Johnson Controls TG8S*MP, TGLS*MP Section II Ductwork, Ductwork General Information, Duct Flanges

Page 5

356485-UIM-G-1211

SECTION II: DUCTWORK

DUCTWORK GENERAL INFORMATION

The duct system’s design and installation must:

1.Handle an air volume appropriate for the served space and within the operating parameters of the furnace specifications.

2.Be installed in accordance of National Fire Protection Association as outlined in NFPA standard 90B (latest editions) or applicable national, provincial, state, and local fire and safety codes.

3.Create a closed duct system. For residential and Non-HUD Modu- lar Home installations, when a furnace is installed so that the sup- ply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.

4.Complete a path for heated or cooled air to circulate through the air conditioning and heating equipment and to and from the condi- tioned space.

The cooling coil must be installed in the supply air duct, down- stream of the furnace. Cooled air may not be passed over the heat exchanger.

When the furnace is used with a cooling coil, the coil must be installed parallel with, or in the supply air side of the furnace to avoid condensa- tion in the primary heat exchanger. When a parallel flow arrangement is used, dampers or other means used to control airflow must be ade- quate to prevent chilled air from entering the furnace. If manually oper- ated, the damper must be equipped with means to prevent the furnace or the air conditioner from operating unless the damper is in full heat or cool position.

When replacing an existing furnace, if the existing plenum is not the same size as the new furnace then the existing plenum must be removed and a new plenum installed that is the proper size for the new furnace. If the plenum is shorter than 12” (30.5 cm) the turbulent air flow may cause the limit controls not to operate as designed, or the limit con- trols may not operate at all.

The duct system is a very important part of the installation. If the duct system is improperly sized the furnace will not operate properly.

The ducts attached to the furnace plenum, should be of sufficient size so that the furnace operates at the specified external static pressure and within the air temperature rise specified on the nameplate.

The minimum plenum height is 12” (30.5 cm). The furnace will not operate properly on a shorter plenum height. The minimum recom- mended rectangular duct height is 4 inches (10 cm) attached to the plenum.

The duct system must be properly sized to obtain the correct airflow for the furnace size that is being installed.

Refer to Table 6 or the furnace rating plate for the correct rise range and static pressures.

If the ducts are undersized, the result will be high duct static pres- sures and/or high temperature rises which can result in a heat exchanger OVERHEATING CONDITION. This condition can result in premature heat exchanger failure, which can result in personal injury, property damage, or death.

If a matching cooling coil is used, it may be placed directly on the fur- nace outlet and sealed to prevent leakage. If thermoplastic evaporator ‘A’ coil drain pans are to be installed in the upflow/horizontal configura- tion, then extra 2” minimum spacing may be needed to ensure against drain pan distortion.

On all installations without a coil, a removable access panel is recom- mended in the outlet duct such that smoke or reflected light would be observable inside the casing to indicate the presence of leaks in the heat exchanger. This access cover shall be attached in such a manner as to prevent leaks.

DUCT FLANGES

Four flanges are provided to attach ductwork to the furnace. These flanges are rotated down for shipment. In order to use the flanges, remove the screw holding an individual flange, rotate the flange so it is in the upward position and reinstall the screw then repeat this for all 4 flanges.

If the flanges are not used, they must remain in the rotated down posi- tion as shipped.

For duct attachment,

Factory

if needed.

installed

FIGURE 1: Duct Attachment

DUCTWORK INSTALLATION AND SUPPLY PLENUM CONNECTION - UPFLOW/HORIZONTAL

Attach the supply plenum to the furnace outlet. The use of an approved flexible duct connector is recommended on all installations. This connection should be sealed to prevent air leakage. The sheet metal should be crosshatched to eliminate any popping of the sheet metal when the indoor fan is energized.

FLOOR BASE AND DUCTWORK INSTALLATION - DOWNFLOW

Installations on combustible material or directly on any floors must use a combustible floor base shown in Figure 8. Follow the instructions supplied with the combustible floor base accessory. This combustible floor base can be replaced with a matching cooling coil, properly sealed to prevent leaks. Follow the instructions supplied with the cooling coil cabinet for installing the cabinet to the duct con- nector. Plug intake and vent pipe holes in bottom panel and move grommet to desired vent side exit.

Downflow Air Conditioning Coil Cabinet

The furnace should be installed with coil cabinet part number specifi- cally intended for downflow application. If a matching cooling coil is used, it may be placed directly on the furnace outlet and sealed to pre- vent leakage. For details of the coil cabinet dimensions and installation requirements, refer to the installation instructions supplied with the coil cabinet.

Attach the air conditioning coil cabinet to the duct connector, and then position the furnace on top of the coil cabinet. The connection to the fur- nace, air conditioning coil cabinet, duct connector, and supply air duct must be sealed to prevent air leakage.

COIL INSTALLATION

On all installations without a coil, a removable access panel is rec- ommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indicate the presence of leaks in the heat exchanger. This access cover shall be attached in such a manner as to prevent leaks.

Johnson Controls Unitary Products

5

Image 5
Contents List of Sections Section I SafetyList of Figures List of TablesAnce to a 50 HZ Power Supply or a Voltage Above 130 Volts Specific Safety Rules and PrecautionsSafety Requirements Codes and Standards Combustion AIR Quality List of ContaminantsDirectly BELOW. Keep Clear of ALL OBSTRUC- Tions InspectionFurnace Location and Clearances Coil Installation Floor Base and Ductwork Installation DownflowSection II Ductwork Ductwork General InformationFurnace Assembly MC & FC Series Coils COIL/FURNACE Assembly MC/FC/PC Series CoilsCoil Flange Installation Furnace Assembly PC Series CoilsDownflow Duct Connectors Coil / Furnace Assembly HC Series CoilsBottom Return and Attic Installations Attic InstallationTypical Suspended Furnace / Crawl Space Installation Suspended Furnace / Crawl Space InstallationAttempt to install filters inside the furnace Filter InstallationSection III Filters Btuh kWGAS Piping Installation GAS SafetySection IV GAS Piping Side ReturnGAS Orifice Conversion for Propane LP High Altitude Pressure Switch ConversionHigh Altitude GAS Orifice Conversion Manifold Pressures in wcElectrical Power Connections Section V Electrical PowerLOW Voltage Control Wiring Connections Supply Voltage ConnectionsSingle Stage PSC AIR Furnace Conditioner ID ModelsThermostat Single Stage Heat Pump Single Stage PSC FurnaceOD Models Section VI Twinning and Staging Vent Connections Section VII Vent SystemStaging Venting Category 1 450 F. MAX. Vent TempVenting Into AN Existing Chimney FAN-ASSISTED Combustion SystemAir Supply Openings and Ducts Vent and Supply Outside Air Safety Check ProcedureVentilated Combustion Air Free AreaNOx Screen Removal Lo-NOx Models Only Section Viii START-UP AdjustmentsCalculating the Furnace Input Natural GAS GAS Piping Leak CheckIgnition System Sequence Revolution Revolution Cu FtSeconds For Read the inlet gas pressure Adjustment of Manifold GAS Pressure & Input RateRead the manifold gas pressure Nominal Manifold PressureManifold Pressure U Tube Connection Adjustment of Temperature RiseAdjustment of FAN Control Settings Bottom Airflow Data Scfm 707 684 641 604 495 397 282 High 1371 1323 1251 757 733 694 659 575 444 3991086 971 843 521 060A10 Medium High 1249 1207 1098 1018 921 669 503Section IX Safety Controls Furnace Control Diagnostics Diagnostic Fault Code Storage and Retrieval Section X Replacement Parts ListWiring Diagram Section XI Wiring DiagramJohnson Controls Unitary Products York Drive Norman, OK

TG8S*MP, GG8S*MP, TGLS*MP, GGLS*MP specifications

Johnson Controls is a leader in the development of innovative building management solutions, and its product line encompassing the GGLS*MP, TGLS*MP, TG8S*MP, and GG8S*MP series exemplifies this commitment to excellence. These devices are designed to optimize energy efficiency, enhance occupant comfort, and ensure seamless integration into commercial building infrastructures.

The GGLS*MP series focuses on the integration of advanced sensors and controllers that facilitate effective lighting and HVAC management. With built-in capabilities for occupancy sensing and daylight harvesting, these devices can automatically adjust settings based on real-time conditions. Their energy-efficient operation not only contributes to lower utility costs but also supports sustainability goals, making them ideal for modern green buildings.

In contrast, the TGLS*MP series emphasizes the importance of temperature regulation and comfort in residential or smaller commercial settings. These controllers utilize advanced algorithms to maintain optimal indoor climates, adjusting heating and cooling outputs in response to ambient conditions. The intuitive user interface makes it easy for users to customize their settings, providing enhanced comfort without sacrificing energy efficiency.

The TG8S*MP series is particularly renowned for its robust communication features. These devices support multiple communication protocols, allowing them to integrate smoothly with existing building management systems. This versatility ensures that customers can leverage their current infrastructure while benefiting from new technology. Additionally, the TG8S*MP includes remote monitoring capabilities, enabling facility managers to track performance metrics and troubleshoot issues from anywhere.

Lastly, the GG8S*MP series brings together security and control features, ensuring that buildings are not only energy-efficient but also secure. With capabilities for access control and monitoring, these devices provide a comprehensive solution for managing facility safety. Their integration with lighting and HVAC systems further enhances overall efficiency, creating a comfortable and secure environment for all occupants.

In summary, Johnson Controls’ GGLS*MP, TGLS*MP, TG8S*MP, and GG8S*MP series presents cutting-edge technologies designed for energy efficiency, ease of use, and versatility. By focusing on comprehensive building management, these products provide optimal performance that aligns with sustainability objectives while enhancing comfort and security. Whether in commercial or residential settings, Johnson Controls continues to lead the way in the intelligent building sector.