Amana VR8205 installation instructions

Page 5

(c)In addition to air needed for combustion, process air shall be provided as required for: cooling of equipment or material, controlling dew point, heating, drying, oxidation or dilution, safety exhaust, odor control, and air for compres- sors.

(d)In addition to air needed for combustion, air shall be supplied for ventilation, including all air required for comfort and proper working conditions for personnel.

(e)While all forms of building construction cannot be covered in detail, air for combustion, ventilation and dilution of flue gases for gas utilization equipment vented by natural draft normally may be obtained by application of one of the methods covered in 5.3.3 and 5.3.4.

(f)Air requirements for the operation of exhaust fans, kitchen ventilation systems, clothes dryers, and fireplaces shall be considered in determining the adequacy of a space to provide combustion air requirements.

5.3.2Equipment Located in Unconfined Spaces: In unconfined spaces (see definition below) in buildings, infiltration may be adequate to provide air for combustion ventilation and dilution of flue gases. However, in buildings of tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), additional air may need to be provided using the methods described in 5.3.3- b or 5.3.4.

Space, Unconfined. For purposes of this Code, a space whose volume is not less than 50 cubic feet per 1,000 BTU per hour of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed through openings not furnished with doors, are considered a part of the unconfined space.

5.3.3Equipment Located in Confined Spaces: (a) All Air from Inside the Building: The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be consid- ered in making this determination. Each opening shall have a minimum free area of 1 square inch per 1,000 BTU per hour of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches. One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure. (Figure 1 )

Figure 1

Equipment Located in Confined Spaces; All

Air from Inside Building. See 5.3.3-a

.

(b)All Air from Outdoors: The confined space shall be provided with two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.

1.When directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure (Figure 2).

Figure 2

Equipment Located in Confined Spaces; All Air from Outdoors—Inlet Air from Ventilated Crawl Space and Outlet Air to Ventilated Attic. See 5.3.3-b

2.When communicating with the outdoors through verti- cal ducts, each opening shall have a minimum free area of 1 square inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure (See Figure 3).

5

Image 5
Contents Table of Contents Installation InstructionsTo The Owner To The InstallerAdditional Safety Considerations Safety and Unit LocationIII. Air Requirements II. General InformationPage Louvers and Grilles Specially Engineered InstallationsIV. Category I Venting Vertical Venting Counterflow Rotated Induced Draft Blower Upflow Rotated Induced Draft BlowerTypical Multiple Flue Clay Tile Chimney Blower AssemblyMasonry Chimneys Check 1 Proper Chimney Termination Checklist SummaryTermination 10 Feet Or Less From Ridge Wall or Parapet Termination More Than 10 Feet From Ridge Wall or Parapet Check 4 Debris in CleanoutCheck 5 Liner Condition Check 3 Chimney Crown ConditionCheck 6 Dilution AIR Check 7 Complete the InstallationFIX 1 Liner Termination FIX 2 -CHANGE Venting ArrangementsGAS Piping VI. Gas PipingGeneral Furnace Layout Upflow InstallationsGas Inlet Through Furnace Right Side Gas Inlet Through Furnace Bottom Side UpflowGas Inlet Through Right Side Counterflow Counterflow InstallationsPropane GAS Piping Charts Propane Gas Installation TypChecking GAS Piping Tanks and Piping Propane GAS UnitsTypical Field Wiring VAC Control Circuit VIl. Electrical WiringJunction Box Left Side Junction BoxLow Voltage Heating Fan Off AdjustmentsTerminals AIR Circulation Blower FAN TimingHeat Anticipator Setting Line Voltage Connection for AccessoriesVIlI. Circulating Air and Filters Control ModuleUpflow/Horizontal Furnaces Return Air Plenum InstallationBottom Return Filter Sizes Furnace Mounted Filter RackTiming Chart for Normal Cooling Operation Integrated Ignition Control Diagnostic Signal ChartLight Signal Operation Number Refer to AbnormalCounterflow Furnaces Start-Up, Adjustments, and ChecksIX. Sequence of Operation Integrated Ignition Control Rollout Protection Device Right To Left InstallationLeft To Right Installation Burner BOX Auxiliary Limit ControlAuxiliary Limit Control Figure Abnormal Operation Integrated Ignition ControlHoneywell Model VR-8205 White Rodgers Model 36E36 Gas ValvesRobertshaw Model Operating InstructionsMeasuring Inlet Gas Pressure Alternate Method White Rodgers Model 36E22High Limit Control Filter Removal XI. MaintenanceAIR Filter AIR Filter Upflow FurnacesFurnace mounted Filter Rack Counterflow Burner Flame Cleaning of Burners Qualified Servicer onlyBurners General Information

VR8205 specifications

The Amana VR8205 is a robust and innovative gas valve designed for use in a variety of heating applications, particularly in residential and commercial HVAC systems. This versatile valve offers a combination of advanced technologies and user-friendly features, making it a popular choice among HVAC professionals and system installers alike.

One of the key features of the Amana VR8205 is its two-stage operation, allowing for precise control of gas flow. The dual-stage design enables the valve to modulate the gas supply based on the heating demand, which enhances system efficiency and promotes better temperature regulation. This feature not only contributes to energy savings but also helps maintain a comfortable indoor environment.

Additionally, the VR8205 is equipped with a strong, durable body construction that ensures reliability and longevity. Designed to withstand harsh operating conditions, the valveā€™s materials are resistant to corrosion and wear, making it suitable for various applications. The robust design of the Amana VR8205 minimizes the likelihood of leaks or failures, providing peace of mind to both installers and end-users.

The valve operates on low voltage, typically requiring 24 volts, which makes it energy-efficient and compatible with most modern thermostatic control systems. This low-voltage operation also simplifies installation, as it reduces the complexity and requirements for the electrical setup.

Another noteworthy characteristic of the Amana VR8205 is its integrated safety features. It includes a combination of automatic and manual shut-off mechanisms, providing an added layer of safety in case of malfunctions. This ensures that the gas supply can be quickly halted in emergency situations, protecting both people and property.

Moreover, the Amana VR8205 is designed for easy maintenance, featuring simple access points for servicing and troubleshooting. This ease of maintenance is crucial for HVAC professionals, as it allows for quick adjustments and repairs, ultimately reducing downtime.

Lastly, the Amana VR8205 has a reputation for adaptability, being compatible with various heating appliances, including furnaces, boilers, and water heaters. Its versatility makes it an excellent solution for a wide range of heating applications, ensuring optimal performance across different systems.

In summary, the Amana VR8205 gas valve is characterized by its two-stage operation, durable construction, low-voltage functionality, integrated safety mechanisms, and ease of maintenance. These features combine to offer a reliable, efficient, and flexible solution for modern heating needs.