Bryant 310JAV, 310AAV warranty → -Maximum Capacity of Pipe, → a-Right Side Gas Entry Example

Page 16

Table 4—Maximum Capacity of Pipe*

NOMINAL

 

 

LENGTH OF PIPE (FT)

 

IRON

INTERNAL

 

 

 

 

 

 

 

 

PIPE

DIAMETER

 

 

 

 

 

 

 

 

 

 

 

 

SIZE

(IN.)

10

 

20

30

40

50

(IN.)

 

 

 

 

 

 

 

 

 

1/2

0.622

175

 

120

97

82

73

3/4

0.824

360

 

250

200

170

151

1

1.049

680

 

465

375

320

285

1-1/4

1.380

1400

 

950

770

660

580

1-1/2

1.610

2100

 

1460

1180

990

900

 

 

 

 

 

 

 

 

*Cubic ft of gas per hr for gas pressures of 0.5 psig (14–in. wc) or less and a pressure drop of 0.5–in wc (based on a 0.60 specific gravity gas).

Ref: Table 12.2 NFPA 54-2002.

Connect gas pipe to gas valve using a backup wrench to avoid damaging gas controls.

Use proper length of pipe to avoid stress on gas control manifold. Failure to follow this warning could result in a gas leak resulting in fire, explosion, personal injury, or death.

An accessible manual shutoff valve MUST be installed external to furnace casing and within 6 ft of furnace. A 1/8-in. NPT plugged tapping, accessible for test gage connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual shutoff valve.

NOTE: The gas valve inlet pressure tap connection is suitable to use as test gage connection providing test pressure DOES NOT exceed maximum 0.5 psig (14-in. wc) stated on gas control valve. (See Fig. 50.)

Some installations require gas entry on right side of furnace (as viewed in upflow). (See Fig. 21a.)

Install a sediment trap in riser leading to furnace as shown in Fig 21b. Connect a capped nipple into lower end of tee. Capped nipple should extend below level of gas controls. Place a ground joint union between gas control manifold and exterior manual equip- ment gas shutoff valve. A 1/8-in. NPT plugged tapping, accessible for test gage connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual shutoff valve.

Piping should be pressure and leak tested in accordance with NFGC in the United States or NSCNGPIC in Canada, local, and national plumbing and gas codes before the furnace has been connected. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace.

90° Elbow

2" Nipple

Street Elbow

Gas Valve

A02327

Fig. 21a—Right Side Gas Entry Example

GAS

SUPPLY

MANUAL

SHUTOFF

VALVE (REQUIRED

SEDIMENT TRAP

UNION

A02035

Fig. 21b—Typical Gas Pipe Arrangement

If pressure exceeds 0.5 psig (14-in. wc), gas supply pipe must be disconnected from furnace and capped before pressure test. If test pressure is equal to or less than 0.5 psig (14-in. wc), turn off electric shutoff switch located on furnace gas control valve and accessible manual shutoff valve before test. After all connections have been made, purge lines and check for leakage.

The gas supply pressure shall be within the maximum and minimum inlet supply pressures marked on the rating plate with the furnace burners ON and OFF.

Step 7—Electrical Connections

Blower access panel door switch opens 115-v power to control center. No component operation can occur. Do not bypass or close switch with panel removed. Failure to follow this warning could result in personal injury or death.

See Fig. 24 for field wiring diagram showing typical field 115-v wiring. Check all factory and field electrical connections for tightness.

Field-supplied wiring shall conform with the limitations of 63°F (33°C) rise.

The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70-2002 and Canadian Elec- trical Code CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire, conduit approved for electrical ground or a listed, grounded power cord (where permitted by local code) when installed in accordance with existing electrical codes. Refer to the power cord manufacturer’s ratings for proper wire gage. Do not use gas piping as an electrical ground. Failure to follow this warning could result in electrical shock, fire, or death.

15

Image 16
Contents 310AAV/JAV Induced-Combustion 4-Way Multipoise Furnace Table of Contents → -Dimensional Drawing Safety ConsiderationsInstallation → -Clearances to CombustiblesIntroduction DimensionsCodes and Standards → Electrostatic Discharge ESD Precautions Procedure LocationAIR for Combustion and Ventilation Location Relative to Cooling EquipmentMinimum Free Area of Combustion Air Opening Unconfined SpaceConfined Space BtuhDownflow Installation InstallationUpflow Installation Ventilation from OutdoorsFilter Arrangement Horizontal InstallationAir Ducts Floor and Plenum Opening Dimensions Opening Dimensions → -Duct FlangesDuctwork Acoustical Treatment Furnace Plenum Opening Floor Opening Casing→ -Horizontal Unit Suspension Supply AIR ConnectionsReturn AIR Connections Gas Piping17 3/4″ 22″Upflow Return Air Configurations and Restrictions → a-Right Side Gas Entry Example → -Maximum Capacity of PipeNominal Length of Pipe FT Iron Internal Diameter Size Wiring For Power Cord Installation→ -Electrical Data BOX RelocationBOX Cover Installation For BX Cable InstallationAccessories Venting Carbon Monoxide Poisoning Hazard Ngpic General Venting RequirementsNscngpic Masonry Chimney RequirementsVent Internal Area of Chimney START-UP, ADJUSTMENT, and Safety Check Appliance Application RequirementsAdditional Venting Requirements Sidewall VentingChimney Inspection Chart Adjustments Start-Up ProceduresExample 88,000 Btuh Input Furnace Installed AT 4300 FT See Venting Notes on Horizontal Left Application-Vent Elbow Left Horizontal Left Application-Vent Elbow Right Then UpHorizontal Right Application-Vent Elbow PCB Speed Selection Altitude Derate Multipler for U.S.AAltitude Percent Derate Multiplier Factor Check Safety Controls GAS Rate CU FT/HRChecklist Service and Maintenance ProceduresElectrical Controls and Wiring IntroductionService Label Care and MaintenanceCleaning AND/OR Replacing AIR Filter Filter Size InformationBlower Motor and Wheel Furnace Filter Quantity and Size Casing WidthCleaning Heat Exchanger Position of Igniter to BurnerCleaning Heat Exchanger Cell Sequence of OperationWiring Diagrams TroubleshootingAltitude 725 750 5001 775 800 6000 825 850 875 900675 700 6001 725 750 7000 775 800 825 8509001 10,000900 925 950 975 850 3000 875 900 Canada 925775 800 875 900 925 950750 5001 775 800 6000 825 850 875 900 600 9001 625 650 10,000 675 700 725 Troubleshooting Guide Blocked vent switch used in Chimney Adapter Kit Copyright 2002 Carrier Corporation
Related manuals
Manual 52 pages 27.61 Kb

310JAV, 310AAV specifications

The Bryant 310AAV and 310JAV are high-efficiency air conditioning and heating systems designed for residential and light commercial applications. These models embody Bryant's commitment to delivering reliable comfort solutions while prioritizing energy efficiency and performance.

One of the standout features of the Bryant 310AAV and 310JAV is their impressive Seasonal Energy Efficiency Ratio (SEER) ratings. The higher the SEER, the more efficient the unit is in using electricity to cool your space. The Bryant 310AAV boasts a SEER rating of up to 16, while the 310JAV offers a slightly lower rating. This efficiency translates into cost savings on monthly energy bills while ensuring indoor comfort throughout the year.

Both models utilize advanced technologies, including two-stage heating and cooling capabilities. This means that the systems can adjust their operation based on the heating or cooling needs of a space, providing optimal temperature control while reducing energy waste. The two-stage operation also contributes to quieter operation levels, making these units suitable for residential settings where noise is a concern.

The 310AAV and 310JAV are equipped with variable-speed compressors, which further enhance their efficiency and comfort levels. The variable-speed technology allows the system to operate at different speeds, ensuring consistent temperature management and reducing the frequency of on-and-off cycling. This leads to steadier indoor temperatures and improved humidity control.

In addition to their performance features, Bryant places a strong emphasis on durability and dependability. The units are constructed with high-quality materials that are designed to withstand various environmental conditions. Features such as a weather-resistant cabinet and an efficient coil design help protect the units from wear and tear, ensuring long-lasting performance.

The implementation of environmentally friendly refrigerant options is another characteristic that demonstrates Bryant's commitment to sustainability. Both the 310AAV and 310JAV utilize R-410A refrigerant, which has a lower environmental impact compared to older refrigerants, aligning with modern standards for eco-friendly HVAC systems.

Overall, the Bryant 310AAV and 310JAV represent a blend of efficiency, advanced technology, and durability. With their attractive SEER ratings, two-stage operation, variable-speed capabilities, and commitment to sustainability, these models stand out as excellent choices for homeowners and businesses looking to enhance their heating and cooling solutions while keeping energy consumption in check. Whether for residential comfort or light commercial use, these Bryant units promise reliability and performance for years to come.