EL296UHE DIRECT VENT APPLICATION

USING EXISTING CHIMNEY

 

 

 

 

 

 

 

 

 

 

 

STRAIGHT-CUT OR

 

 

 

 

 

 

 

3”-8”

ANGLE-CUT IN DIRECTION

 

 

 

 

 

 

 

 

OF ROOF SLOPE *

 

 

 

 

 

 

(76MM-203MM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8” - 12”

 

 

 

 

 

 

EXHAUST VENT

 

 

(203MM - 305MM)

 

1/2” (13MM)

 

 

 

WEATHERPROOF

 

 

 

 

 

 

 

 

 

 

 

 

 

INSULATION

 

 

Minimum 12” (305MM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHOULDER OF FITTINGS

 

 

 

 

INTAKE PIPE

 

 

 

 

above chimney top

 

INSULATION (optional)

 

 

 

PROVIDE SUPPORT

 

 

 

 

 

 

 

 

 

 

OF PIPE ON TOP PLATE

 

 

 

 

 

 

 

 

 

 

 

 

plate or average snow

 

 

SHEET

 

 

 

 

 

 

 

 

 

 

 

ALTERNATE

 

 

 

 

 

 

 

 

 

METAL TOP

 

 

 

 

 

 

accumulation

 

 

 

 

 

INTAKE PIPE

 

 

 

PLATE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3” - 8”

 

(76MM-

INSULATE

203MM)

 

EXTERIOR

 

TO FORM

 

 

PORTION OF

SEAL

 

 

CHIMNEY

 

 

 

 

 

*SIZE TERMINATION PIPE PER TABLE 8.

NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If ver­ tical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illus­ trated. In any exterior portion of chimney, the exhaust vent must be insulated.

FIGURE 46

Details of Exhaust Piping Terminations for Non‐Direct Vent Applications

Exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is pre­ ferred. Figures 47 through 50 show typical terminations.

1 - Exhaust piping must terminate straight out or up as shown. The termination pipe must be sized as listed in table 8.The specified pipe size ensures proper veloc­ ity required to move the exhaust gases away from the building.

2 - On field supplied terminations for side wall exit, ex­ haust piping may extend a maximum of 12 inches (305MM) for 2” PVC and 20 inches (508MM) for 3” (76MM) PVC beyond the outside wall. See figure 48.

 

SIZE TERMINATION

12” (305MM)

PIPE PER TABLE 8.

 

ABOVE AVE.

 

SNOW

 

ACCUMULATION

1/2” (13MM) FOAM

 

INSULATION

3” (76MM) OR

UNCONDITIONED

2” (51MM) PVC

ATTIC SPACE

 

PROVIDE SUPPORT

 

FOR EXHAUST LINES

NON-DIRECT VENT ROOF TERMINATION KIT

(15F75 or 44J41)

FIGURE 47

 

12” (305MM) MAX. for 2” (51MM)

 

20” (508MM) MAX. for 3” (76MM)

1/2” (13MM) ARMAFLEX

 

INSULATION IN

 

UNCONDITIONED SPACE

1/2” (13MM)

 

ARMAFLEX

FIELD-PROVIDED

INSULATION

REDUCER MAY

 

BE REQUIRED TO

 

ADAPT LARGER

 

VENT PIPE SIZE

PVC REDUCER

TO TERMINATION

12” MIN.

SIZE TERMINATION

(305MM)

PIPE PER TABLE 8.

Above Grade or

 

average snow

 

accumulation

NON-DIRECT VENT FIELD SUPPLIED WALL TERMINATION OR

(15F74) WALL TERMINATION KIT

FIGURE 48

3 - If exhaust piping must be run up a side wall to position above snow accumulation or other obstructions, pip­ ing must be supported every 24 inches (610MM) as shown in figure 49. When exhaust piping must be run up an outside wall, any reduction in exhaust pipe size must be done after the final elbow.

 

12” (305MM) MAX. for 2” (51MM)

UNCONDITIONED

20” (508MM) MAX. for 3” (76MM)

 

SPACE

 

6” (152MM)

 

Max

SIZE TER­

 

MINATION

*WALL SUPPORT

PIPE PER

OUTSIDE WALL

TABLE 8.

 

FIELD-PROVIDED

12” (305MM)

REDUCER MAY BE

ABOVE GRADE OR

REQUIRED TO

AVERAGE SNOW

ADAPT LARGER

ACCUMULATION

VENT PIPE SIZE TO

 

TERMINATION

 

1/2” (13MM) FOAM

 

INSULATION IN

 

UNCONDITIONED

1/2” (13MM) FOAM

SPACE

INSULATION

 

NON-DIRECT VENT FIELD SUPPLIED WALL TERMINATION EXTENDED OR (15F74) WALL TERMINATION VENT PIPE EXTENDED

*Use wall support every 24” (610). Use two supports if extension is

greater than 24” but less than 48”.

FIGURE 49

Page 33

Image 33
Contents Table of Contents Installation Instructions EL296UHETOP View EL296UHE Unit Dimensions inches mmEL296UHE Gas Furnace Safety InformationShipping and Packing List Package 1 of 1 containsInstallation Locations Installed in Combination with a Cooling CoilUse of Furnace as Construction Heater Combustion, Dilution & Ventilation Air GeneralAir from Inside Confined SpaceUnconfined Space Equipment in Confined Space ALL AIR from InsideAir from Outside Equipment in Confined Space ALL AIR from OutsideEquipment in Confined Space Shipping Bolt Removal Installation Setting EquipmentMoved before the furnace is placed into operation. Af­ EL296 Furnaces with 1/2 HP Blower MotorFront View Setting EquipmentSide View END ViewSide Return Air With transition and filter Return Air GuidelinesOptional Return Air Base Upflow Applications Only Removing the Bottom PanelFrontBack Suspended Installation of Horizontal Unit Horizontal Application Installation ClearancesPlatform Installation of Horizontal Unit Horizontal Suspension KITPipe & Fittings Specifications FiltersDuct System Piping and Fittings Specifications Joint Cementing ProcedureSpecification Primer & Solvent CementPiping Suspension Guidelines Venting PracticesWall Thickness Guidelines Removal of the Furnace from Common VentVent Piping Guidelines Horizontal Installation Offset RequirementsExhaust Piping Figures 22, 24 Minimum Vent Pipe LengthsPiping Size Process Standard Concentric Outdoor Termination Usage135 Standard Termination Elevation 4500 10,000 ftMaximum Allowable Intake or Exhaust Vent Length in Feet Concentric Termination at Elevation 0 4500 ftConcentric Termination Elevation 4501 10,000 ft Standard Termination Elevation 4500 10,000 ft Applications Right Hand Discharge Shown Intake Piping General Guidelines for Vent Terminations 32 to 20 to Inside Corner Detail US Installations1 Canadian Installations2No minimum to outside corner Exiting Exhaust and Intake Vent Different pressure zones Direct Vent Roof Termination KITEL296UHE 51MM 76MM Alternate Terminations Tee & Forty-Five Degree Elbows OnlySupport 51MM 7MM Vent PipeSide View Front ViewTop View Exhaust NON-DIRECT Vent Roof Termination KIT EL296UHE Direct Vent Application Using Existing ChimneyCondensate Piping EL296UHE NON-DIRECT Vent Application Using Existing ChimneyCondensate Trap Locations Condensate Trap With Optional Overflow SwitchUnit shown in horizontal left-hand discharge position EL296UHE with Evaporator Coil Using a Common Drain178 Trap / Drain Assembly Using 1/2 PVC or 3/4 PVCGas Piping Leak CheckPlugged TAP Left Side Piping Standard Right Side Piping Alternate Horizontal Applications Possible Gas Piping ConfigurationsInterior MAKE-UP BOX Installation Precautions and ProceduresElectrical GAS Pipe Capacity FT3/HR kL/HROn-Board Links and Diagnostic Push Button Figure Typical EL296UHE Wiring Diagram LED Integrated ControlIntegrated Control DIP Switch Settings EL296 Field Wiring Applications With Conventional Thermostat With tstat with OFFHumidity control Heat / 1 CoolHeat Pump Single StageComfortSense 7000 L7724UOFF Unit Start-Up For Your Safety Read Before OperatingGas Pressure Adjustment GAS Meter Clocking ChartDial Proper Combustion High Altitude Information Carbon Monoxide Poisoning Hazard Heating Sequence of Operation Other Unit AdjustmentsCabinet Parts Repair Parts ListControl Panel Parts Blower PartsCleaning The Burner Assembly ServiceBlower FiltersTypical Start-Up & Performance Check ListTotal External Static Drain Line Temperature RiseCondensate Line Thermostat Vent PipeApproved Carbon Monoxide Detectors Requirements for Commonwealth of Massachusetts

EL296UHE, Elite Series Gas Furnace specifications

Lennox International Inc. has long been a trusted name in the heating, ventilation, and air conditioning (HVAC) industry, and their Elite Series Gas Furnace, the EL296UHE, stands out as a remarkable choice for homeowners seeking efficiency and reliability. This gas furnace is designed to deliver exceptional performance while ensuring the comfort of your living space.

One of the most significant features of the EL296UHE is its impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 96%. This means that a substantial portion of the energy consumed is converted into heat, translating to lower energy bills and a reduced environmental footprint. By minimizing energy waste, homeowners can enjoy both cost savings and greater environmental responsibility.

The EL296UHE is equipped with a two-stage heating process that allows it to operate at different speeds. This dual-stage functionality offers a more consistent temperature throughout the home, minimizing cold spots and enhancing overall comfort. Additionally, this furnace features a variable-speed blower motor, which not only improves the distribution of heated air but also quietly adjusts the airflow to match the heating requirements of your space.

In terms of technology, the EL296UHE incorporates advanced design elements such as a patented ZenBalanceā„¢ technology. This innovation further increases efficiency by adjusting the heating output based on real-time demands, ensuring optimal comfort without excessive energy consumption.

Durability is another hallmark of the EL296UHE. Constructed with high-quality materials, this furnace is built to withstand the rigors of daily use. Its stainless-steel heat exchanger is particularly noteworthy, as it enhances the furnace's ability to operate efficiently while maximizing longevity.

Homeowners are also reassured by the EL296UHE's quiet operation. The design minimizes operational noise, making it an ideal choice for those who prefer a peaceful home environment. Furthermore, the furnace is equipped with an ENERGY STARĀ® certification, a testament to its energy-efficient performance.

Lastly, Lennox offers comprehensive warranties for the EL296UHE, ensuring peace of mind for consumers. The combination of high efficiency, advanced technology, and durability makes the Lennox Elite Series Gas Furnace, EL296UHE, an excellent investment for homeowners looking to enhance their heating systems for optimal comfort and efficiency.