Amana VR8205 installation instructions Furnace mounted Filter Rack Counterflow

Page 28

The furnace-mounted filter rack includes a rack mounted on the top of the furnace. Two filters fit into the rack and rest against the sides of the return air plenum, forming a “V” above the furnace.

The filters should be inspected frequently and cleaned or replaced when necessary. In some installations, the filters can be inspected after disconnecting the electrical power and removing the optional access door in the return air plenum. If this access panel is not present, proceed as follows:

1.Disconnect the electrical power.

2.Remove the non-louvered door from the furnace.

3.Remove the left filter by reaching to the left side of the blower, pushing the filter up slightly to remove it from the filter rack, and pulling it down to the left of the blower and out the blower door. Repeat with the right filter.

4a. Dirty throwaway filters must be replaced with the same filter type and size.

4b. Dirty, permanent metal filters must be cleaned as follows:

Wash, rinse, and dry the permanent filters. Both sides should then be sprayed with a filter adhesive as is recommended on the adhesive container. Many hard- ware stores stock spray adhesives for use with perma- nent filters.

If badly torn or uncleanable, these filters must be replaced by equal size permanent, high velocity filters. Throwaway filters must not be used as replacement for permanent filters. Under normal use, permanent filters should last for several years.

5.To reinstall the filters, first MAKE CERTAIN THE AIRFLOW DIRECTION ARROW POINTS TOWARDS THE FURNACE. Then insert the filters from the left side of the blower. Starting with the right filter, push the filter into the plenum so that the bottom of the filter rests in the filter rack and the upper edge rests against the side of the plenum. Repeat with the left filter (Figure 44).

6.Replace the blower door, then reconnect the electrical power.

BLOWER MOTOR

The air circulating blower motor bearings are permanently lubricated. No further lubrication is required.

INDUCED DRAFT BLOWER MOTOR

The induced draft blower motor is permanently lubricated. No further lubrication is required.

FLAME SENSOR (INTEGRATED IGNITION CONTROL) (QUALIFIED SERVICER ONLY)

The fuel or combustion air supply can create a nearly invisible coating on the flame sensor. This coating acts as an insulator, causing a drop in the flame sensing signal. To remove this coating, a qualified servicer should carefully clean the flame sensor with emery cloth or steel wool. After cleaning, the microamp signal should be in the range listed in Specification Sheet.

IGNITOR (QUALIFIED SERVICER ONLY)

If the ignitor and the surrounding air are at about 70°F and the ignitor wires are not connected to any other electrical components, the resistance of the ignitor should not ex- ceed 200 ohms. If it does, the ignitor should be replaced.

FLUE PASSAGES (QUALIFIED SERVICER ONLY)

At the start of each heating season, inspect and if nec- essary, clean the furnace flue passages.

CLEANING FLUE PASSAGES (QUALIFIED SERVICER ONLY)

1.Shut off electric power and gas supply to the furnace.

2.Remove burner assembly by disconnecting the gas line and removing the manifold brackets from the partition panel.

3.Remove the flue from the induced draft blower and the collector box from the partition panel.

4.The primary heat exchanger tubes can be cleaned using a round wire brush attached to a length of high grade stainless steel cable, such as drain cleanout cable. Attach a variable speed reversible drill to the other end of the spring cable. Slowly rotate the cable with the drill and insert it into one of the primary heat exchanger tubes. While reversing the drill, work the cable in and out several times to obtain sufficient cleaning. Use a large cable for the large tube, and then repeat the operation with a small cable for the smaller tube. Repeat for each tube.

5.When all heat exchanger tubes have been cleaned, replace the parts in the reverse order in which they were removed.

6.To reduce the chances of repeated fouling of the heat exchanger, perform the steps listed in Section X, Start- up, Adjustments, and Checks.

Figure 44

Furnace mounted Filter Rack

(Counterflow)

28

Image 28
Contents Installation Instructions Table of ContentsTo The Installer To The OwnerSafety and Unit Location Additional Safety ConsiderationsII. General Information III. Air RequirementsPage IV. Category I Venting Vertical Venting Specially Engineered InstallationsLouvers and Grilles Upflow Rotated Induced Draft Blower Counterflow Rotated Induced Draft BlowerMasonry Chimneys Blower AssemblyTypical Multiple Flue Clay Tile Chimney Termination 10 Feet Or Less From Ridge Wall or Parapet Checklist SummaryCheck 1 Proper Chimney Termination Check 4 Debris in Cleanout Termination More Than 10 Feet From Ridge Wall or ParapetCheck 5 Liner Condition Check 3 Chimney Crown ConditionCheck 7 Complete the Installation Check 6 Dilution AIRFIX 1 Liner Termination FIX 2 -CHANGE Venting ArrangementsVI. Gas Piping GAS PipingUpflow Installations General Furnace LayoutGas Inlet Through Furnace Right Side Gas Inlet Through Furnace Bottom Side UpflowCounterflow Installations Gas Inlet Through Right Side CounterflowPropane Gas Installation Typ Propane GAS Piping ChartsChecking GAS Piping Tanks and Piping Propane GAS UnitsVIl. Electrical Wiring Typical Field Wiring VAC Control CircuitJunction Box Left Side Junction BoxHeating Fan Off Adjustments Low VoltageTerminals AIR Circulation Blower FAN TimingLine Voltage Connection for Accessories Heat Anticipator SettingVIlI. Circulating Air and Filters Control ModuleReturn Air Plenum Installation Upflow/Horizontal FurnacesBottom Return Filter Sizes Furnace Mounted Filter RackIntegrated Ignition Control Diagnostic Signal Chart Timing Chart for Normal Cooling OperationLight Signal Operation Number Refer to AbnormalIX. Sequence of Operation Integrated Ignition Control Start-Up, Adjustments, and ChecksCounterflow Furnaces Left To Right Installation Right To Left InstallationRollout Protection Device Auxiliary Limit Control Burner BOXAuxiliary Limit Control Figure Abnormal Operation Integrated Ignition ControlGas Valves Honeywell Model VR-8205 White Rodgers Model 36E36Robertshaw Model Operating InstructionsWhite Rodgers Model 36E22 Measuring Inlet Gas Pressure Alternate MethodHigh Limit Control XI. Maintenance Filter RemovalAIR Filter AIR Filter Upflow FurnacesFurnace mounted Filter Rack Counterflow Cleaning of Burners Qualified Servicer only Burner FlameBurners General Information

VR8205 specifications

The Amana VR8205 is a robust and innovative gas valve designed for use in a variety of heating applications, particularly in residential and commercial HVAC systems. This versatile valve offers a combination of advanced technologies and user-friendly features, making it a popular choice among HVAC professionals and system installers alike.

One of the key features of the Amana VR8205 is its two-stage operation, allowing for precise control of gas flow. The dual-stage design enables the valve to modulate the gas supply based on the heating demand, which enhances system efficiency and promotes better temperature regulation. This feature not only contributes to energy savings but also helps maintain a comfortable indoor environment.

Additionally, the VR8205 is equipped with a strong, durable body construction that ensures reliability and longevity. Designed to withstand harsh operating conditions, the valveā€™s materials are resistant to corrosion and wear, making it suitable for various applications. The robust design of the Amana VR8205 minimizes the likelihood of leaks or failures, providing peace of mind to both installers and end-users.

The valve operates on low voltage, typically requiring 24 volts, which makes it energy-efficient and compatible with most modern thermostatic control systems. This low-voltage operation also simplifies installation, as it reduces the complexity and requirements for the electrical setup.

Another noteworthy characteristic of the Amana VR8205 is its integrated safety features. It includes a combination of automatic and manual shut-off mechanisms, providing an added layer of safety in case of malfunctions. This ensures that the gas supply can be quickly halted in emergency situations, protecting both people and property.

Moreover, the Amana VR8205 is designed for easy maintenance, featuring simple access points for servicing and troubleshooting. This ease of maintenance is crucial for HVAC professionals, as it allows for quick adjustments and repairs, ultimately reducing downtime.

Lastly, the Amana VR8205 has a reputation for adaptability, being compatible with various heating appliances, including furnaces, boilers, and water heaters. Its versatility makes it an excellent solution for a wide range of heating applications, ensuring optimal performance across different systems.

In summary, the Amana VR8205 gas valve is characterized by its two-stage operation, durable construction, low-voltage functionality, integrated safety mechanisms, and ease of maintenance. These features combine to offer a reliable, efficient, and flexible solution for modern heating needs.