11NO PREVIOUS CODE – Stored codes are erased after 72 hours. On RED LED boards stored status codes can also be

erased whenever power (115V or 24V) is interrupted. Run system through a heating or cooling cycle to check system.

12BLOWER ON AFTER POWER UP – (115V OR 24V) – Normal operation.

Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed) or when (R-W opens) during the blower on-delay period.

13LIMIT CIRCUIT LOCKOUT – Lockout occurs if the limit, draft safeguard, flame rollout, or blocked vent switch*(if used) is open longer than 3 minutes. Control will auto-reset after 3 hours. See code 33.

14IGNITION LOCKOUT – System failed to ignite gas and prove flame in 4 attempts.

Control will auto-reset after 3 hours. See status code 34.

21GAS HEATING LOCKOUT – Turn off power and wait 5 minutes to retry. Check for:

-Stuck closed gas valve relay on control.

-Miswire or short to gas valve wire.

22ABNORMAL FLAME-PROVING SIGNAL Flame is proved while gas valve is de-

energized. Inducer will run until fault is cleared. Check for:

- Stuck open or leaky gas valve.

31PRESSURE SWITCH DID NOT CLOSE OR REOPENED – If open longer than 5 minutes, inducer shuts off for 15 minutes before retry. If opens during blower on- delay period, blower will come on for the selected blower off-delay. Check for:

-Proper vent sizing.

-Low inducer voltage (115V).

-Low inlet gas pressure (if LGPS used).

-Inadequate combustion air supply.

-Disconnected or obstructed pressure tubing.

-Defective inducer motor.

-Defective pressure switch.

-Excessive wind.

-Restricted vent.

33LIMIT CIRCUIT FAULT – Indicates the limit, draft safeguard, flame rollout, or

blocked vent switch* (if used) is open.

 

Blower will run for 4 minutes or until open

 

switch remakes whichever is longer. If

 

open longer than 3 minutes, code

 

changes to lockout #13. If open less

 

than 3 min. status code #33 continues

 

to flash until blower shuts off. Flame

 

rollout switch and BVSS requires manual

 

reset. Check for:

 

- Dirty filter or restricted duct system.

 

-

Loose blower wheel.

 

- Defective switch or connections.

 

- Defective blower motor or capacitor.

 

- Inadequate combustion air supply

 

 

(flame rollout switch open).

 

-

Restricted vent.

 

-

Proper vent sizing.

 

-

Excessive wind.

 

34 IGNITION PROVING FAILURE – If flame

 

is not sensed during the trial for ignition

 

period, the control will repeat the ignition

 

NO

sequence 3 more times before lockout

 

#14 occurs. If flame signal is lost during

 

Unplug igniter harness from control and initiate another component test sequence. Check for 115V between pin 1 and NEUTRAL-L2 on the control. Was 115V present for the 15 second period?

Reconnect the R thermostat lead and set thermostat to call for heat. Connect voltmeter across gas valve connections. Does gas valve receive 24V?

YES

Does gas valve open and allow gas to flow?

YES

Do the main burners ignite?

YES

Do the main burners stay on?

NO

Repeat call for heat and check flame sensor current during trial for ignition period. Is the DC microamps below 0.5?

YES

45CONTROL CIRCUITRY LOCKOUT Auto-reset after 1 hour lockout due to:

-Flame circuit failure.

- Gas valve relay stuck open.

-Software check error.

Reset power to clear lockout. Replace control if code repeats.

NO

Replace furnace control.

YES

 

Check for continuity in the harness and igniter.

 

 

 

Replace defective component.

NO

 

Check connections. If OK, replace control.

 

 

 

 

 

 

 

 

Check that all gas valves are turned on.

 

 

 

Replace valve.

 

 

 

Check for:

NO

 

 

- Inadequate flame carryover or rough

 

 

 

 

 

 

ignition.

NO

 

- Low inlet gas pressure.

 

- Proper firing rate.

 

 

 

 

 

 

 

 

 

- Blocked or incorrect carry- over gap.

 

 

 

(.045” nominal)

YES

 

Allow blower to come on and repeat test to

 

 

 

 

 

 

check for intermittent operation.

NO

 

Check connections and retry. If current is

 

near typical value (4.0-6.0 nominal) and

 

 

 

 

 

 

burners will not stay on, replace control.

23PRESSURE SWITCH DID NOT OPEN Check for:

-Obstructed pressure tube.

-Pressure switch stuck closed.

24SECONDARY VOLTAGE FUSE IS OPEN Check for:

-Short circuit in secondary voltage (24V) wiring including thermostat leads. Disconnect thermostat leads to isolate short circuit.

the blower on-delay period, blower will

YES

come on for the selected blower off-delay.

 

 

Check the following items first before proceeding to the next step.

-Gas valve turned off.

-Manual shut-off valve.

-Green/Yellow wire MUST be connected to furnace sheet metal.

-Flame sensor must not be grounded. To determine whether the problem is in the gas valve, igniter, or flame sensor the system can be operated in the component test mode to check the igniter. First remove the R thermostat connection from the control and initiate the component test sequence. Does the igniter glow orange/white by the end of the 15 second warm-up period?

*Blocked vent switch used in Chimney Adapter Kit

Clean flame sensor with fine steel wool and recheck current. Nominal current is 4.0 to 6.0 microamps.

Is current near typical value?

YES

Will main burners ignite and stay on?

YES

Fixed.

NO

Replace electrode.

NO

Replace furnace control.

 

A02106b

Image 44
Contents 310AAV/JAV Induced-Combustion 4-Way Multipoise Furnace Table of Contents → -Dimensional Drawing Safety ConsiderationsInstallation → -Clearances to CombustiblesCodes and Standards DimensionsIntroduction → Electrostatic Discharge ESD Precautions Procedure LocationAIR for Combustion and Ventilation Location Relative to Cooling EquipmentMinimum Free Area of Combustion Air Opening Unconfined SpaceConfined Space BtuhDownflow Installation InstallationUpflow Installation Ventilation from OutdoorsAir Ducts Horizontal InstallationFilter Arrangement Floor and Plenum Opening Dimensions Opening Dimensions → -Duct FlangesDuctwork Acoustical Treatment Furnace Plenum Opening Floor Opening Casing→ -Horizontal Unit Suspension Supply AIR ConnectionsReturn AIR Connections Gas Piping17 3/4″ 22″Upflow Return Air Configurations and Restrictions Nominal Length of Pipe FT Iron Internal Diameter Size → -Maximum Capacity of Pipe→ a-Right Side Gas Entry Example Wiring For Power Cord Installation→ -Electrical Data BOX RelocationAccessories For BX Cable InstallationBOX Cover Installation Venting Carbon Monoxide Poisoning Hazard Ngpic General Venting RequirementsNscngpic Masonry Chimney RequirementsVent Internal Area of Chimney START-UP, ADJUSTMENT, and Safety Check Appliance Application RequirementsAdditional Venting Requirements Sidewall VentingChimney Inspection Chart Example 88,000 Btuh Input Furnace Installed AT 4300 FT Start-Up ProceduresAdjustments See Venting Notes on Horizontal Left Application-Vent Elbow Left Horizontal Left Application-Vent Elbow Right Then UpHorizontal Right Application-Vent Elbow PCB Altitude Percent Derate Multiplier Factor Altitude Derate Multipler for U.S.ASpeed Selection Check Safety Controls GAS Rate CU FT/HRChecklist Service and Maintenance ProceduresElectrical Controls and Wiring IntroductionService Label Care and MaintenanceCleaning AND/OR Replacing AIR Filter Filter Size InformationBlower Motor and Wheel Furnace Filter Quantity and Size Casing WidthCleaning Heat Exchanger Position of Igniter to BurnerCleaning Heat Exchanger Cell Sequence of OperationWiring Diagrams TroubleshootingAltitude 725 750 5001 775 800 6000 825 850 875 900675 700 6001 725 750 7000 775 800 825 8509001 10,000900 925 950 975 850 3000 875 900 Canada 925775 800 875 900 925 950750 5001 775 800 6000 825 850 875 900 600 9001 625 650 10,000 675 700 725 Troubleshooting Guide Blocked vent switch used in Chimney Adapter Kit Copyright 2002 Carrier Corporation
Related manuals
Manual 52 pages 27.61 Kb

310JAV, 310AAV specifications

The Bryant 310AAV and 310JAV are high-efficiency air conditioning and heating systems designed for residential and light commercial applications. These models embody Bryant's commitment to delivering reliable comfort solutions while prioritizing energy efficiency and performance.

One of the standout features of the Bryant 310AAV and 310JAV is their impressive Seasonal Energy Efficiency Ratio (SEER) ratings. The higher the SEER, the more efficient the unit is in using electricity to cool your space. The Bryant 310AAV boasts a SEER rating of up to 16, while the 310JAV offers a slightly lower rating. This efficiency translates into cost savings on monthly energy bills while ensuring indoor comfort throughout the year.

Both models utilize advanced technologies, including two-stage heating and cooling capabilities. This means that the systems can adjust their operation based on the heating or cooling needs of a space, providing optimal temperature control while reducing energy waste. The two-stage operation also contributes to quieter operation levels, making these units suitable for residential settings where noise is a concern.

The 310AAV and 310JAV are equipped with variable-speed compressors, which further enhance their efficiency and comfort levels. The variable-speed technology allows the system to operate at different speeds, ensuring consistent temperature management and reducing the frequency of on-and-off cycling. This leads to steadier indoor temperatures and improved humidity control.

In addition to their performance features, Bryant places a strong emphasis on durability and dependability. The units are constructed with high-quality materials that are designed to withstand various environmental conditions. Features such as a weather-resistant cabinet and an efficient coil design help protect the units from wear and tear, ensuring long-lasting performance.

The implementation of environmentally friendly refrigerant options is another characteristic that demonstrates Bryant's commitment to sustainability. Both the 310AAV and 310JAV utilize R-410A refrigerant, which has a lower environmental impact compared to older refrigerants, aligning with modern standards for eco-friendly HVAC systems.

Overall, the Bryant 310AAV and 310JAV represent a blend of efficiency, advanced technology, and durability. With their attractive SEER ratings, two-stage operation, variable-speed capabilities, and commitment to sustainability, these models stand out as excellent choices for homeowners and businesses looking to enhance their heating and cooling solutions while keeping energy consumption in check. Whether for residential comfort or light commercial use, these Bryant units promise reliability and performance for years to come.