Lennox International Inc EL296UHE Gas Pressure Adjustment, GAS Meter Clocking Chart, Dial

Page 50

4 - Move gas valve switch to OFF.

5 - Replace the access panel.

Failure To Operate

If the unit fails to operate, check the following:

1 - Is the thermostat calling for heat?

2 - Are access panels securely in place?

3 - Is the main disconnect switch closed?

4 - Is there a blown fuse or tripped breaker?

5 - Is the filter dirty or plugged? Dirty or plugged filters will cause the limit control to shut the unit off.

6 - Is gas turned on at the meter?

7 - Is the manual main shut‐off valve open?

8 - Is the internal manual shut‐off valve open?

9 - Is the unit ignition system in lockout? If the unit locks out again, inspect the unit for blockages.

Heating Sequence Of Operation

1 - When thermostat calls for heat, combustion air inducer starts.

2 - Combustion air pressure switch proves blower opera­ tion. Switch is factory set and requires no adjustment.

3 - After a 15-second prepurge, the hot surface ignitor en­ ergizes.

4 - After a 20-second ignitor warm-up period, the gas valve solenoid opens. A 4-second trial for ignition peri­ od begins.”

5 - Gas is ignited, flame sensor proves the flame, and the combustion process continues.

6 - If flame is not detected after first ignition trial, the igni­ tion control will repeat steps 3 and 4 four more times before locking out the gas valve (“WATCHGUARD” flame failure mode). The ignition control will then auto­ matically repeat steps 1 through 6 after 60 minutes.

To interrupt the 60-minute “WATCHGUARD” period, move thermostat from “Heat” to “OFF” then back to “Heat”. Heating sequence then restarts at step 1.

Gas Pressure Adjustment

Gas Flow (Approximate)

TABLE 15

GAS METER CLOCKING CHART

 

 

Seconds for One Revolution

 

 

 

 

 

 

 

 

EL296

 

Natural

 

LP

 

Unit

 

1 cu ft

2 cu ft

 

1 cu ft

 

2 cu ft

 

 

Dial

Dial

 

Dial

 

DIAL

 

 

 

 

 

 

 

 

-045

 

80

160

 

200

 

400

 

 

 

 

 

 

 

 

-070

 

55

110

 

136

 

272

 

 

 

 

 

 

 

 

-090

 

41

82

 

102

 

204

 

 

 

 

 

 

 

 

-110

 

33

66

 

82

 

164

 

 

 

 

 

 

 

 

-135

 

27

54

 

68

 

136

 

 

 

 

 

 

 

 

 

Natural-1000 btu/cu ft

LP-2500 btu/cu ft

 

Furnace should operate at least 5 minutes before check­ ing gas flow. Determine time in seconds for two revolu­ tions of gas through the meter. (Two revolutions assures a more accurate time.) Divide by two and compare to time in table 15. If manifold pressure matches table 17 and rate is incorrect, check gas orifices for proper size and re­ striction. Remove temporary gas meter if installed.

NOTE - To obtain accurate reading, shut off all other gas appliances connected to meter.

Supply Pressure Measurement

An inlet post located on the gas valve provides access to the supply pressure. See figure 66. Back out the 3/32 hex screw one turn, connect a piece of 5/16 tubing and connect to a manometer to measure supply pressure. See table 17 for supply line pressure.

On multiple unit installations, each unit should be checked separately, with and without units operating. Supply pres­ sure must fall within range listed in table 17.

Manifold Pressure Measurement

NOTE - Pressure test adapter kit (10L34) is available from Lennox to facilitate manifold pressure measurement.

A manifold pressure post located on the gas valve provides access to the manifold pressure. See figure 66. Back out the 3/32 hex screw one turn, connect a piece of 5/16 tubing and connect to a manometer to measure manifold pres­ sure.

To correctly measure manifold pressure, the differential pressure between the positive gas manifold and the nega­ tive burner box must be considered.

1 - Connect the test gauge positive side “+“ to manifold pressure tap on gas valve as noted above.

2 - Tee into the gas valve regulator vent hose and connect to test gauge negative “-”.

3 - Ignite unit on low fire and let run for 5 minutes to allow for steady state conditions.

4 - After allowing unit to stabilize for 5 minutes, record manifold pressure and compare to value given in table 17.

5 - If necessary, make adjustments. Figure 66 shows location of high fire and low fire adjustment screws.

6 - Repeat steps 3, 4 and 5 on high fire. See values in table 17.

NOTE - Shut unit off and remove manometer as soon as an accurate reading has been obtained. Re-start unit and check gas valve for gas leaks.

Page 50

Image 50
Contents Installation Instructions EL296UHE Table of ContentsEL296UHE Unit Dimensions inches mm TOP ViewShipping and Packing List Safety InformationEL296UHE Gas Furnace Package 1 of 1 containsUse of Furnace as Construction Heater Installation LocationsInstalled in Combination with a Cooling Coil General Combustion, Dilution & Ventilation AirUnconfined Space Confined SpaceAir from Inside Equipment in Confined Space ALL AIR from InsideEquipment in Confined Space Air from OutsideEquipment in Confined Space ALL AIR from Outside Moved before the furnace is placed into operation. Af­ Installation Setting EquipmentShipping Bolt Removal EL296 Furnaces with 1/2 HP Blower MotorSide View Setting EquipmentFront View END ViewReturn Air Guidelines Side Return Air With transition and filterFrontBack Optional Return Air Base Upflow Applications OnlyRemoving the Bottom Panel Platform Installation of Horizontal Unit Horizontal Application Installation ClearancesSuspended Installation of Horizontal Unit Horizontal Suspension KITDuct System Pipe & Fittings SpecificationsFilters Specification Joint Cementing ProcedurePiping and Fittings Specifications Primer & Solvent CementWall Thickness Guidelines Venting PracticesPiping Suspension Guidelines Removal of the Furnace from Common VentExhaust Piping Figures 22, 24 Horizontal Installation Offset RequirementsVent Piping Guidelines Minimum Vent Pipe LengthsPiping Size Process Outdoor Termination Usage Standard ConcentricStandard Termination Elevation 4500 10,000 ft 135Concentric Termination Elevation 4501 10,000 ft Maximum Allowable Intake or Exhaust Vent Length in FeetConcentric Termination at Elevation 0 4500 ft Standard Termination Elevation 4500 10,000 ft Applications Right Hand Discharge Shown Intake Piping General Guidelines for Vent Terminations 32 to 20 to US Installations1 Canadian Installations2 Inside Corner DetailNo minimum to outside corner EL296UHE Exiting Exhaust and Intake Vent Different pressure zonesDirect Vent Roof Termination KIT Alternate Terminations Tee & Forty-Five Degree Elbows Only 51MM 76MM51MM 7MM Vent Pipe SupportTop View Side ViewFront View Exhaust EL296UHE Direct Vent Application Using Existing Chimney NON-DIRECT Vent Roof Termination KITEL296UHE NON-DIRECT Vent Application Using Existing Chimney Condensate PipingCondensate Trap With Optional Overflow Switch Condensate Trap LocationsEL296UHE with Evaporator Coil Using a Common Drain Unit shown in horizontal left-hand discharge positionTrap / Drain Assembly Using 1/2 PVC or 3/4 PVC 178Plugged TAP Gas PipingLeak Check Horizontal Applications Possible Gas Piping Configurations Left Side Piping Standard Right Side Piping AlternateElectrical Precautions and ProceduresInterior MAKE-UP BOX Installation GAS Pipe Capacity FT3/HR kL/HROn-Board Links and Diagnostic Push Button Figure Typical EL296UHE Wiring Diagram Integrated Control LEDIntegrated Control DIP Switch Settings EL296 Field Wiring Applications With Conventional Thermostat Humidity control OFFWith tstat with Heat / 1 CoolComfortSense Single StageHeat Pump 7000 L7724UOFF For Your Safety Read Before Operating Unit Start-UpDial Gas Pressure AdjustmentGAS Meter Clocking Chart Proper Combustion High Altitude Information Carbon Monoxide Poisoning Hazard Other Unit Adjustments Heating Sequence of OperationControl Panel Parts Repair Parts ListCabinet Parts Blower PartsBlower ServiceCleaning The Burner Assembly FiltersStart-Up & Performance Check List TypicalCondensate Line Thermostat Temperature RiseTotal External Static Drain Line Vent PipeRequirements for Commonwealth of Massachusetts Approved Carbon Monoxide Detectors

EL296UHE, Elite Series Gas Furnace specifications

Lennox International Inc. has long been a trusted name in the heating, ventilation, and air conditioning (HVAC) industry, and their Elite Series Gas Furnace, the EL296UHE, stands out as a remarkable choice for homeowners seeking efficiency and reliability. This gas furnace is designed to deliver exceptional performance while ensuring the comfort of your living space.

One of the most significant features of the EL296UHE is its impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 96%. This means that a substantial portion of the energy consumed is converted into heat, translating to lower energy bills and a reduced environmental footprint. By minimizing energy waste, homeowners can enjoy both cost savings and greater environmental responsibility.

The EL296UHE is equipped with a two-stage heating process that allows it to operate at different speeds. This dual-stage functionality offers a more consistent temperature throughout the home, minimizing cold spots and enhancing overall comfort. Additionally, this furnace features a variable-speed blower motor, which not only improves the distribution of heated air but also quietly adjusts the airflow to match the heating requirements of your space.

In terms of technology, the EL296UHE incorporates advanced design elements such as a patented ZenBalanceā„¢ technology. This innovation further increases efficiency by adjusting the heating output based on real-time demands, ensuring optimal comfort without excessive energy consumption.

Durability is another hallmark of the EL296UHE. Constructed with high-quality materials, this furnace is built to withstand the rigors of daily use. Its stainless-steel heat exchanger is particularly noteworthy, as it enhances the furnace's ability to operate efficiently while maximizing longevity.

Homeowners are also reassured by the EL296UHE's quiet operation. The design minimizes operational noise, making it an ideal choice for those who prefer a peaceful home environment. Furthermore, the furnace is equipped with an ENERGY STARĀ® certification, a testament to its energy-efficient performance.

Lastly, Lennox offers comprehensive warranties for the EL296UHE, ensuring peace of mind for consumers. The combination of high efficiency, advanced technology, and durability makes the Lennox Elite Series Gas Furnace, EL296UHE, an excellent investment for homeowners looking to enhance their heating systems for optimal comfort and efficiency.