Amana VR8205 Termination 10 Feet Or Less From Ridge Wall or Parapet, Checklist Summary

Page 9

CHECKLIST SUMMARY

This checklist serves as a summary of the items to be checked before venting an Air Command 80 furnace into a masonry chimney. In addition, we recommend that a quali- fied serviceman use this checklist to perform a yearly inspection of the furnace venting system.

This checklist is only a summary. For detailed information on each of the procedures mentioned, see the paragraph referenced with each item.

This inspection is based upon a draft topical report, “Ma- sonry Chimney Inspection and Relining”, issued by the Gas Research Institute. While not yet finalized, we believe this report represents the best information on this subject which is currently available.

CHECK 1 - PROPER CHIMNEY TERMINATION.

A masonry chimney used as a vent for gas fired equipment must extend at least three feet above the highest point where it passes through the roof. It must extend at least two feet higher than any portion of a building within a horizontal distance of 10 feet. In addition, the chimney must terminate at least 3 feet above any forced air inlet located within 10 feet. The chimney must extend at least five feet above the highest connected equipment draft hood outlet or flue collar.

If the chimney does not meet these termination require- ments, but all other requirements in the checklist can be met, it may be possible for a mason to extend the chimney. If this will not be practical, see Fix 1, page 12.

Proper Chimney

Termination?

(Check 1)

Yes

Chimney channel free of solid and liquid fuel appliances? (Check 2)

Yes

No

No

Line, terminate with

listed vent cap

(Fix 1)

Change venting arrangements (Fix 2)

10' or Less

2' Min. 2' Min.

3' Min.

Wall or

Parapet

Chimney

Crown in good

condition? (Check 3)

Yes

Cleanout free of debris?

(Check 4)

Yes

Liner in good condition? (Check 5)

Yes

Dilution air available? (Check 6)

Yes

Complete the installation. (Check 7)

No

No

No

No

Rebuild crown (Fix 3)

and /or Reline (Fix 4)

Reline (Fix 4)

Reline (Fix 4)

Reline (Fix 4)

 

 

10' or Less

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2' Min.

 

Ridge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3' Min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chimney

Figure 9

Termination 10 Feet Or Less From Ridge,

Wall or Parapet

9

Image 9
Contents Table of Contents Installation InstructionsTo The Owner To The InstallerAdditional Safety Considerations Safety and Unit LocationIII. Air Requirements II. General InformationPage Specially Engineered Installations IV. Category I Venting Vertical VentingLouvers and Grilles Counterflow Rotated Induced Draft Blower Upflow Rotated Induced Draft BlowerBlower Assembly Masonry ChimneysTypical Multiple Flue Clay Tile Chimney Checklist Summary Termination 10 Feet Or Less From Ridge Wall or ParapetCheck 1 Proper Chimney Termination Termination More Than 10 Feet From Ridge Wall or Parapet Check 4 Debris in CleanoutCheck 5 Liner Condition Check 3 Chimney Crown ConditionCheck 6 Dilution AIR Check 7 Complete the InstallationFIX 1 Liner Termination FIX 2 -CHANGE Venting ArrangementsGAS Piping VI. Gas PipingGeneral Furnace Layout Upflow InstallationsGas Inlet Through Furnace Right Side Gas Inlet Through Furnace Bottom Side UpflowGas Inlet Through Right Side Counterflow Counterflow InstallationsPropane GAS Piping Charts Propane Gas Installation TypChecking GAS Piping Tanks and Piping Propane GAS UnitsTypical Field Wiring VAC Control Circuit VIl. Electrical WiringJunction Box Left Side Junction BoxLow Voltage Heating Fan Off AdjustmentsTerminals AIR Circulation Blower FAN TimingHeat Anticipator Setting Line Voltage Connection for AccessoriesVIlI. Circulating Air and Filters Control ModuleUpflow/Horizontal Furnaces Return Air Plenum InstallationBottom Return Filter Sizes Furnace Mounted Filter RackTiming Chart for Normal Cooling Operation Integrated Ignition Control Diagnostic Signal ChartLight Signal Operation Number Refer to AbnormalStart-Up, Adjustments, and Checks IX. Sequence of Operation Integrated Ignition ControlCounterflow Furnaces Right To Left Installation Left To Right InstallationRollout Protection Device Burner BOX Auxiliary Limit ControlAuxiliary Limit Control Figure Abnormal Operation Integrated Ignition ControlHoneywell Model VR-8205 White Rodgers Model 36E36 Gas ValvesRobertshaw Model Operating InstructionsMeasuring Inlet Gas Pressure Alternate Method White Rodgers Model 36E22High Limit Control Filter Removal XI. MaintenanceAIR Filter AIR Filter Upflow FurnacesFurnace mounted Filter Rack Counterflow Burner Flame Cleaning of Burners Qualified Servicer onlyBurners General Information

VR8205 specifications

The Amana VR8205 is a robust and innovative gas valve designed for use in a variety of heating applications, particularly in residential and commercial HVAC systems. This versatile valve offers a combination of advanced technologies and user-friendly features, making it a popular choice among HVAC professionals and system installers alike.

One of the key features of the Amana VR8205 is its two-stage operation, allowing for precise control of gas flow. The dual-stage design enables the valve to modulate the gas supply based on the heating demand, which enhances system efficiency and promotes better temperature regulation. This feature not only contributes to energy savings but also helps maintain a comfortable indoor environment.

Additionally, the VR8205 is equipped with a strong, durable body construction that ensures reliability and longevity. Designed to withstand harsh operating conditions, the valveā€™s materials are resistant to corrosion and wear, making it suitable for various applications. The robust design of the Amana VR8205 minimizes the likelihood of leaks or failures, providing peace of mind to both installers and end-users.

The valve operates on low voltage, typically requiring 24 volts, which makes it energy-efficient and compatible with most modern thermostatic control systems. This low-voltage operation also simplifies installation, as it reduces the complexity and requirements for the electrical setup.

Another noteworthy characteristic of the Amana VR8205 is its integrated safety features. It includes a combination of automatic and manual shut-off mechanisms, providing an added layer of safety in case of malfunctions. This ensures that the gas supply can be quickly halted in emergency situations, protecting both people and property.

Moreover, the Amana VR8205 is designed for easy maintenance, featuring simple access points for servicing and troubleshooting. This ease of maintenance is crucial for HVAC professionals, as it allows for quick adjustments and repairs, ultimately reducing downtime.

Lastly, the Amana VR8205 has a reputation for adaptability, being compatible with various heating appliances, including furnaces, boilers, and water heaters. Its versatility makes it an excellent solution for a wide range of heating applications, ensuring optimal performance across different systems.

In summary, the Amana VR8205 gas valve is characterized by its two-stage operation, durable construction, low-voltage functionality, integrated safety mechanisms, and ease of maintenance. These features combine to offer a reliable, efficient, and flexible solution for modern heating needs.