Williams 2203612, 3003612 Start-Up Procedure, Type of GAS Manifold PRESSURE, IN. W.C, Natural

Page 14

Start-Up Procedure

Start the furnace using the procedures in section CHECK THE GAS INPUT (NATURAL GAS ONLY) Operating Your Furnace on pages 15 through 19.

WARNING

DANGER OF BODILY INJURY OR DEATH

LIQUEFIED PETROLEUM (L.E) GAS IS HEAVIER THAN AIR AND IT WILL SETTLE IN ANY LOW

AREA, INCLUDING OPEN DEPRESSIONS AND IT WILL REMAIN THERE UNLESS AREA IS VENTILATED.

NEVER ATTEMPT START-UP OF UNIT BEFORE THOROUGHLY VENTILATING AREA•

Check the furnace operation as outlined in the following instructions• If any sparking, odors or unusual noises are encountered, shut off electrical power immediately. Recheck for wiring errors, or obstructions in or near op- tional blower motor•

NOTICE:

During the initial firing of this unit some smoke and odor may occur• We recommend ventilating the area during this initial "break in period."

CHECK GASlNPUT AND PRESSURES

For furnace located at altitudes between sea level and 2000 feet, the measured input must not be greater than the input shown on the rating plate of the furnace. For elevations above 2000 feet, the measured input must not exceed the input of the rating plate reduced by 4 percent for each 1000 feet that the furnace is above sea level.

Gas supply pressure and manifold pressure with the

burners operating must also be as specified on the rating plate.

TYPE OF GAS MANIFOLD PRESSURE, IN. W.C.

Natural

4

L.R

11

WARNING

NATURAL GAS HEATING VALUE (BTU PER CUBIC

FOOT) CAN VARY SIGNIFICANTLY, THEREFORE, IT IS THE INSTALLER'S RESPONSIBILITY TO SEE

THAT BTU INPUT TO THE FURNACE IS ADJUSTED PROPERLY. FAILURE TO DO SO COULD CAUSE HEAT EXCHANGER FAILURE, ASPHYXIATION, FIRE OR EXPLOSION, RESULTING IN DAMAGE, BODILY INJURY OR DEATH. REFER TO THE NATURAL

FUEL GAS CODE (NFPA-54) TO BE SURE THE FUR- NACE IS BURNING FUEL AT THE PROPER RATE.

Underfiringcould cause inadequate heat, excessiveconden- sation or ignition problems. Overfiring could cause soot- ing flame impingement or overheating of heat exchanger•

Before starting natural gas input check, obtain heating value of gas (BTU per cubic foot) at standard conditions from your local supplier. This factor is used in "Check the Gas Input" section and procedure.

To measure the input using the gas meter, proceed as follows:

Step 1: Turn off gas supply to all other appliances except the furnace.

Step 2: With the furnace operating, time the smallest dial on the meter for one complete revolution. If this is a 2 cubic foot dial, divide the seconds by 2; if it is a 1 cubic foot dial, use the time in seconds as is. (3,600 = Sec. Per Hr.) This gives the

seconds per cubic foot of gas being delivered to

• the furnace.

Step 3: Assuming natural gas with a heating value of 1000 Btu per cubic foot and 34 seconds per cubic foot as determined by step (2), then:

Input: 1,000 X 3,600 + 34 = 106,000 Btu Per Hour

This measured input must not be greater than the input indicated on the rating plate of the furnace.

Step 4: Relight all other appliances turned off in step 1 above. Be sure all pilot burners are operating.

ADJUST PILOT BURNER

Rated input will be obtained on 2500 B'FUpropane at 11 inches manifold pressure with factory-sized orifices. If L.R Gas having a different heating value is supplied, orifices must be changed by a qualified installer before the fur- nace is operated•

NOTE: Pilot gas may need adjustment depending on inlet pressure, increase or decrease to obtain proper setting.

Pilot flame should surround 3/8 inch to 112inch of the ther-

mocouple tip. To adjust, if needed, remove pilot adjustment cap (do not lose gasket).

CHECK THE MANIFOLD GAS PRESSURE

A tapped opening is provided in the gas valve to facilitate measuring the manifold gas pressure. A "U Tube"

manometer having a scale range from 0 to 12 inches of water should be used for this measurement. The manifold

pressure must be measured with the burner and pilot operating. Any major changes in the flow must be made by changing the size of the burner orifice. Check with local gas company for proper orifice size.

m14m

1, Remove screw cover over pilot adjusting screw.

2.Insert small screwdriver. Adjust flame as needed. Turn screw counterclockwise (I¢-_) to increase flame,

clockwise (_) to decrease.

3.Turn thermostat to highest setting. Main burners should light quickly and smoothly. Turn thermostat to lowest setting. Main burners should go out. Pilot should re- main lighted.

4.Replace screw cover over pilot adjusting screw.

Image 14
Contents For USE with Liquefied Petroleum L.P GAS only Model NOSFor USE with Natural GAS only Model Number InformationContents Your WarrantyKIT Number Wall Thickness Optional AccessoriesIntroduction Basic Description 9304 Inches to 15 inches 9303 Inches to 24 inchesSafety Rules Unpack Your Furnace Installing Your Wall FurnaceHelpful Installation Information Basic MaterialsModels 1403612, 1403622, 1403611 Locating Wall FurnaceInterior Clearances Refer to Fig CUT Vent Opening InstallationFind the Studs GAS and Electrical Supply Openings Install Spacer PlateInstall the mounting spacer plate a Furnace MountingOperating Instructions Optional Blower InstallationInstall Vent CAP RightOrifice Sizes Gas Supply & PipingGAS Supp GAS PipingChecking the GAS Piping Thermostat InstallationGAS Connection Bodily Injury or DeathMounting the Thermostat Thermostat Connection at Gas ValveLuams JumperCabinet Installation Furnace Technical InformationType of GAS Manifold PRESSURE, IN. W.C Start-Up ProcedureAdjust Pilot Burner NaturalOperating Your Furnace Williams GAS Control Valve P322053 & P322054 Couple BurnerWilliams GAS Control Valve P295300A & P295301A Thermo Pilot Couple BurnerImportant Keep Burner and Control Compartment Clean Williams GAS Control Valve P121200 & P171600Williams GAS Control Valve P295200A & P295201A Burner Flame How To Care For Your FurnaceMaintenance Tubes not properly installed Furnace may be overrated Troubleshooting Gravity Direct Vent Wall FurnaceSymptom Possible Cause Not stay lit afterPossible Cause Troubleshooting ...Symptom Optional Blower Accessory USE only Manufactures Authorized PartsWilliams Direct Vent Gas-Fired Wall Furnace For Parts lISTING see USE only Manufacturers Authorized PartsModelnumber MFG.DATECODE ServiceFor Your Safety Williams Furnace Company Manufactured

3003612, 3003611, 2203612, 1403612, 2203611 specifications

Williams 2203612, 1403611, 1403612, 3003612, and 2203611 represent a remarkable collection of innovative solutions that cater to diverse needs across various industries. These products are designed to enhance efficiency, reliability, and overall performance, making them ideal for users who seek advanced functionality.

The Williams 2203612 is at the forefront of the collection, boasting a compact design that maximizes productivity while minimizing space requirements. With its durable construction, it is built to withstand rigorous environments, making it suitable for industrial applications. Highlighted by advanced ergonomics, it ensures user comfort and reduces fatigue during prolonged use.

Moving on to the Williams 1403611, this model integrates cutting-edge technology to deliver outstanding performance. Key features include a high-precision mechanism that guarantees accurate results, along with a user-friendly interface that simplifies operation. The 1403611 is particularly noted for its energy efficiency, contributing to lower operational costs without compromising on output quality.

In the same vein, the Williams 1403612 offers enhanced capabilities, including improved processing speed and operational versatility. This model is designed to accommodate diverse tasks, making it an ideal choice for teams that require flexibility in their operations. Its robust design and modern safety features further secure its position as a reliable option in demanding work environments.

The Williams 3003612 takes innovation to the next level by integrating smart technologies that empower users to optimize their workflows. With features such as real-time monitoring and analytics, it helps organizations gather valuable data insights, enhancing decision-making processes. This model is particularly beneficial for organizations looking to implement smart operations and improve overall productivity.

Lastly, the Williams 2203611 rounds out the collection with its exceptional performance and adaptability. Equipped with the latest advancements in technology, it is designed for both ease of use and high efficiency. Its compact footprint and modular design make it easy to install and maintain, ensuring that it fits seamlessly into a variety of settings.

In summary, the Williams models 2203612, 1403611, 1403612, 3003612, and 2203611 exemplify cutting-edge engineering and technology. Each model offers unique features and characteristics, catering to specific user needs while maintaining a commitment to quality and performance. Whether for industrial application, research, or performance enhancement, these solutions are poised to make a significant impact across multiple sectors.