Amana VR8205 Propane Gas Installation Typ, Checking GAS Piping, Propane GAS Piping Charts

Page 15

CHECKING GAS PIPING

CAUTION

To prevent personal injury or property damage due to fire, the following instructions must be performed regarding gas connections, pressure testing, location of shutoff valve and installation of gas piping.

Before placing in operation, leak test the unit and gas connections. To avoid the possibility of explosion or fire, never use a match or open flame to test for leaks. Never exceed specified pressures for testing. Higher pressure may damage the gas valve and cause overfiring, resulting in heat exchanger failure.

This unit and shutoff valve must be disconnected from the gas supply piping system before supply piping system pressure testing with test pressures in excess of 1/2 psig (3.48 kPa).

This unit must be isolated from the gas supply system by closing its manual shutoff valve before pressure testing of gas supply piping system with test pressures equal to or less than 1/2 psig (3.48 kPa).

For satisfactory operation, propane gas pressure must be 10 inch WC at the furnace manifold with all gas appliances in operation. Maintaining proper gas pressure depends on three main factors:

1.Vaporization rate, depending on temperature of the liquid, and “wetted surface” area of the container or containers.

2.Proper pressure regulation. (Two-stage regulation is recommended for both cost and efficiency).

3.Pressure drop in lines between regulators, and be- tween second stage regulator and the appliance. Pipe size will depend on length of pipe run and total load of all appliances.

Complete information regarding tank sizing for vaporiza- tion, recommended regulator settings, and pipe sizing is available from most regulator manufacturers and propane gas suppliers.

Since propane gas will quickly dissolve white lead or most standard commercial compounds, special pipe dope must be used. Shellac base compounds resistant to the actions of liquefied petroleum gases such as Gasolac, Stalactic, Clyde’s or John Crane are satisfactory.

Refer to Figure 19 for typical propane gas installations.

TANKS AND PIPING - PROPANE GAS UNITS

WARNING

To prevent death, personal injury or property damage due to fire or explosion caused by a propane gas leak, install a gas detecting warning device. Since rust can reduce the level of odorant in propane gas, a gas detecting warning device is the only reliable way to detect a propane gas leak. Contact a local propane gas supplier about installing a gas detecting warning device.

WARNING

All metal inserts, screens or turbulators must be removed from the heat exchanger tubes when using propane gas. Failure to comply could cause serious personal injury or death. Failure to comply with this requirement will also void warranty coverage.

All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriters (See NBFU Manual 58).

Figure 19

Propane Gas Installation (Typ.)

PROPANE GAS PIPING CHARTS

Sizing Between First and Second Stage Regulator

Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting. Capacities in 1,000 BTU/hour.

Pipe or

 

 

 

 

 

Nominal Pipe Size

Tubing

 

Tubing Size, O.D. Type L

 

Schedule 40

Length,

3/8"

1/2"

5/8"

3/4"

7/8"

1/2"

3/4"

Feet

 

 

 

 

 

 

 

10

730

1,700

3,200

5,300

8,300

3,200

7,500

20

500

1,100

2,200

3,700

5,800

2,200

4,200

30

400

920

2,000

2,900

4,700

1,800

4,000

40

370

850

1,700

2,700

4,100

1,600

3,700

50

330

770

1,500

2,400

3,700

1,500

3,400

60

300

700

1,300

2,200

3,300

1,300

3,100

80

260

610

1,200

1,900

2,900

1,200

2,600

100

220

540

1,000

1,700

2,600

1,000

2,300

125

200

490

900

1,400

2,300

900

2,100

150

190

430

830

1,300

2,100

830

1,900

175

170

400

780

1,200

1,900

770

1,700

200

160

380

730

1,100

1,800

720

1,500

To convert to capacities at 15 psig settings - multiply by 1.130

To convert to capacities at 5 psig settings - multiply by 0.879

15

Image 15
Contents Table of Contents Installation InstructionsTo The Owner To The InstallerAdditional Safety Considerations Safety and Unit LocationIII. Air Requirements II. General InformationPage Specially Engineered Installations IV. Category I Venting Vertical VentingLouvers and Grilles Counterflow Rotated Induced Draft Blower Upflow Rotated Induced Draft BlowerBlower Assembly Masonry ChimneysTypical Multiple Flue Clay Tile Chimney Checklist Summary Termination 10 Feet Or Less From Ridge Wall or ParapetCheck 1 Proper Chimney Termination Check 3 Chimney Crown Condition Check 4 Debris in CleanoutTermination More Than 10 Feet From Ridge Wall or Parapet Check 5 Liner ConditionFIX 2 -CHANGE Venting Arrangements Check 7 Complete the InstallationCheck 6 Dilution AIR FIX 1 Liner TerminationGAS Piping VI. Gas PipingGas Inlet Through Furnace Bottom Side Upflow Upflow InstallationsGeneral Furnace Layout Gas Inlet Through Furnace Right SideGas Inlet Through Right Side Counterflow Counterflow InstallationsTanks and Piping Propane GAS Units Propane Gas Installation TypPropane GAS Piping Charts Checking GAS PipingJunction Box VIl. Electrical WiringTypical Field Wiring VAC Control Circuit Junction Box Left SideAIR Circulation Blower FAN Timing Heating Fan Off AdjustmentsLow Voltage TerminalsControl Module Line Voltage Connection for AccessoriesHeat Anticipator Setting VIlI. Circulating Air and FiltersFurnace Mounted Filter Rack Return Air Plenum InstallationUpflow/Horizontal Furnaces Bottom Return Filter SizesRefer to Abnormal Integrated Ignition Control Diagnostic Signal ChartTiming Chart for Normal Cooling Operation Light Signal Operation NumberStart-Up, Adjustments, and Checks IX. Sequence of Operation Integrated Ignition ControlCounterflow Furnaces Right To Left Installation Left To Right InstallationRollout Protection Device Abnormal Operation Integrated Ignition Control Auxiliary Limit ControlBurner BOX Auxiliary Limit Control FigureOperating Instructions Gas ValvesHoneywell Model VR-8205 White Rodgers Model 36E36 Robertshaw ModelMeasuring Inlet Gas Pressure Alternate Method White Rodgers Model 36E22High Limit Control AIR Filter Upflow Furnaces XI. MaintenanceFilter Removal AIR FilterFurnace mounted Filter Rack Counterflow General Information Cleaning of Burners Qualified Servicer onlyBurner Flame Burners

VR8205 specifications

The Amana VR8205 is a robust and innovative gas valve designed for use in a variety of heating applications, particularly in residential and commercial HVAC systems. This versatile valve offers a combination of advanced technologies and user-friendly features, making it a popular choice among HVAC professionals and system installers alike.

One of the key features of the Amana VR8205 is its two-stage operation, allowing for precise control of gas flow. The dual-stage design enables the valve to modulate the gas supply based on the heating demand, which enhances system efficiency and promotes better temperature regulation. This feature not only contributes to energy savings but also helps maintain a comfortable indoor environment.

Additionally, the VR8205 is equipped with a strong, durable body construction that ensures reliability and longevity. Designed to withstand harsh operating conditions, the valveā€™s materials are resistant to corrosion and wear, making it suitable for various applications. The robust design of the Amana VR8205 minimizes the likelihood of leaks or failures, providing peace of mind to both installers and end-users.

The valve operates on low voltage, typically requiring 24 volts, which makes it energy-efficient and compatible with most modern thermostatic control systems. This low-voltage operation also simplifies installation, as it reduces the complexity and requirements for the electrical setup.

Another noteworthy characteristic of the Amana VR8205 is its integrated safety features. It includes a combination of automatic and manual shut-off mechanisms, providing an added layer of safety in case of malfunctions. This ensures that the gas supply can be quickly halted in emergency situations, protecting both people and property.

Moreover, the Amana VR8205 is designed for easy maintenance, featuring simple access points for servicing and troubleshooting. This ease of maintenance is crucial for HVAC professionals, as it allows for quick adjustments and repairs, ultimately reducing downtime.

Lastly, the Amana VR8205 has a reputation for adaptability, being compatible with various heating appliances, including furnaces, boilers, and water heaters. Its versatility makes it an excellent solution for a wide range of heating applications, ensuring optimal performance across different systems.

In summary, the Amana VR8205 gas valve is characterized by its two-stage operation, durable construction, low-voltage functionality, integrated safety mechanisms, and ease of maintenance. These features combine to offer a reliable, efficient, and flexible solution for modern heating needs.