Lennox International Inc EL296UHE NON-DIRECT Vent Application Using Existing Chimney

Page 34

EL296UHE NON-DIRECT VENT APPLICATION

USING EXISTING CHIMNEY

 

SIZE TERMINATION

 

 

 

STRAIGHT-CUT OR

 

PIPE PER TABLE 8.

 

 

ANGLE-CUT IN DIRECTION

 

 

 

 

OF ROOF SLOPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXHAUST VENT

 

 

 

 

 

 

 

 

 

 

 

1/2” (13MM)

 

 

Minimum 12” (305MM)

 

 

WEATHERPROOF

 

 

 

 

INSULATION

 

 

above chimney top

 

 

 

 

 

 

 

 

 

 

plate or average snow

 

 

 

 

 

 

SHOULDER OF FITTINGS

 

 

accumulation

 

 

 

PROVIDE SUPPORT

 

 

 

 

 

 

 

 

 

OF PIPE ON TOP PLATE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHEET

 

 

 

 

 

 

 

 

 

 

METAL TOP

 

 

 

 

 

 

 

 

 

 

PLATE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSULATE

 

 

 

 

 

 

 

 

 

 

 

TO FORM

 

 

 

 

 

 

EXTERIOR

 

 

 

SEAL

 

 

 

 

 

 

PORTION OF

 

 

 

 

 

 

 

 

 

 

 

CHIMNEY

 

NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If ver­ tical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illus­ trated. In any exterior portion of chimney, the exhaust vent must be insulated.

FIGURE 50

Condensate Piping

This unit is designed for either right‐ or left‐side exit of con­ densate piping in upflow applications. In horizontal applica­ tions, the condensate trap must extend below the unit. An 8” service clearance is required for the condensate trap. Refer to figures 51 and 53 for condensate trap locations. Figure 59 shows trap assembly using 1/2” PVC or 3/4” PVC.

NOTE - If necessary the condensate trap may be installed up to 5’ away from the furnace. Use PVC pipe to connect trap to furnace condensate outlet. Piping from furnace must slope down a minimum of 1/4” per ft. toward trap.

1 - Determine which side condensate piping will exit the unit, location of trap, field-provided fittings and length of PVC pipe required to reach available drain.

2 - Use a large flat head screw driver or a 1/2” drive socket extension and remove plug (figure 51) from the cold end header box at the appropriate location on the side of the unit. Install provided 3/4 NPT street elbow fitting into cold end header box. Use Teflon tape or appropri­ ate pipe dope.

3 - Install the cap over the clean out opening at the base of the trap. Secure with clamp. See figure 59.

4 - Install drain trap using appropriate PVC fittings, glue all joints. Glue the provided drain trap as shown in fig­ ure 59. Route the condensate line to an open drain. Condensate line must maintain a 1/4” downward slope from the furnace to the drain.

CONDENSATE TRAP AND PLUG LOCATIONS

(Unit shown in upflow position)

Trap

(same on right side)

1-1/2 in.

Plug (same on left side)

NOTE - In upflow applications where side return air filter is installed on same side as the conden­ sate trap, filter rack must be installed beyond condensate trap or trap must be re-located to avoid interference.

FIGURE 51

5 - Figures 54 and 56 show the furnace and evaporator coil using a separate drain. If necessary the conden­ sate line from the furnace and evaporator coil can drain together. See figures 55, 57 and 58.

Upflow furnace (figure 57) - In upflow furnace applica­ tions the field provided vent must be a minimum 1” to a maximum 2” length above the condensate drain outlet connection. Any length above 2” may result in a flooded heat exchanger if the combined primary drain line were to become restricted.

Horizontal furnace (figure 58) - In horizontal furnace applications the field provided vent must be a mini­ mum 4” to a maximum 5” length above the condensate drain outlet connection. Any length above 5” may re­ sult in a flooded heat exchanger if the combined pri­ mary drain line were to become restricted.

NOTE - In horizontal applications it is recommended to install a secondary drain pan underneath the unit and trap assembly.

NOTE - Appropriately sized tubing and barbed fitting may be used for condensate drain. Attach to the drain on the trap using a hose clamp. See figure 52.

Page 34

Image 34
Contents Installation Instructions EL296UHE Table of ContentsEL296UHE Unit Dimensions inches mm TOP ViewShipping and Packing List Safety InformationEL296UHE Gas Furnace Package 1 of 1 containsInstalled in Combination with a Cooling Coil Installation LocationsUse of Furnace as Construction Heater General Combustion, Dilution & Ventilation AirUnconfined Space Confined SpaceAir from Inside Equipment in Confined Space ALL AIR from InsideEquipment in Confined Space ALL AIR from Outside Air from OutsideEquipment in Confined Space Moved before the furnace is placed into operation. Af­ Installation Setting EquipmentShipping Bolt Removal EL296 Furnaces with 1/2 HP Blower MotorSide View Setting EquipmentFront View END ViewReturn Air Guidelines Side Return Air With transition and filterRemoving the Bottom Panel Optional Return Air Base Upflow Applications OnlyFrontBack Platform Installation of Horizontal Unit Horizontal Application Installation ClearancesSuspended Installation of Horizontal Unit Horizontal Suspension KITFilters Pipe & Fittings SpecificationsDuct System Specification Joint Cementing ProcedurePiping and Fittings Specifications Primer & Solvent CementWall Thickness Guidelines Venting PracticesPiping Suspension Guidelines Removal of the Furnace from Common VentExhaust Piping Figures 22, 24 Horizontal Installation Offset RequirementsVent Piping Guidelines Minimum Vent Pipe LengthsPiping Size Process Outdoor Termination Usage Standard ConcentricStandard Termination Elevation 4500 10,000 ft 135Concentric Termination at Elevation 0 4500 ft Maximum Allowable Intake or Exhaust Vent Length in FeetConcentric Termination Elevation 4501 10,000 ft Standard Termination Elevation 4500 10,000 ft Applications Right Hand Discharge Shown Intake Piping General Guidelines for Vent Terminations 32 to 20 to US Installations1 Canadian Installations2 Inside Corner DetailNo minimum to outside corner Direct Vent Roof Termination KIT Exiting Exhaust and Intake Vent Different pressure zonesEL296UHE Alternate Terminations Tee & Forty-Five Degree Elbows Only 51MM 76MM51MM 7MM Vent Pipe SupportFront View Side ViewTop View Exhaust EL296UHE Direct Vent Application Using Existing Chimney NON-DIRECT Vent Roof Termination KITEL296UHE NON-DIRECT Vent Application Using Existing Chimney Condensate PipingCondensate Trap With Optional Overflow Switch Condensate Trap LocationsEL296UHE with Evaporator Coil Using a Common Drain Unit shown in horizontal left-hand discharge positionTrap / Drain Assembly Using 1/2 PVC or 3/4 PVC 178Leak Check Gas PipingPlugged TAP Horizontal Applications Possible Gas Piping Configurations Left Side Piping Standard Right Side Piping AlternateElectrical Precautions and ProceduresInterior MAKE-UP BOX Installation GAS Pipe Capacity FT3/HR kL/HROn-Board Links and Diagnostic Push Button Figure Typical EL296UHE Wiring Diagram Integrated Control LEDIntegrated Control DIP Switch Settings EL296 Field Wiring Applications With Conventional Thermostat Humidity control OFFWith tstat with Heat / 1 CoolComfortSense Single StageHeat Pump 7000 L7724UOFF For Your Safety Read Before Operating Unit Start-UpGAS Meter Clocking Chart Gas Pressure AdjustmentDial Proper Combustion High Altitude Information Carbon Monoxide Poisoning Hazard Other Unit Adjustments Heating Sequence of OperationControl Panel Parts Repair Parts ListCabinet Parts Blower PartsBlower ServiceCleaning The Burner Assembly FiltersStart-Up & Performance Check List TypicalCondensate Line Thermostat Temperature RiseTotal External Static Drain Line Vent PipeRequirements for Commonwealth of Massachusetts Approved Carbon Monoxide Detectors

EL296UHE, Elite Series Gas Furnace specifications

Lennox International Inc. has long been a trusted name in the heating, ventilation, and air conditioning (HVAC) industry, and their Elite Series Gas Furnace, the EL296UHE, stands out as a remarkable choice for homeowners seeking efficiency and reliability. This gas furnace is designed to deliver exceptional performance while ensuring the comfort of your living space.

One of the most significant features of the EL296UHE is its impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 96%. This means that a substantial portion of the energy consumed is converted into heat, translating to lower energy bills and a reduced environmental footprint. By minimizing energy waste, homeowners can enjoy both cost savings and greater environmental responsibility.

The EL296UHE is equipped with a two-stage heating process that allows it to operate at different speeds. This dual-stage functionality offers a more consistent temperature throughout the home, minimizing cold spots and enhancing overall comfort. Additionally, this furnace features a variable-speed blower motor, which not only improves the distribution of heated air but also quietly adjusts the airflow to match the heating requirements of your space.

In terms of technology, the EL296UHE incorporates advanced design elements such as a patented ZenBalanceā„¢ technology. This innovation further increases efficiency by adjusting the heating output based on real-time demands, ensuring optimal comfort without excessive energy consumption.

Durability is another hallmark of the EL296UHE. Constructed with high-quality materials, this furnace is built to withstand the rigors of daily use. Its stainless-steel heat exchanger is particularly noteworthy, as it enhances the furnace's ability to operate efficiently while maximizing longevity.

Homeowners are also reassured by the EL296UHE's quiet operation. The design minimizes operational noise, making it an ideal choice for those who prefer a peaceful home environment. Furthermore, the furnace is equipped with an ENERGY STARĀ® certification, a testament to its energy-efficient performance.

Lastly, Lennox offers comprehensive warranties for the EL296UHE, ensuring peace of mind for consumers. The combination of high efficiency, advanced technology, and durability makes the Lennox Elite Series Gas Furnace, EL296UHE, an excellent investment for homeowners looking to enhance their heating systems for optimal comfort and efficiency.