, performance, and convenience. Designed to cater to both residential and light commercial spaces, it combines robust features with advanced technologies to provide optimal cooling solutions.

One of the standout characteristics of the Fedders F80A is its impressive cooling capacity. With a BTU rating that makes it suitable for medium-sized rooms, this unit efficiently maintains comfortable indoor temperatures even during the hottest summer months. Users can benefit from its powerful performance without worrying about energy wastage.

Energy efficiency is a critical aspect of the Fedders F80A. It features an Energy Efficiency Ratio (EER) that meets current regulatory standards, which translates to lower energy bills and a reduced environmental footprint. The inclusion of eco-friendly refrigerants further enhances its appeal, making it a responsible choice for environmentally-conscious consumers.

The Fedders F80A is also equipped with user-friendly controls. An intuitive remote control allows for easy operation from anywhere in the room. Additionally, the unit comes with programmable settings that let users schedule their cooling preferences, ensuring comfort at all times without unnecessary energy expenditure.

Another key feature of this model is its multi-speed fan. The fan operates on various speeds, providing users with flexibility in airflow and noise levels. Whether a quiet night is desired or a powerful cooling burst is needed, the Fedders F80A caters to individual preferences effectively.

Installation and maintenance are also areas where the Fedders F80A shines. Its relatively straightforward installation process allows for quick setup, and its design makes routine maintenance a hassle-free task. Periodic cleaning of the filters ensures continued efficient operation, contributing to the unit's durability and longevity.

Overall, the Fedders F80A combines powerful cooling capabilities with energy efficiency and user-centric features. Its blend of technology and user-friendly design makes it a suitable choice for anyone looking to invest in reliable air conditioning. With its reputation for performance and efficiency, the Fedders F80A stands as a commendable option in the competitive air conditioning market.